Plan Review Details - Permit 07080521
Plan Review Stops For Permit 07080521
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-13 Cont ID  
Sent By jwitmer Date 2007-11-13 Time 09:04 Rev Time 0.77
Received By jwitmer Date 2007-11-13 Time 09:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-17 Cont ID  
Sent By jwitmer Date 2007-09-17 Time 20:40 Rev Time 1.55
Received By jwitmer Date 2007-09-17 Time 20:40 Sent To  
Notes
2007-09-17 21:03:25PALM BEACH MOTOR CARS LIMITED INC.
 JAGUAR LOUNGE REMODEL
 SEPT 17,2007
  
 BUILDING PLAN REVIEW
 PERMIT: 07080521
 ADD: 915 S DIXIE HWY
 CONT: POPPER & ASSOCIATES
 TEL: (561)719-7131
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET A-101 INDICATES THE BUILDING TYPE TO BE TYPE
 IV UNPROTECTED UNSPRINKLED, PLEASE CONSULT WITH TABLE
 601 THIS IS HEAVY TIMBER CONSTRUCTION UNDERTHE 2004
 FBC. PLEASE PROVIDE THE FOLLOWING INFORMATION,110.2*
 W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT IS
 REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED. 2004 FBC W/ 2006 REVISIONS
 TO WHAT LEVEL IS THIS ALTERATION UNDER THE 2004
 EXISTING BUILDING CODE?
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H ) NUMBER OF FLOORS
 I ) SQ. FT. FOOTPRINTOF TOTAL BUILDING
  
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-11-07 Cont ID  
Sent By dpalmer Date 2007-11-07 Time 16:59 Rev Time 0.00
Received By dpalmer Date 2007-11-07 Time 16:59 Sent To  
Notes
2007-11-07 17:00:01STAMPED ELECTRICAL SHEETS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-11 Cont ID  
Sent By dpalmer Date 2007-09-11 Time 15:01 Rev Time 0.00
Received By dpalmer Date 2007-09-11 Time 14:29 Sent To  
Notes
2007-09-11 15:02:04*** DENIED ***
  
  
 1) NOTE: PLEASE SEE 13-101, 13-415.1.1,.1.2 FOR
 REQUIRED LIGHTING CONTROLS FOR NEW LIGHTING.
 PLEASE EXPLAIN HOW METHOD *A* IS BEING USED FOR WHOLE
 BUILDING WHEN THIS IS AN EXISTING CONDITIONED SPACE.
 *FOR ELECTRICAL, ONLY NEED TO MEET THE MAXIMUM
 PERFORMANCE LEVELS FOR LIGHTING DENSITIES PER 13-415.2
 AND TABLES 415.2.C.1, 415.2.B.1.
 THIS CAN BE SHOWN ON TABLE OF SOME SORT ON PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-11-15 Cont ID  
Sent By mwennerg Date 2007-11-15 Time 13:37 Rev Time 0.00
Received By mwennerg Date 2007-11-15 Time 13:37 Sent To  
Notes
2007-11-15 13:38:28E-MAILED CORRECTION RESPONSES ON 11/15/07.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-11-09 Cont ID  
Sent By mwennerg Date 2007-11-09 Time 09:55 Rev Time 0.00
Received By mwennerg Date 2007-11-09 Time 09:55 Sent To  
Notes
2007-11-09 09:56:52***DENIED***
 A RESPONSE LETTER WAS ATTACHED TO THE PLANS EXLUDING
 FIRE REVIEW COMMENTS. NO CHANGES OR NOTES ADDED TO
 DRAWINGS.
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 2) IT APPEARS THAT FIRE ALARM EQUIPMENT IS SHOWN ON
 ELECTRICAL SHEET 101. IF WORK IMPACTS EXISTING BUILDING
 FIRE PROTECTION SYSTEM, SEPARATE SHOP DRAWINGS AND
 PERMITS MAY BE REQUIRED FOR FIRE ALARM REMODEL.
  
 3) THE EXIT DOOR FROM THE STAIRWELL WOULD SEEM TO
 OBSTRUCT THE EXTERIOR EXIT DOOR. PLEASE CLARIFY IF
 STAIR DOOR IS PROVIDED WITH A UL LISTED CLOSER THAT
 FUNCTIONS PROPERLY.
  
 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH ALL REQUIREMENTS OF NFPA 241.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-09-28 Cont ID  
Sent By mwennerg Date 2007-09-28 Time 13:11 Rev Time 0.00
Received By mwennerg Date 2007-09-28 Time 13:11 Sent To  
Notes
2007-09-28 13:19:21***DENIED***
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 2) IT APPEARS THAT FIRE ALARM EQUIPMENT IS SHOWN ON
 ELECTRICAL SHEET 101. IF WORK IMPACTS EXISTING BUILDING
 FIRE PROTECTION SYSTEM, SEPARATE SHOP DRAWINGS AND
 PERMITS MAY BE REQUIRED FOR FIRE ALARM REMODEL.
  
 3) THE EXIT DOOR FROM THE STAIRWELL WOULD SEEM TO
 OBSTRUCT THE EXTERIOR EXIT DOOR. PLEASE CLARIFY IF
 STAIR DOOR IS PROVIDED WITH A UL LISTED CLOSER THAT
 FUNCTIONS PROPERLY.
  
 4) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH ALL REQUIREMENTS OF NFPA 241.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-24 Cont ID  
Sent By adarroug Date 2007-10-24 Time 09:11 Rev Time 0.00
Received By adarroug Date 2007-10-24 Time 09:11 Sent To  
Notes
2007-11-07 17:51:33MOVED TO BOB # 5.RB
2007-11-07 13:41:55TO "COMM" BD#51
2007-10-24 09:12:09WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-28 Cont ID  
Sent By lmartine Date 2007-09-28 Time 13:52 Rev Time 0.00
Received By lmartine Date 2007-08-16 Time 14:20 Sent To  
Notes
2007-09-11 08:35:30TO "COMM" BD#28
2007-08-16 14:25:42WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-13 Cont ID  
Sent By rregueir Date 2007-11-13 Time 07:47 Rev Time 0.00
Received By rregueir Date 2007-11-13 Time 07:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-20 Cont ID  
Sent By rregueir Date 2007-09-20 Time 18:07 Rev Time 0.00
Received By rregueir Date 2007-09-20 Time 17:56 Sent To  
Notes
2007-09-20 18:07:06REVIEW #: 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE DESIGN PROFESSIONAL OR THE OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THE FLORIDA BUILDING CODE,
 EXISTING BUILDING. SEE FBC,EB 301.5
  
 2. ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY SHALL
 BE PROVIDED WITH VENTILATION IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, MECHANICAL. FBC, EB 609.1
  
 3. PROVIDE VENTILATION CALCULATIONS SHOWING OCCUPANCY
 CLASSIFICATION, OCCUPANT LOAD, OUTDOOR AIR REQUIRED AND
 OUTDOOR AIR PROVIDED PER FBC,M TABLE 403.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]


Account Summary | Usage Policy | Privacy Policy