Plan Review Details - Permit 07080515
Plan Review Stops For Permit 07080515
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-04-18 Cont ID  
Sent By rmcdouga Date 2008-04-18 Time 07:41 Rev Time 0.00
Received By rmcdouga Date 2008-04-18 Time 07:00 Sent To  
Notes
2008-04-18 07:58:58REVISED STRUCTURAL DETAIL FOR THE LIVING ROOM WINDOWS.
 CHANGED FROM TUBE STEEL COLUMNS BETWEEN WINDOWS TO
 REINFORCED MASONRY COLUMNS. SEE SHEET A2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-04-09 Cont ID  
Sent By rmcdouga Date 2008-04-09 Time 07:24 Rev Time 0.00
Received By rmcdouga Date 2008-04-08 Time 19:15 Sent To  
Notes
2008-04-09 07:23:29REVISED DRAWING SHEET #1 MASONRY REPAIR IS DENIED
  
 1) THE ENGINEER'S SIGNATURE ON THE DRAWING IS A COPY.
 THE SIGNATURE IS REQUIRED TO BE ORIGINAL PER FS 471 AND
 FAC 61G15-23.002.
  
 2) THE DRAWING REVISING THE PLAN IS FROM STEVE WALSH AN
 ENGINEER AND THE APPROVED PLANS ARE SIGNED AND SEALED
 BY RANDALL STOFFT AN ARCHITECT. THE DESIGNER OF RECORD
 FOR THE PROJECT IS RANDALL STOFFT ANY REVISIONS TO THE
 PLANS ARE REQUIRED TO BE DONE BY HIM. THERE IS NOTHING
 ON THE PLANS THAT INDICATE STEVE WALSH AS THE
 STRUCTURAL DESIGNER FOR THIS PROJECT.
  
 3) ONE OF THE SUBMITTED DRAWINGS IS BEING RETAINED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-03-04 Cont ID  
Sent By rmcdouga Date 2008-03-04 Time 10:43 Rev Time 0.00
Received By rmcdouga Date 2008-03-04 Time 10:43 Sent To Z
Notes
2008-03-04 10:45:13REVISION TO LOCATION OF SUMMER KITCHEN AND A/C
 CONDENSERS OK FOR BUILDING. SHEET A-2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-11-30 Cont ID  
Sent By rmcdouga Date 2007-11-30 Time 16:09 Rev Time 0.00
Received By rmcdouga Date 2007-11-30 Time 11:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-29 Cont ID  
Sent By rmcdouga Date 2007-08-29 Time 14:16 Rev Time 0.00
Received By rmcdouga Date 2007-08-29 Time 14:16 Sent To  
Notes
2007-08-29 14:15:582004 FBC WITH 2007 SUPPLEMENT
 CONSTRUCT NEW SINGLE FAMILY RESIDENCE
  
 DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)SUBMIT A COPY OF THE PAID RECEIPT FOR THE PALM
 BEACH COUNTY IMPACT FEES.
  
 3) REVISE THE CODE EDITION SPECIFIED ON SHEET T1 TO THE
 2004 FBC WITH 2007 SUPPLEMENT.
  
 4) THE REAR QUADRANT OF THE STRUCTURE ABUTS A LAKE AND
 A GOLF COURSE, WHICH HAS EXPOSURE C-TYPE TERRAIN FOR A
 DISTANCE OF MORE THAN 600 FEET. THEREFORE,THE
 STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C. PER
 R301.2.1.4 EXPOSURE CATEGORY. 3. EXPOSURE C. OPEN
 TERRAIN WITH SCATTERED OBSTRUCTIONS, INCLUDING SURFACE
 UNDULATIONS OR OTHER IRREGULARITIES, HAVING HEIGHTS
 GENERALLY LESS THAN 30 FEET (9144 MM) EXTENDING MORE
 THAN 1,500 FEET (457.2 M) FROM THE BUILDING SITE IN ANY
 QUADRANT. THIS EXPOSURE SHALL ALSO APPLY TO ANY
 BUILDING LOCATED WITHIN EXPOSURE B-TYPE TERRAIN WHERE
 THE BUILDING IS DIRECTLY ADJACENT TO OPEN AREAS OF
 EXPOSURE C-TYPE TERRAIN IN ANY QUADRANT FOR A DISTANCE
 OF MORE THAN 600 FEET (182.9 M). SHORT-TERM (LESS THAN
 TWO YEAR) CHANGES IN THE PRE-EXISTING TERRAIN EXPOSURE,
 FOR THE PURPOSES OF DEVELOPMENT, SHALL NOT BE
 CONSIDERED OPEN FIELDS. WHERE DEVELOPMENT BUILD OUT
 WILL OCCUR WITHIN THREE YEARS AND THE RESULTANT
 CONDITION WILL MEET THE DEFINITION OF EXPOSURE B,
 EXPOSURE B SHALL BE REGULATING FOR THE PURPOSE OF
 PERMITTING. THIS CATEGORY INCLUDES FLAT OPEN COUNTRY,
 GRASSLANDS AND OCEAN OR GULF SHORELINES. THIS CATEGORY
 DOES NOT INCLUDE INLAND BODIES OF WATER THAT PRESENT A
 FETCH OF 1 MILE (1.61 KM) OR MORE OR INLAND WATERWAYS
 OR RIVERS WITH A WIDTH OF 1 MILE (1.61 KM) OR MORE (SEE
 EXPOSURE D). PLEASE REVISE THE EXPOSURE CATEGORY
 SPECIFIED ON THE PLANS AND REVISE THE COMPONENT AND
 CLADDING PRESSURES TO EXPOSURE C.
  
 5) PLEASE INDICATE THAT THE INTERNAL PRESSURE
 COEFFICIENT ON T1 IS FOR BOTH POSITIVE AND NEGATIVE
 PRESSURES BY ADDING THE PLUS AND MINUS SIGNS. SEE
 ASCE7-02.
  
 6)SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS.
 EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM)
 SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE
 RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL
 NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM
 AN ADJACENT PROJECTION OR WALL. THE LEFT SIDE OF THE
 STRUCTURE IS LOCATED 5 FEET FROM THE PROPERTY LINE.
 INDICATE ON THE PLANS THAT THE DISTANCE TO THE ADJACENT
 STRUCTURE IS MORE THAN 6 FEET OR THAT THE ADJACENT LOT
 IS VACANT.
  
 7) SUBMIT A DRAINAGE PLAN SHOWING COMPLIANCE WITH
 R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048
 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 PROVIDED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
  
 8) PROVIDE CONNECTION DETAILS FOR THE TOP AND BOTTOM OF
 THE 4 X 6 X 3/16 " T.S. COLUMNS BETWEEN THE LIVING ROOM
 WINDOWS. SPECIFY FASTENERS, ETC. FBC * 106.1.2
  
 9) PROVIDE A DETAIL OF THE WINDOW BUCK TO STEEL COLUMN
 DETAIL FOR THE 4X6 STEEL COLUMNS AT LIVING ROOM
 WINDOWS.
  
 10) PROVIDE AN ELEVATION OF THE EXTERIOR WALL AT THE
 BREAKFAST AND FAMILY ROOM. SPECIFY THE PRESSURES FOR
 THE WINDOW AT THE BREAKFAST ROOM.
  
 11) THE FL PRODUCT APPROVAL NUMBER LISTED IN THE ANCHOR
 SCHEDULE ON A3 FOR THE USP RT16 HURRICANE TIE IS
 INCORRECT. THE FL NUMBER FOR THIS CONNECTOR IS FL565,
 THE ONE LISTED IS FOR THE RT16 FLAT AND TWIST STRAP
 CONNECTORS. PLEASE CORRECT.
  
 12) THE DOUBLE OUT SWING FRONT DOORS, AS WELL AS, SOME
 OF THE OTHER PRODUCTS MAY NOT MEET THE INCREASED
 COMPONENT AND CLADDING PRESSURES OF THE EXPOSURE C
 CATEGORY. PLEASE REVIEW PRODUCT APPROVALS FOR ADEQUATE
 PRESSURES.
  
 13) SUBMIT RATIONAL ANALYSIS FROM A FLORIDA LICENSED
 ENGINEER FOR THE EXTERIOR 18" X 18" ACCESS DOOR TO THE
 WHIRLPOOL TUB MOTOR SHOWING THAT THE DOOR IS CAPABLE OF
 WITH STANDING THE WINDLOAD PRESSURES. SPECIFY THE
 ANCHOR TYPE, EMBED DEPTH, ETC. PROVIDE MANUFACTURER'S
 SPECIFICATIONS.
  
 -ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-04-08 Cont ID  
Sent By btrobaug Date 2008-04-08 Time 15:00 Rev Time 0.00
Received By btrobaug Date 2008-04-08 Time 14:35 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-03-04 Cont ID  
Sent By btrobaug Date 2008-03-04 Time 08:05 Rev Time 0.00
Received By btrobaug Date 2008-03-03 Time 16:34 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-02-25 Cont ID  
Sent By btrobaug Date 2008-02-25 Time 09:09 Rev Time 0.00
Received By btrobaug Date 2008-02-25 Time 07:03 Sent To PC
Notes
2008-02-25 09:09:14 
  
 REVISION DENIED
  
 1} PER 553.791 FS, THESE PLANS MUST BE SENT TO THE
 PPIVATE PROVIDER FOR REVIEW PRIOR TO SUBMITTING THEM TO
 THIS DEPARTMENT.
  
 2} THE ARCHITECT SHALL CLOUD OR INDICATE BY ANOTHER
 ACCEPTABLE METHOD USED BY THE INDUSTRY, THE REVISIONS
 ON THESE PLANS.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-11-21 Cont ID  
Sent By btrobaug Date 2007-11-21 Time 10:51 Rev Time 0.00
Received By btrobaug Date 2007-11-21 Time 09:48 Sent To P
Notes
2007-11-21 10:52:14 
  
 TO MIKE'S DESK./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-21 Cont ID  
Sent By btrobaug Date 2007-08-21 Time 17:32 Rev Time 0.00
Received By btrobaug Date 2007-08-21 Time 07:42 Sent To P
Notes
2007-08-21 17:30:23 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 FLORIDA STATUTES 1/2007,2004 FBC AS AMENDED, CHAPTER
 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THESE COMMENTS REFER TO SHEET A7.
  
 1} CIRCUIT # 40 IN PANEL "B" INDICATES A LOAD OF 3.6
 KW. IN VIOLATION OF 210.23, LIMITING THE CIRCUIT
 AMPACITY TO 80% OF THE CIRCUIT RATING ( AT 20 AMPS).
 LIST THE CIRCUIT RATING AND CONDUCTOR SIZE SO
 COMPLIANCE WITH 310.16 MAY BE REVIEWED. NOTE: THE HIGH
 HATS LISTED ON THOSE CIRCUITS ARE NOT REQUIRED TO BE ON
 A SEPARATE CIRCUIT AND MAY BE PUT ON OTHER LIGHTING AND
 RECEPTACLE CIRCUITS.
  
 2} SHEET A2 ANDA7 INDICATES IN A NOTE THATAHU #2,
 IN BEDROOM #2CLOSET, IS CEILING HUNG. SHEET M1 SYSTEM
 SPECIFICATIONS INDICATE THERE IS A 30 AMP FUSE IN THE
 AIR HANDLER. OVERCURRENT PROTECTION IN A CLOTHES CLOSET
 IS IN VIOLATION OF 240.24(D). ALSO THERE IS A
 DISCONNECT IN THE CLOSET AND IT IS UNCLEAR IF IT
 CONTAINS OCP. IF THE INSTALLATION IS INTENDED TO BE IN
 THE ATTIC RATHER THAN IN THE CLOSET, ARECEPTACLE PER
 210.63, IS REQUIRED.
  
 3} RECEPTACLES ARE REQUIRED TO BE ADDED OR RELOCATED TO
 COMPLY WITH 210.52(A) IN THE CLUB, LIVING AND MASTER
 BEDROOMS.
  
 4} SHOW COMPLIANCE WITH R313.1. FBC "OUTSIDE EACH
 SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
 BEDROOMS" AND NFPA-72, 11.5.1.1(2) "OUTSIDE OF EACH
 SEPARATE SLEEPING AREA, IN THE IMMEDIATE VICINITY OF
 THE SLEEPING ROOMS" FOR THE GUEST SUITE.
  
 5} THE ENGINEERSNAME ON THE PLAN PROVIDER AFFIDAVIT
 AND SEAL, IS DIFFERENT THAN THE ONE ON FILE WITH DBPR.
 PLEASE CLARIFY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-09-03 Cont ID  
Sent By adarroug Date 2008-09-03 Time 11:49 Rev Time 0.00
Received By adarroug Date 2008-09-03 Time 11:49 Sent To Z
Notes
2008-09-03 11:49:33TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-08-26 Cont ID  
Sent By tgordon Date 2008-08-26 Time 08:55 Rev Time 0.00
Received By tgordon Date 2008-08-26 Time 08:55 Sent To Z
Notes
2008-08-26 08:56:02TO "ZONING" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-04-18 Cont ID  
Sent By adarroug Date 2008-04-18 Time 16:11 Rev Time 0.00
Received By adarroug Date 2008-04-18 Time 16:11 Sent To M
Notes
2008-04-18 16:13:07TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-04-17 Cont ID  
Sent By adarroug Date 2008-04-17 Time 09:24 Rev Time 0.00
Received By adarroug Date 2008-04-17 Time 09:24 Sent To B
Notes
2008-04-17 09:24:37TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-04-03 Cont ID  
Sent By adarroug Date 2008-04-03 Time 14:43 Rev Time 0.00
Received By adarroug Date 2008-04-03 Time 14:43 Sent To E
Notes
2008-04-03 14:43:57TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-03-03 Cont ID  
Sent By adarroug Date 2008-03-03 Time 16:09 Rev Time 0.00
Received By adarroug Date 2008-03-03 Time 16:09 Sent To E
Notes
2008-03-03 16:10:03TO "BTROBAUG" DESK/REV--PRIVATE PROVIDER--

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-12 Cont ID  
Sent By adarroug Date 2008-02-12 Time 14:57 Rev Time 0.00
Received By adarroug Date 2008-02-12 Time 14:57 Sent To E
Notes
2008-02-12 14:57:46TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-11-19 Cont ID  
Sent By adarroug Date 2007-11-19 Time 10:21 Rev Time 0.00
Received By adarroug Date 2007-11-19 Time 10:21 Sent To Z
Notes
2007-11-19 10:21:31TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-29 Cont ID  
Sent By rmcdouga Date 2007-08-29 Time 14:16 Rev Time 0.00
Received By rmcdouga Date 2007-08-16 Time 15:56 Sent To  
Notes
2007-08-16 15:56:44TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2008-09-05 Cont ID  
Sent By rkussner Date 2008-09-05 Time 08:48 Rev Time 0.00
Received By rkussner Date 2008-09-05 Time 08:48 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-08-27 Cont ID  
Sent By rkussner Date 2008-08-27 Time 09:01 Rev Time 0.00
Received By rkussner Date 2008-09-05 Time 08:47 Sent To  
Notes
2008-08-27 09:44:59LANDSCAPE***FAILED***
  
 PROVIDE THE SIZE AND SPACING FOR ALL PROPOSED PLANT
 MATERIAL.
  
 PALM TREES MAY BE SUBSTITUTED FOR NOT MORE THAN 35% OF
 THE SHADE OR FLOWERING TREES REQUIRED.BECAUSE 10
 TREES ARE REQUIRED, AT LEAST 7 SHADE OR FLOWERING TREES
 ARE REQUIRED.ONLY 5 HAVE BEEN PROVIDED.
  
 THE PROPOSED TREES ALONG THE NORTH PERIMETER OF THE
 SITE SHALL BE KEPT OUT OF THE GRAVEL.PLEASE PROVIDE A
 SEPARATOR TO CONTAIN THE GRAVEL AND KEEP IT AWAY FROM
 THE ROOT BALL OF THE TREES.
  
 PROVIDE THE PLANT LIST FOR LOT #23.
  
 CONTACT INFORMATION:
 ROBERT KUSSNER @ 822-1462

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-04-21 Cont ID  
Sent By tgordon Date 2008-04-21 Time 09:56 Rev Time 0.30
Received By tgordon Date 2008-04-21 Time 09:56 Sent To  
Notes
2008-04-21 09:56:51REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2008-03-04 Cont ID  
Sent By tgordon Date 2008-03-04 Time 11:52 Rev Time 0.20
Received By tgordon Date 2008-03-04 Time 11:52 Sent To  
Notes
2008-03-04 11:53:27REVISION TO BUILDING PLANS PAGES A2 AND A7.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-27 Cont ID  
Sent By tgordon Date 2007-11-27 Time 12:18 Rev Time 0.30
Received By tgordon Date 2007-11-27 Time 12:18 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-08-20 Cont ID  
Sent By tgordon Date 2007-08-20 Time 14:22 Rev Time 0.30
Received By tgordon Date 2007-08-20 Time 14:22 Sent To E
Notes
2007-08-20 14:33:48PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) ENERGY CALCULATIONS LINE 11A STATE THE AIR HANDLER
 IS LOCATED INTERIOR, MECHANICAL PLANS SHOW THE AIR
 HANDLERS ARE LOCATED IN THE GARAGE AND ATTIC, PLEASE
 CORRECT ENERGY CALCULATIONS.
  
 2) ENERGY CALCULATIONS LINE 12 A, B, AND C STATE TWO
 FIVE TON AND ONE TWO TON A/C SYSTEMS ARE BEING
 INSTALLED AND COOLING LOAD CALCULATION SHOW THAT IN
 WHATS NEEDED, BUT MECHANICAL PLANS SHOW ONE FIVE TON,
 ONE TWO TON, AND ONE THREE TON. THE THREE MUST COINCIDE
 PLEASE CORRECT MECHANICAL PLANS. SEE 2004 FBC
 13-607.1.ABC.1.
  
 3) MECHANICAL PLANS NEED THE JOB ADDRESS ON THEM, SEE
 2004 FBC/ CITY WPB AMEND. 106.1.3.
  
 4) SEE F.S. 553.719 (4) (C) (C) FOR PRIVATE PROVIDER
 ACKNOWLEDMENT MISSING.AN ACKNOWLEDGMENT FROM THE FEE
 OWNER IN SUBSTANTIALLY THE FOLLOWING FORM:
 I HAVE ELECTED TO USE ONE OR MORE PRIVATE
 PROVIDERS TO PROVIDE BUILDING CODE PLANS REVIEW AND/OR
 INSPECTION SERVICES ON THE BUILDING OR STRUCTURE THAT
 IS THE SUBJECT OF THE ENCLOSED PERMIT APPLICATION, AS
 AUTHORIZED BY S. 553.791, FLORIDA STATUTES. I
 UNDERSTAND THAT THE LOCAL BUILDING OFFICIAL MAY NOT
 REVIEW THE PLANS SUBMITTED OR PERFORM THE REQUIRED
 BUILDING INSPECTIONS TO DETERMINE COMPLIANCE WITH THE
 APPLICABLE CODES, EXCEPT TO THE EXTENT SPECIFIED IN
 SAID LAW. INSTEAD, PLANS REVIEW AND/OR REQUIRED
 BUILDING INSPECTIONS WILL BE PERFORMED BY LICENSED OR
 CERTIFIED PERSONNEL IDENTIFIED IN THE APPLICATION. THE
 LAW REQUIRES MINIMUM INSURANCE REQUIREMENTS FOR SUCH
 PERSONNEL, BUT I UNDERSTAND THAT I MAY REQUIRE MORE
 INSURANCE TO PROTECT MY INTERESTS. BY EXECUTING THIS
 FORM, I ACKNOWLEDGE THAT I HAVE MADE INQUIRY REGARDING
 THE COMPETENCE OF THE LICENSED OR CERTIFIED PERSONNEL
 AND THE LEVEL OF THEIR INSURANCE AND AM SATISFIED THAT
 MY INTERESTS ARE ADEQUATELY PROTECTED. I AGREE TO
 INDEMNIFY, DEFEND, AND HOLD HARMLESS THE LOCAL
 GOVERNMENT, THE LOCAL BUILDING OFFICIAL, AND THEIR
 BUILDING CODE ENFORCEMENT PERSONNEL FROM ANY AND ALL
 CLAIMS ARISING FROM MY USE OF THESE LICENSED OR
 CERTIFIED PERSONNEL TO PERFORM BUILDING CODE INSPECTION
 SERVICES WITH RESPECT TO THE BUILDING OR STRUCTURE THAT
 IS THE SUBJECT OF THE ENCLOSED PERMIT APPLICATION.
  
 5) ENGINEERS NAME ON PRIVATE PROVIDER AFFIDAVIT JOHN F.
 DESNOYERS, IS NOT THE SAME NAME ON LICENSE # 47885
 (JEAN F. DESNOYERS) PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].

Review Stop P PLUMBING
Rev No 3 Status N Date 2008-03-04 Cont ID  
Sent By mperson Date 2008-03-04 Time 09:10 Rev Time 0.00
Received By mperson Date 2008-03-04 Time 09:10 Sent To B
Notes
2008-03-04 09:17:39NOTE: REVISION HAS NO PLUMBING CHANGES, HOWEVER A GAS
 REVISION WILL BE REQUIRED FOR GAS PERMIT #08010729 FOR
 THE RELOCATED BBQ.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-11-26 Cont ID  
Sent By mperson Date 2007-11-26 Time 14:36 Rev Time 0.00
Received By mperson Date 2007-11-26 Time 14:35 Sent To M
Notes
2007-11-26 14:45:49CONTRACTOR INFORMATION
 (SHEET A2 IS INDICATING GAS APPLIANCES)
 NOTE: GAS PERMIT REQUIRED. GAS OR PLUMBING CONTRACTOR
 TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL GAS
 INSPECTIONS TO BE COMPLETE BEFORE FINAL INSPECTION.
  
  
 ****************PROVISO****************
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 **NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE
 LOCATED AT 4' A.F.F. FACING THE UTILITY ROOM OR AT THE
 BASE OF THE STACK FACING THE 2-CAR GARAGE.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-08-22 Cont ID  
Sent By mperson Date 2007-08-22 Time 15:24 Rev Time 0.00
Received By mperson Date 2007-08-22 Time 15:24 Sent To B
Notes
2007-08-22 16:07:31DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET A6 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN ON SHEET A2: PER FBC-2004
 CHAPTER 1, THE CITY OF WEST PALM BEACH AMENDMENTS,
 SECTION 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELAVENT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 A} THE BRANCH TO THE POWDER ROOM BATH SHOULD BE BEFORE
 THE UTIL. THE WAY THE ISOMETRICT IS DRAWN. IF IT IS THE
 INTENT TO LEAVE THE BRANCH TO THE POWDER ROOM WHERE IT
 IS ON THE ISOMETRIC, PLEASE INDICATE THE REQUIRED
 OFFSETS ON THE RESUBMITTAL TO REFLECT THE FLOOR PLAN.
  
 B} LAV IS MISSING FROM BATH 3. PLEASE CORRECT ON THE
 RESUBMITTAL.
  
 C} DISHWASHER IS INDICATED ON THE WRONG SIDE OF THE
 DOUBLE BOWL SINK W/DISP. AND PER FBC-2004 PLUMBING,
 SECTION 802.1.6 DOMESTIC DISHWASHING MACHINES SHALL
 DISCHARGE INTO A WYE-BRANCH FITTING ON THE TAILPIECE OF
 THE KITCHEN SINK OR THE DISHWASHER CONNECTION OF A FOOD
 WASTE GRINDER. PLEASE CORRECT ON THE RESUBMITTAL.
  
 D} HER BATH DOES NOT REFLECT THE FLOOR PLAN ON SHEET
 A2:
  
 A) SHEET A2 DOES NOT INDICATE A BIDET, BUT THE
 SANITARY ISOMETRIC IS INDICATING A BIDET ON SHEET A6.
 PLEASE CLARIFY AND CORRECT ON THE RESUBMITTAL.
  
 B) LAV IS BEING INDICATED IN THE WRONG PLACE. PLEASE
 CORRECT ON THE RESUBMITTAL.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
 NOTE: NOT ALL PIPES OR TRAPS ARE SIZED ON THE SANITARY
 ISOMETRIC RISER DIAGRAM ON SHEET A6. PLEASE CORRECT
 THIS ON THE RESUBMITTAL.
  
 3. SHEET A2 IS INDICATING GAS APPLIANCES:
  
 **CONTRACTOR INFORMATION**
  
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL INSPECTION.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-04-03 Cont ID  
Sent By choops Date 2008-04-03 Time 14:18 Rev Time 0.00
Received By choops Date 2008-04-03 Time 14:18 Sent To PC
Notes
2008-04-03 14:20:05***APPROVED - REVISION - CHANGING LOCATION OF OUTDOOR
 KITCHEN AND A/C EQUIPMENT***
  
 *OBTAINED DRAINAGE EASEMENT HOLDER APPROVAL.
  

Review Stop Z ZONING
Rev No 3 Status F Date 2008-03-04 Cont ID  
Sent By choops Date 2008-03-04 Time 11:08 Rev Time 0.00
Received By choops Date 2008-03-04 Time 11:08 Sent To M
Notes
2008-03-04 11:12:06***FAILED - REVISION - CHANGING LOCATION OF OUTDOOR
 KITCHEN AND A/C EQUIPMENT***
  
  
 1)AS THE NEWLY SUBMITTED FLOOR PLAN/ELECTRIC PLAN
 (SHEET A2/A7) SHOW THE A/C MECHANICAL EQUIPMENT IN A
 DIFFERENT LOCATION FROM WHAT WAS ORIGINALLY APPROVED,
 INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C EQUIPMENT
 TO ALL PROPERTY LINES.AS PER SECTION 94-305(B)(4) OF
 THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT PROJECT MORE
 THAN 4 FEET INTO A REQUIRED SETBACK.
  
 NOTE:NO STRUCTURE/EQUIPMENT SHALL BE BUILT WITHIN THE
 20 FOOT DRAINAGE EASEMENT .
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "M" - TG

Review Stop Z ZONING
Rev No 2 Status P Date 2007-11-20 Cont ID  
Sent By choops Date 2007-11-20 Time 16:48 Rev Time 0.00
Received By choops Date 2007-11-20 Time 16:48 Sent To E
Notes
2007-11-20 16:49:48***APPROVED - RESUB #1***
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-20 Cont ID  
Sent By choops Date 2007-08-20 Time 11:06 Rev Time 0.00
Received By choops Date 2007-08-20 Time 11:06 Sent To E
Notes
2007-08-20 11:07:58***FAILED***
  
  
 2)PROVIDE SETBACK DIMENSIONS FROM A/C EQUIPMENT TO
 THE PROPERTY LINES.
  
 3)ELEVATION DIMENSIONS TO BE MEASURED FROM GRADE.
  
 4)PLEASE PROVIDE A LANDSCAPE PLAN SHOWING COMPLIANCE
 WITH SECTION 94-442 OF THE CITY OF WEST PALM BEACH
 ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 5)PROVIDE TOTAL SQUARE FOOTAGE OF PROPOSED DRIVEWAY
 WITHIN THE FRONT YARD (FROM FRONT PROPERTY LINE TO THE
 FRONT OF THE PRINCIPAL STRUCTURE).
  
 NOTE:MUST MAINTAIN THE LESSOR OF 1,000 SQ.FT. OR 75%
 OF THE FRONT YARD AS LANDSCAPED MATERIAL.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720