Plan Review Stops For Permit 07080505 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-09-26 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-09-26 |
Time |
13:51 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-09-26 |
Time |
13:39 |
Sent To |
PC |
|
Notes |
2007-09-26 13:39:52 | PROCESS PLAN. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2007-09-19 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-09-19 |
Time |
18:55 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-09-19 |
Time |
18:55 |
Sent To |
|
|
Notes |
2007-09-19 18:55:54 | BUILDING PLAN REVIEW | | PERMIT: 07080505 | | ADD: 580 VILLAGE BLVD | | CONT: G.A. RAY INC. | | TEL: (561)714-3740 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 2ND | | ACTION: | | | | 1)OK | | | | 2)OK | | | | 3)OK | | | | 4)OK | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] | | | | | | | | PROVISOR: | | THE NEW RECEPTIONIST AREA SHALL MEET THE REQUIREMENTS | | OF SECTION 11-7. A PORTION OF THE MAIN COUNTER SHALL BE | | A MINIMUM OF 36 INCHES IN LENGTH AND A MAXIMUM HEIGHT | | OF 36 INCHES. SHOW COMPLIANCE |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-09-05 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-09-05 |
Time |
07:40 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-09-04 |
Time |
11:58 |
Sent To |
PC |
|
Notes |
2007-09-05 07:40:27 | | | BUILDING PLAN REVIEW | | PERMIT: 07080505 | | ADD: 580 VILLAGE BLVD | | CONT: G.A. RAY INC. | | TEL: (561)714-3740 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 1ST | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | 2)THE NEW RECEPTIONIST AREA SHALL MEET THE | | REQUIREMENTS OF SECTION 11-7. A PORTION OF THE MAIN | | COUNTER SHALL BE A MINIMUM OF 36 INCHES IN LENGTH AND A | | MAXIMUM HEIGHT OF 36 INCHES. SHOW COMPLIANCE. | | | | 3)FBC. 803.1 INTERIOR WALL AND CEILING FINISHES SHALL | | BE CLASSIFIED IN ACCORDANCE WITH ASTM E 84. THE NEW | | WALL AND CEILING SHALL HAVE A FLAME SPREAD OF CLASS A / | | B OR C. | | | | 4)SHOW THE COMMON PATH OF EGRESS TRAVEL ON THE | | DRAWINGS. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2007-09-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-09-15 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-09-15 |
Time |
10:31 |
Sent To |
|
|
Notes |
2007-09-15 10:32:42 | ** NEW REVISED ELECTRICAL SHEETS EVEN THOUGH PREVIOUS | | PASSED. | | STILL REDLINED CIRCUITING FOREM/EXT LIGHTS PER | | 700.12F. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2007-08-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-08-31 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-08-31 |
Time |
15:44 |
Sent To |
|
|
Notes |
2007-08-31 16:03:52 | REDLINED PLANS. | | | | WRONG NEC REFERENCED, SHOULD BE 2005. | | ALSO REDLINE D700.12F OR CIRCUITING OF EMERGENCY AND | | EXIT LTS. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2007-09-25 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-09-25 |
Time |
11:03 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-09-25 |
Time |
10:58 |
Sent To |
|
|
Notes |
2007-09-25 11:03:39 | *****APPROVED***** | | | | THE COMMENT FROM THE PREVIOUS FIRE PLAN REVIEW HAS BEEN | | SATISFIED;PLAN SHEET 2 STAMPED, INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-08-30 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-08-30 |
Time |
14:32 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-08-30 |
Time |
10:57 |
Sent To |
|
|
Notes |
2007-08-30 14:30:53 | *****UNSAT***** | | | | | | 1.SPECIFY THE WALL AND CEILING FINISH MATERIALS TO BE | | REPLACED IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-09-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-11 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-11 |
Time |
14:02 |
Sent To |
|
|
Notes |
2007-09-15 10:22:12 | TO BOB SPACE #12, DVP | 2007-09-11 14:03:15 | WAITING FOR "BOB" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-09-11 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-05 |
Time |
14:00 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-16 |
Time |
14:09 |
Sent To |
|
|
Notes |
2007-08-29 11:32:55 | TO "BOB"#8 | 2007-08-16 14:10:02 | WAITING FOR "BOB" |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2007-08-30 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-08-30 |
Time |
15:51 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2007-08-30 |
Time |
15:51 |
Sent To |
|
|
Notes |
2007-08-30 15:53:46 | *** PROVISO *** | | 1) ALL ROOMS TO COMPLY WITH 2004 FBC/M 601.4 BALANCED | | RETURN AIR. | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2007-09-21 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-09-21 |
Time |
14:18 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-09-21 |
Time |
14:18 |
Sent To |
|
|
Notes |
2007-09-21 14:19:06 | *ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK | | DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE. |
|
|