Plan Review Details - Permit 07080482
Plan Review Stops For Permit 07080482
Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-09-27 Cont ID  
Sent By mperson Date 2007-09-27 Time 11:54 Rev Time 0.00
Received By mperson Date 2007-09-27 Time 11:54 Sent To PC
Notes
2007-09-27 13:08:37REVISION DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. THE SUBMITTED REVISED GAS ISOMETRIC RISER DIAGRAM
 IS NOT SIZED CORRECTLY PER TABLES 402.4(2) AND
 402.4(20). THE GAS PIPING NEEDS TO BE INCREASED TO
 1-1/2".
  
 2. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 NOTE: DELIVERY PRESSURE IS NOT INDICATED ON THE
 REVISION. APPROVED PERMIT COPY INDICATES 0.5 PSI.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2007-09-10 Cont ID  
Sent By mperson Date 2007-09-10 Time 15:55 Rev Time 0.00
Received By mperson Date 2007-09-10 Time 15:55 Sent To PC
Notes
2007-09-10 15:56:01NOTE: REFERENCE GEN/COM PERMIT #06071436

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-12 Cont ID  
Sent By adarroug Date 2007-09-12 Time 15:13 Rev Time 0.00
Received By adarroug Date 2007-09-12 Time 15:13 Sent To G
Notes
2007-09-12 15:14:14TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-10 Cont ID  
Sent By mperson Date 2007-09-10 Time 15:56 Rev Time 0.00
Received By mperson Date 2007-08-16 Time 10:45 Sent To  
Notes
2007-08-16 10:45:34TO "G" BOX