Plan Review Details - Permit 07080505
Plan Review Stops For Permit 07080505
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-09-26 Cont ID  
Sent By mjacobs Date 2007-09-26 Time 13:51 Rev Time 0.00
Received By mjacobs Date 2007-09-26 Time 13:39 Sent To PC
Notes
2007-09-26 13:39:52PROCESS PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-09-19 Cont ID  
Sent By mjacobs Date 2007-09-19 Time 18:55 Rev Time 0.00
Received By mjacobs Date 2007-09-19 Time 18:55 Sent To  
Notes
2007-09-19 18:55:54BUILDING PLAN REVIEW
 PERMIT: 07080505
 ADD: 580 VILLAGE BLVD
 CONT: G.A. RAY INC.
 TEL: (561)714-3740
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION:
  
 1)OK
  
 2)OK
  
 3)OK
  
 4)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  
  
 PROVISOR:
 THE NEW RECEPTIONIST AREA SHALL MEET THE REQUIREMENTS
 OF SECTION 11-7. A PORTION OF THE MAIN COUNTER SHALL BE
 A MINIMUM OF 36 INCHES IN LENGTH AND A MAXIMUM HEIGHT
 OF 36 INCHES. SHOW COMPLIANCE

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-05 Cont ID  
Sent By mjacobs Date 2007-09-05 Time 07:40 Rev Time 0.00
Received By mjacobs Date 2007-09-04 Time 11:58 Sent To PC
Notes
2007-09-05 07:40:27 
 BUILDING PLAN REVIEW
 PERMIT: 07080505
 ADD: 580 VILLAGE BLVD
 CONT: G.A. RAY INC.
 TEL: (561)714-3740
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)THE NEW RECEPTIONIST AREA SHALL MEET THE
 REQUIREMENTS OF SECTION 11-7. A PORTION OF THE MAIN
 COUNTER SHALL BE A MINIMUM OF 36 INCHES IN LENGTH AND A
 MAXIMUM HEIGHT OF 36 INCHES. SHOW COMPLIANCE.
  
 3)FBC. 803.1 INTERIOR WALL AND CEILING FINISHES SHALL
 BE CLASSIFIED IN ACCORDANCE WITH ASTM E 84. THE NEW
 WALL AND CEILING SHALL HAVE A FLAME SPREAD OF CLASS A /
 B OR C.
  
 4)SHOW THE COMMON PATH OF EGRESS TRAVEL ON THE
 DRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-15 Cont ID  
Sent By dpalmer Date 2007-09-15 Time 10:31 Rev Time 0.00
Received By dpalmer Date 2007-09-15 Time 10:31 Sent To  
Notes
2007-09-15 10:32:42** NEW REVISED ELECTRICAL SHEETS EVEN THOUGH PREVIOUS
 PASSED.
 STILL REDLINED CIRCUITING FOREM/EXT LIGHTS PER
 700.12F.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-08-31 Cont ID  
Sent By dpalmer Date 2007-08-31 Time 16:02 Rev Time 0.00
Received By dpalmer Date 2007-08-31 Time 15:44 Sent To  
Notes
2007-08-31 16:03:52REDLINED PLANS.
  
 WRONG NEC REFERENCED, SHOULD BE 2005.
 ALSO REDLINE D700.12F OR CIRCUITING OF EMERGENCY AND
 EXIT LTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-09-25 Cont ID  
Sent By mawillia Date 2007-09-25 Time 11:03 Rev Time 0.00
Received By mawillia Date 2007-09-25 Time 10:58 Sent To  
Notes
2007-09-25 11:03:39*****APPROVED*****
  
 THE COMMENT FROM THE PREVIOUS FIRE PLAN REVIEW HAS BEEN
 SATISFIED;PLAN SHEET 2 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-08-30 Cont ID  
Sent By mawillia Date 2007-08-30 Time 14:32 Rev Time 0.00
Received By mawillia Date 2007-08-30 Time 10:57 Sent To  
Notes
2007-08-30 14:30:53*****UNSAT*****
  
  
 1.SPECIFY THE WALL AND CEILING FINISH MATERIALS TO BE
 REPLACED IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-11 Cont ID  
Sent By adarroug Date 2007-09-11 Time 14:02 Rev Time 0.00
Received By adarroug Date 2007-09-11 Time 14:02 Sent To  
Notes
2007-09-15 10:22:12TO BOB SPACE #12, DVP
2007-09-11 14:03:15WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-11 Cont ID  
Sent By adarroug Date 2007-09-05 Time 14:00 Rev Time 0.00
Received By adarroug Date 2007-08-16 Time 14:09 Sent To  
Notes
2007-08-29 11:32:55TO "BOB"#8
2007-08-16 14:10:02WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-08-30 Cont ID  
Sent By tgordon Date 2007-08-30 Time 15:51 Rev Time 0.25
Received By tgordon Date 2007-08-30 Time 15:51 Sent To  
Notes
2007-08-30 15:53:46*** PROVISO ***
 1) ALL ROOMS TO COMPLY WITH 2004 FBC/M 601.4 BALANCED
 RETURN AIR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2007-09-21 Cont ID  
Sent By choops Date 2007-09-21 Time 14:18 Rev Time 0.00
Received By choops Date 2007-09-21 Time 14:18 Sent To  
Notes
2007-09-21 14:19:06*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.