Plan Review Stops For Permit 07080517 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-11-30 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2007-11-30 |
Time |
09:39 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2007-11-30 |
Time |
06:58 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-11-09 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2007-11-09 |
Time |
15:56 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2007-11-09 |
Time |
15:56 |
Sent To |
|
|
Notes |
2007-11-09 16:50:17 | 2004 FBC W/2007 REVISIONS | | CONSTRUCT A NEW SINGLE FAMILY RESIDENCE | | | | DENIED BY BUILDING | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2) IMPACT FEES MUST BE PAID TO PALM | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | COPY OF RECEIPT SUBMITTED TO CITY OF | | WEST PALM BEACH BUILDING DEPARTMENT, | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | 3) THE DESIGN PRESSURES LISTED IN THE PRODUCT APPROVALS | | FOR THE 9' AND 16' GARAGE DOORS ARE LESS THAN THE | | REQUIRED COMPONENT AND CLADDING PRESSURES SPECIFIED ON | | SHEET A4.0 OF THE PLANS. PLEASE CORRECT. FAC RULE 9B-72 | | AND FBC R301.2.1 SEE COMMENT # 12 OF PREVIOUS BUILDING | | REVIEW. | | | | 4) HAVE THE PRIVATE PROVIDER REVIEW AND PLACE THEIR | | STAMP ON THE PRODUCT APPROVALS THAT ARE REQUIRED BY FAC | | RULE 9B-72.. SEE FS 553.791(6). | | | | - ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-08-30 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2007-08-30 |
Time |
10:10 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2007-08-30 |
Time |
07:26 |
Sent To |
|
|
Notes |
2007-08-30 17:21:28 | 2004 FBC WITH 2007 SUPPLEMENT | | CONSTRUCT NEW SINGLE FAMILY RESIDENCE | | | | DENIED BY BUILDING | | | | 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | MUST BE SUBMITTED BEFORE A | | PERMIT CAN BE ISSUED. | | | | 2)SUBMIT A COPY OF THE PAID RECEIPT FOR THE PALM | | BEACH COUNTY IMPACT FEES. | | | | 3) REVISE THE CODE EDITION SPECIFIED ON SHEET T1 TO THE | | 2004 FBC WITH 2007 SUPPLEMENT. | | | | 4) THE REAR QUADRANT OF THE STRUCTURE ABUTS A LAKE AND | | A GOLF COURSE, WHICH HAS EXPOSURE C-TYPE TERRAIN FOR A | | DISTANCE OF MORE THAN 600 FEET. THEREFORE,THE | | STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C. PER | | R301.2.1.4 EXPOSURE CATEGORY. 3. EXPOSURE C. OPEN | | TERRAIN WITH SCATTERED OBSTRUCTIONS, INCLUDING SURFACE | | UNDULATIONS OR OTHER IRREGULARITIES, HAVING HEIGHTS | | GENERALLY LESS THAN 30 FEET (9144 MM) EXTENDING MORE | | THAN 1,500 FEET (457.2 M) FROM THE BUILDING SITE IN ANY | | QUADRANT. THIS EXPOSURE SHALL ALSO APPLY TO ANY | | BUILDING LOCATED WITHIN EXPOSURE B-TYPE TERRAIN WHERE | | THE BUILDING IS DIRECTLY ADJACENT TO OPEN AREAS OF | | EXPOSURE C-TYPE TERRAIN IN ANY QUADRANT FOR A DISTANCE | | OF MORE THAN 600 FEET (182.9 M). SHORT-TERM (LESS THAN | | TWO YEAR) CHANGES IN THE PRE-EXISTING TERRAIN EXPOSURE, | | FOR THE PURPOSES OF DEVELOPMENT, SHALL NOT BE | | CONSIDERED OPEN FIELDS. WHERE DEVELOPMENT BUILD OUT | | WILL OCCUR WITHIN THREE YEARS AND THE RESULTANT | | CONDITION WILL MEET THE DEFINITION OF EXPOSURE B, | | EXPOSURE B SHALL BE REGULATING FOR THE PURPOSE OF | | PERMITTING. THIS CATEGORY INCLUDES FLAT OPEN COUNTRY, | | GRASSLANDS AND OCEAN OR GULF SHORELINES. THIS CATEGORY | | DOES NOT INCLUDE INLAND BODIES OF WATER THAT PRESENT A | | FETCH OF 1 MILE (1.61 KM) OR MORE OR INLAND WATERWAYS | | OR RIVERS WITH A WIDTH OF 1 MILE (1.61 KM) OR MORE (SEE | | EXPOSURE D). PLEASE REVISE THE EXPOSURE CATEGORY | | SPECIFIED ON THE PLANS AND REVISE THE COMPONENT AND | | CLADDING PRESSURES TO EXPOSURE C. | | | | 5) PLEASE INDICATE THAT THE INTERNAL PRESSURE | | COEFFICIENT ON T1 IS FOR BOTH POSITIVE AND NEGATIVE | | PRESSURES BY ADDING THE PLUS AND MINUS SIGNS. SEE | | ASCE7-02. | | | | 6)SUBMIT A DRAINAGE PLAN SHOWING COMPLIANCE WITH | | R401.3 DRAINAGE. | | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER | | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS | | TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO | | DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE | | GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM | | OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 | | MM). | | EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER | | PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL | | WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE | | PROVIDED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. | | | | 7) TWO OF THE STEEL COLUMNS ON SHEET A1.0 DO NOT HAVE | | THE BASE CONNECTIONS SPECIFIED ON THE FOUNDATION PLAN. | | | | 8) SPECIFY THE LENGTH/EMBED DEPTH OF THE 5/8" EXPANSION | | BOLTS IN THE CONNECTION DETAIL G ON A3.0. | | | | 9) SPECIFY THE WINDLOAD PRESSURES FOR THE EXTERIOR DOOR | | AT THE MASTER BEDROOM. | | | | 10) PLEASE CLARIFY IF THE STEEL COLUMN TO TIE BEAM | | CONNECTION DETAIL ON A7 IS FOR THE THE 6 X 2 INCH | | COLUMNS BETWEEN THE LIVING ROOM WINDOWS. THE DETAIL | | SHOWS A 4 X 4 INCH STEEL COLUMN. | | | | 11) THE FL PRODUCT APPROVAL NUMBER LISTED IN THE ANCHOR | | SCHEDULE ON A3 FOR THE USP RT16 HURRICANE TIE IS | | INCORRECT. THE FL NUMBER FOR THIS CONNECTOR IS FL565, | | THE ONE LISTED IS FOR THE RT16 FLAT AND TWIST STRAP | | CONNECTORS. PLEASE CORRECT. | | | | 12) THE DOUBLE OUT SWING FRONT DOORS, AS WELL AS, SOME | | OF THE OTHER PRODUCTS MAY NOT MEET THE INCREASED | | COMPONENT AND CLADDING PRESSURES OF THE EXPOSURE C | | CATEGORY. PLEASE REVIEW PRODUCT APPROVALS FOR ADEQUATE | | PRESSURES. | | | | 13) SUBMIT RATIONAL ANALYSIS FROM A FLORIDA LICENSED | | ENGINEER FOR THE EXTERIOR 18" X 18" ACCESS DOOR TO THE | | WHIRLPOOL TUB MOTOR SHOWING THAT THE DOOR IS CAPABLE OF | | WITH STANDING THE WINDLOAD PRESSURES. SPECIFY THE | | ANCHOR TYPE, EMBED DEPTH, ETC. PROVIDE MANUFACTURER'S | | SPECIFICATIONS. | | | | 14) SUBMIT PRODUCT APPROVALS FOR THE LARGE MISSLE | | IMPACT STRUCTURAL WINDOW MULLIONS. THE ONLY ONES | | SUBMITTED ARE BAY WINDOW MULLIONS. | | | | 15) THE 54 X 96 INCH @ THE DINING ROOM AND 60 X 86 INCH | | @ THE MASTER BATH ARCH TOP FIXED GLASS WINDOWS AND THE | | 92 X 98 INCH FIXED GLASS WINDOW @ THE MASTER BED ROOM | | EXCEED THE SIZE LIMITATIONS OF THE PRODUCT APPROVAL FOR | | THE PGT PW-701 WINDOWS. PLEASE CORRECT. | | | | 16) SUBMIT A SIGNED AND SEALED ANALYSIS REPORT OF TIE | | BEAM CB-4 ABOVE THE BAY WINDOW AND THE ECCENTRICALLY | | LOADED COLUMNS FROM A FLORIDA LICENSED ENGINEER. THE | | ALUMINUM CORNER POSTS FOR THE BAY WINDOWS SHOWN ON A2.O | | DO NOT PROVIDE ANY SUPPORT FOR THE GRAVITY LOADS OF THE | | BEAM. PROVIDE A STEEL PLACEMENT DETAIL FOR THE BEAM AND | | SUPPORTING COLUMN REINFORCEMENT. FBC * 106.1.2 | | | | -ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2008-05-07 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2008-05-07 |
Time |
07:06 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2008-05-07 |
Time |
06:55 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2007-11-08 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-11-08 |
Time |
08:26 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-11-08 |
Time |
07:53 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-08-21 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-08-21 |
Time |
16:07 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-08-21 |
Time |
07:09 |
Sent To |
P |
|
Notes |
2007-08-21 12:41:55 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | FLORIDA STATUTES 1/2007,2004 FBC AS AMENDED, CHAPTER | | 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | THESE COMMENTS REFER TO SHEET A8.0. | | | | 1} THERE IS NO EQUIPMENT GROUND SHOWN BEING RAN WITH | | THE FEEDER FROM PANEL "B" TO THE POOL PANEL.AN | | EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED FROM | | THE FIRST MEANS OF DISCONNECT TO THE PANEL PER 250.110, | | SIZED PER 250.122. SEE RISER DIAGRAM. | | | | 2} THERE IS A 20 AMP CIRCUIT,#22, IN PANEL "A" FOR | | THE POOL LIGHTS, AND A 15 AMP CIRCUIT, NO NUMBER GIVEN, | | FOR POOL LIGHTS IN SUB PANEL"D". IT IS NOT CLEAR IF | | THIS IS A DUPLICATION OR IF THERE ARE TWO SEPARATE | | CIRCUITS FOR POOL LIGHTS. SEE ARTICLE 408.4 2005 NEC | | WHICH ASKS FOR CLARITY IN THE SCHEDULES. | | | | 3} CIRCUIT # 21, PANEL "A", DINING ROOM OUTLETS, ARE ON | | A 15 AMP CIRCUIT. TO COMPLY WITH 210.52(B)(1) FOR SMALL | | APPLIANCE CIRCUITS, THIS MUST BE A 20 AMP CIRCUIT. | | | | 4} CIRCUIT # 40 IN BOTH PANELS INDICATES A LOAD OF 2.3 | | KW. IN VIOLATION OF 210.23, LIMITING THE CIRCUIT | | AMPACITY TO 80% OF THE CIRCUIT RATING ( AT 20 AMPS). | | LIST THE CIRCUIT RATING AND CONDUCTOR SIZE SO | | COMPLIANCE WITH 310.16 MAY BE REVIEWED. NOTE: THE HIGH | | HATS LISTED ON THOSE CIRCUITS ARE NOT REQUIRED TO BE ON | | A SEPARATE CIRCUIT AND MAY BE PUT ON OTHER LIGHTING AND | | RECEPTACLE CIRCUITS. | | | | 5} LOCATE PANEL "D" ON THE PLAN. 106.3.5.4(8), FBC AS | | AMENDED. | | | | 6} SHEET A2.0 INDICATES IN A NOTE THATAHU #3,IN | | "HER" CLOSET, MASTER BEDROOM, IS CEILING HUNG. SHEET M1 | | SYSTEM SPECIFICATIONS INDICATE THERE IS A 30 AMP FUSE | | IN THE AIR HANDLER. OVERCURRENT PROTECTION IN A CLOTHES | | CLOSET IS IN VIOLATION OF 240.24(D). ALSO THERE IS A | | DISCONNECT IN THE CLOSET AND IT IS UNCLEAR IF IT | | CONTAINS OCP. IF THE INSTALLATION IS INTENDED TO BE IN | | THE ATTIC THAN IN THE CLOSET, RECEPTACLE PER 210.63, IS | | REQUIRED. | | | | 7} THE ENGINEERSNAME ON THE PLAN PROVIDER AFFIDAVIT | | AND SEAL, IS DIFFERENT THAN THE ONE ON FILE WITH DBPR. | | PLEASE CLARIFY. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2008-10-03 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-10-03 |
Time |
16:07 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-10-03 |
Time |
16:07 |
Sent To |
Z |
|
Notes |
2008-10-03 16:07:56 | TO"Z" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2008-08-26 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-08-26 |
Time |
08:57 |
Rev Time |
0.00 |
Received By |
tgordon |
Date |
2008-08-26 |
Time |
08:57 |
Sent To |
Z |
|
Notes |
2008-08-26 08:57:44 | TO "ZONING" BOX. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2008-05-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-05 |
Time |
09:06 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-05 |
Time |
09:06 |
Sent To |
E |
|
Notes |
2008-05-05 09:07:47 | TO "BTROBAUG" DESK/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2008-04-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-04-24 |
Time |
15:31 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-04-24 |
Time |
15:31 |
Sent To |
M |
|
Notes |
2008-04-24 15:32:20 | TO "M" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-11-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-19 |
Time |
10:16 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-19 |
Time |
10:16 |
Sent To |
P |
|
Notes |
2007-11-19 10:17:09 | TO "P" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-11-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-02 |
Time |
11:02 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-02 |
Time |
11:02 |
Sent To |
Z |
|
Notes |
2007-11-02 11:02:46 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-08-30 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2007-08-30 |
Time |
10:10 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2007-08-16 |
Time |
15:57 |
Sent To |
|
|
Notes |
2007-08-16 15:57:10 | TO "SFR" "Z" |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
2 |
Status |
P |
Date |
2008-10-06 |
|
|
Cont ID |
|
Sent By |
rkussner |
Date |
2008-10-06 |
Time |
12:19 |
Rev Time |
0.00 |
Received By |
rkussner |
Date |
2008-10-06 |
Time |
12:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
L |
LANDSCAPING |
Rev No |
1 |
Status |
F |
Date |
2008-08-27 |
|
|
Cont ID |
|
Sent By |
rkussner |
Date |
2008-08-27 |
Time |
10:02 |
Rev Time |
0.00 |
Received By |
rkussner |
Date |
2008-08-27 |
Time |
10:02 |
Sent To |
|
|
Notes |
2008-08-27 10:04:52 | LANDSCAPE ***FAILED*** | | | | PROVIDE SIZE AND SPACING FOR ALL PROPOSED PLANT | | MATERIAL. | | | | CONTACT INFORMATION: | | ROBERT KUSSNER @ 822-1462 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
2008-04-25 08:23:02 | REVISED MECH. PLAN. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2007-11-09 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-11-08 |
Time |
11:29 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-11-08 |
Time |
11:28 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-08-20 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-08-20 |
Time |
14:06 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-08-20 |
Time |
14:06 |
Sent To |
E |
|
Notes |
2007-08-20 15:22:33 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER | | 1 CITY OF WEST PALM BEACH AMENDMENTS. | | | | *** DENIED *** | | 1) SEE F.S. 553.719 (4) (C) (C) FOR PRIVATE PROVIDER | | ACKNOWLEDMENT MISSING.AN ACKNOWLEDGMENT FROM THE FEE | | OWNER IN SUBSTANTIALLY THE FOLLOWING FORM: | | I HAVE ELECTED TO USE ONE OR MORE PRIVATE | | PROVIDERS TO PROVIDE BUILDING CODE PLANS REVIEW AND/OR | | INSPECTION SERVICES ON THE BUILDING OR STRUCTURE THAT | | IS THE SUBJECT OF THE ENCLOSED PERMIT APPLICATION, AS | | AUTHORIZED BY S. 553.791, FLORIDA STATUTES. I | | UNDERSTAND THAT THE LOCAL BUILDING OFFICIAL MAY NOT | | REVIEW THE PLANS SUBMITTED OR PERFORM THE REQUIRED | | BUILDING INSPECTIONS TO DETERMINE COMPLIANCE WITH THE | | APPLICABLE CODES, EXCEPT TO THE EXTENT SPECIFIED IN | | SAID LAW. INSTEAD, PLANS REVIEW AND/OR REQUIRED | | BUILDING INSPECTIONS WILL BE PERFORMED BY LICENSED OR | | CERTIFIED PERSONNEL IDENTIFIED IN THE APPLICATION. THE | | LAW REQUIRES MINIMUM INSURANCE REQUIREMENTS FOR SUCH | | PERSONNEL, BUT I UNDERSTAND THAT I MAY REQUIRE MORE | | INSURANCE TO PROTECT MY INTERESTS. BY EXECUTING THIS | | FORM, I ACKNOWLEDGE THAT I HAVE MADE INQUIRY REGARDING | | THE COMPETENCE OF THE LICENSED OR CERTIFIED PERSONNEL | | AND THE LEVEL OF THEIR INSURANCE AND AM SATISFIED THAT | | MY INTERESTS ARE ADEQUATELY PROTECTED. I AGREE TO | | INDEMNIFY, DEFEND, AND HOLD HARMLESS THE LOCAL | | GOVERNMENT, THE LOCAL BUILDING OFFICIAL, AND THEIR | | BUILDING CODE ENFORCEMENT PERSONNEL FROM ANY AND ALL | | CLAIMS ARISING FROM MY USE OF THESE LICENSED OR | | CERTIFIED PERSONNEL TO PERFORM BUILDING CODE INSPECTION | | SERVICES WITH RESPECT TO THE BUILDING OR STRUCTURE THAT | | IS THE SUBJECT OF THE ENCLOSED PERMIT APPLICATION. | | | | 2) ENGINEERS NAME ON PRIVATE PROVIDER AFFIDAVIT JOHN F. | | DESNOYERS, IS NOT THE SAME NAME ON LICENSE # 47885 | | (JEAN F. DESNOYERS) PLEASE CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL: [email protected]. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2007-11-26 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-11-26 |
Time |
15:43 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-11-26 |
Time |
15:43 |
Sent To |
B |
|
Notes |
2007-11-26 15:47:04 | CONTRACTOR INFORMATION | | (SHEET A2 IS INDICATING GAS APPLIANCES) | | NOTE: GAS PERMIT REQUIRED. GAS OR PLUMBING CONTRACTOR | | TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL GAS | | INSPECTIONS TO BE COMPLETE BEFORE FINAL INSPECTION. | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2007-11-09 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-11-09 |
Time |
14:57 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-11-09 |
Time |
08:46 |
Sent To |
B |
|
Notes |
2007-11-09 09:33:13 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS | | TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | PLUMBING PLAN REVIEW: | | DENIED 2ND TIME: | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE ON THE | | RESUBMITTED PLANS. | | | | 1. SHEET A6.0 PLUMBING RISER DIAGRAM: THE BIDET IN THE | | MASTER BATH IS NOT VENTED. PER *901.2.1, VENTING | | REQUIRED. | | | | 2. ENERGY CALCULATIONS WERE NOT RESUBMITTED WITH PLANS | | PLEASE RESUBMIT ENERGY CALULATIONS WITH WATER HEATING | | REQUIREMENTS PER | | CHAPTER 13 ENERGY EFFICIENCY SECTION 13-101.0 GENERAL. | | THIS CODE IS A STATEWIDE UNIFORM CODE AND SHALL NOT BE | | MADE MORE STRINGENT OR LENIENT BY LOCAL GOVERNMENT. THE | | CODE PROVIDES FOR A UNIFORM STANDARD OF ENERGY | | EFFICIENCY BY, AT A MINIMUM, SETTING FORTH MINIMUM | | REQUIREMENTS FOR EXTERIOR ENVELOPES, LIGHTING, | | ELECTRICAL DISTRIBUTION, AND SELECTION OF HEATING, | | LIGHTING, VENTILATION, AIR CONDITIONING AND SERVICE | | WATER HEATING SYSTEMS. IT SHALL APPLY TO ALL NEW | | BUILDINGS, TO ADDITIONS TO EXISTING BUILDINGS AND | | MANUFACTURED HOMES, TO RENOVATIONS TO EXISTING | | BUILDINGS, BOTH PUBLIC AND PRIVATE, WITH CERTAIN | | EXCEPTIONS, TO CHANGES OF OCCUPANCY TYPE, TO THE | | SITE-INSTALLED COMPONENTS AND FEATURES OF A | | MANUFACTURED HOMES AT THEIR FIRST SET-UP, AND TO THE | | INSTALLATION OR REPLACEMENT OF BUILDING SYSTEMS AND | | COMPONENTS WITH NEW PRODUCTS FOR WHICH THERMAL | | EFFICIENCY STANDARDS ARE SET BY THIS CODE. NEW | | BUILDINGS, WITH EXCEPTION OF THOSE EXEMPTED BELOW, AND | | IN ACCORDANCE WITH THE SPECIFIC EXCEPTIONS OF | | INDIVIDUAL SECTIONS SHALL BE DESIGNED TO COMPLY WITH | | SUBCHAPTER 13-4 OR 13-6 OF THIS CODE. | | | | **THE FOLLOWING IS CONTRACTOR INFORMATION ONLY BECAUSE | | SHEET A2.0 IS INDICATING GAS APPLIANCES. | | | | NOTE: GAS PERMIT REQUIRED. PLUMBING OR GAS CONTRACTOR | | TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL GAS | | INSPECTIONS TO BE COMPLETE BEFORE FINAL INSPECTION. | | | | END OF COMMENTS: | | | | REVIEW BY: MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-08-23 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-08-23 |
Time |
08:17 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-08-23 |
Time |
08:17 |
Sent To |
B |
|
Notes |
2007-08-23 09:38:41 | DENIED | | REFERENCE: | | ** FBC-2004 PLUMBING. | | ** FBC-2004 CHAPTER 1, THE CITY OF | | WEST PALM BEACH AMENDMENTS. | | ** FLORIDA ADMINISTRATIVE CODE. | | ** FLORIDA STATUTES. | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | 1. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 | | RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A | | PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING | | ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT | | LOCATIONS. | | NOTE: NOT ALL WASTE PIPES OR TRAPS ARE SIZED ON SHEET | | A6.0 PLUMBING RISER DIAGRAM. PLEASE CORRECT THIS ON THE | | RESUBMITTAL. | | | | 2. SHEET A6.0 SANITARY PLUMBING RISER DIAGRAM DOES NOT | | REFLECT THE FLOOR PLAN ON SHEET A2.0. PER FBC-2004 | | CHAPTER 1 THE CITY OF WEST PALM BEACH AMENDMENTS | | SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | PROVISIONS OF THIS CODE | | AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, | | AS DETERMINED BY THE BUILDING OFFICIAL. | | | | A} THE WASHING MACHINE AND LAUNDRY TRAY ARE BEING | | INDICATED IN THE WRONG PLACE. | | | | B} BATHROOM OFF BEDROOM 2 THE TUB/SHOWER IS | | INCORRECTLY IDENIFIED AS A SHOWER AND LOCATED IN THE | | WRONG PLACE. ALSO THE LAV IS LOCATED IN THE WRONG | | PLACE. | | | | 3. SHEET A6.0 SANITARY PLUMBING RISER DIAGRAM THE | | WASHING MACHINE NEEDS A TRAP PER FBC-2004 PLUMBING, | | SECTION 1002.1 ALSO PLEASE INDICATE THE REQUIRED | | STANDPIPE FOR THE WASHING MACHINE PER FBC-2004 | | PLUMBING, SECTION 802.4. | | | | 4. SHEET A6.0 SANITARY PLUMBING RISER DIAGRAM MASTER | | BATH W. POOL TUB PER FBC-2004 PLUMBING, TABLE 906.1 A | | VENT IS REQUIRED FOR THE W. POOL TUB TRAP BECAUSE IT IS | | OVER 6 FEET FROM THE VENT. | | | | 5. SHEET A6.0 SANITARY PLUMBING RISER DIAGRAM | | DISHWASHER DRAIN. PER FBC-2004 PLUMBING SECTION 802.1.6 | | DOMESTIC DISHWASHING MACHINES SHALL DISCHARGE | | INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK INTO A | | STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION | | 802.2 OR DISCHARGE INTO A WYE-BRANCH FITTING ON THE | | TAILPIECE OF THE KITCHEN SINK OR THE DISHWASHER | | CONNECTION OF A FOOD WASTE GRINDER. PLEASE CLARIFY HOW | | THE DISHWASHER WILL DRAIN. IF IT IS THE INTENT TO USE A | | STANDPIPE PLEASE CLEARLY INDICATE AND SIZE THE | | STANDPIPE ON THE RESUBMITTAL. | | | | 6. SHEET A6.0 SANITARY PLUMBING RISER DIAGRAM POWDER | | ROOM: THE 2 INCH LOOP VENT BEING INDICATED FROM THE TOP | | OF THE WATER CLOSET IS NOT FEASIBLE OR REQUIRED. PLEASE | | DELETE THIS VENT ON THE RESUBMITTAL. | | | | **THE FOLLOWING IS CONTRACTOR INFORMATION ONLY BECAUSE | | SHEET A2.0 IS INDICATING GAS APPLIANCES | | | | NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- | | TOR TO SUBMIT PLANS WITH PERMIT APPLICA- | | TION. ALL GAS INSPECTIONS TO BE COMPLETE | | BEFORE FINAL INSPECTION. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL= [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2007-11-07 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-11-07 |
Time |
14:16 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-11-07 |
Time |
14:16 |
Sent To |
E |
|
Notes |
2007-11-07 14:17:40 | ***APPROVED - RESUB #1*** | | | | FRONT SETBACK OK PER PB CASE NO. 993SSS | | | | TYPICAL LANDSCAPE PLANTING TYPE AND QUANTITY PROVIDED. | | | | | | | | SENT TO "E" - BT |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2007-08-20 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-08-20 |
Time |
09:17 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-08-20 |
Time |
09:17 |
Sent To |
E |
|
Notes |
2007-08-20 09:25:35 | ***FAILED*** | | | | | | 1)DOES NOT MEET FRONT SETBACK REQUIREMENT OF 25'. | | | | 2)PROVIDE SETBACK DIMENSIONS FROM A/C EQUIPMENT TO | | THE PROPERTY LINES. | | | | 3)SOME DIMENSIONS ON SHEET A4.0 ARE NOT LEGIBLE. | | ELEVATION DIMENSIONS TO BE MEASURED FROM GRADE. | | | | 4)PLEASE PROVIDE A LANDSCAPE PLAN SHOWING COMPLIANCE | | WITH SECTION 94-442 OF THE CITY OF WEST PALM BEACH | | ZONING AND LAND DEVELOPMENT REGULATIONS. | | | | 5)PROVIDE TOTAL SQUARE FOOTAGE OF PROPOSED DRIVEWAY | | WITHIN THE FRONT YARD (FROM FRONT PROPERTY LINE TO THE | | FRONT OF THE PRINCIPAL STRUCTURE). | | | | NOTE:MUST MAINTAIN THE LESSOR OF 1,000 SQ.FT. OR 75% | | OF THE FRONT YARD AS LANDSCAPED MATERIAL. | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | TECHNICIAN | | (561)805-6720 | | |
|
|