Plan Review Details - Permit 07080439
Plan Review Stops For Permit 07080439
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-12-04 Cont ID  
Sent By rmcdouga Date 2007-12-04 Time 14:23 Rev Time 0.00
Received By rmcdouga Date 2007-12-04 Time 14:22 Sent To  
Notes
2007-12-04 14:24:03RETURNED PLANS WITH IMPACT FEE STAMPE AND RECEIPT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-12-04 Cont ID  
Sent By rmcdouga Date 2007-12-04 Time 08:23 Rev Time 0.00
Received By rmcdouga Date 2007-12-04 Time 07:01 Sent To  
Notes
2007-12-04 08:36:01PLAN REVIEW STATUS WILL BE CHANGED TO PASS AND PERMIT
 ISSUED WHEN PLANS ARE STAMPED FOR COUNTY IMPACT FEES
 AND COPY OF RECEIPT SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-11-01 Cont ID  
Sent By rmcdouga Date 2007-11-01 Time 17:55 Rev Time 0.00
Received By rmcdouga Date 2007-11-01 Time 17:55 Sent To  
Notes
2007-11-01 18:50:152004 FBC W/2007 REVISIONS
 CONVERT MODEL TO SFR
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 4) SPECIFY THE EDGE DISTANCE, CONN TYPE, ANCHOR TYPE,
 ANCHOR SPACING, ETC. FOR THE STORM PANELS. PLEASE
 CIRCLE THE APPROPRIATE ITEMS ON SHEET 6 OF THE PRODUCT
 APPROVAL DRAWINGS.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-04 Cont ID  
Sent By rmcdouga Date 2007-11-01 Time 17:55 Rev Time 0.00
Received By rmcdouga Date 2007-09-04 Time 13:46 Sent To M
Notes
2007-09-04 15:59:372004 FBC W/2007 SUPPLEMENT
 CONVERT TEMPORARY SALES OFFICE BACK TO SFR
  
 DENIED BY BUILDING
  
 1) THE DESCRIPTION OF WORK ON THE PERMIT APPLICATION IS
 FOR DRYWALL WORK ONLY.THE PLANS THAT WERE SUBMITTED
 INDICATE THAT INTERIOR WALLS WILL NEED TO BE REMOVED
 AND NEW ONES INSTALLED, KITCHEN CABINETS TO BE
 INSTALLED IN THE DISPLAY AREA, ETC.
  
 2) THE VALUE FOR THE WORK LISTED ON THE PERMIT
 APPLICATION IS TOO LOW FOR THE AMOUNT OF WORK THAT WILL
 BE REQUIRED TO CONVERT THE STRUCTURE FROM THE SALES
 OFFICE INTERIOR BUILD OUT TO THE RESIDENTIAL LAYOUT
 SHOWN ON THE PLANS THAT WERE SUBMITTED.
  
 3) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 DESCRIBING THE WORK WILL BE REQUIRED BECAUSE THE VALUE
 OF THE WORK IS OVER $2500.00. FS 713.
  
 4) NEW ELECTRICAL, MECHANICAL AND PLUMBING PLANS
 SHOWING THE EXISTING CONDITIONS AND PROPOSED CHANGES
 WILL BE REQUIRED. FBC* 106.1.2 AMENDED BY W.P.B.
  
 5) THE PLANS FROM THE ARCHITECT ARE REQUIRED TO BE
 SIGNED, SEALED AND DATED. FBC*106.1 AND FS 481.
  
 6) SPECIFY WHICH OF THE ROOM OPTIONS SPECIFIED ON THE
 PLANS WILL BE USED. FBC * 106.1.2.
  
 7) THE EXISTING FLOOR PLAN INDICATES DOUBLE OUTSWING
 FRENCH DOORS AT THE GATHERING ROOM AND THE NEW FLOOR
 PLAN SHOWS A DOUBLE WINDOW AT THIS LOCATION. THE
 EXISTING FLOOR PLAN SPECIFIES A SMALLER WINDOW AT THE
 DISPLAY AREA THAN THE NEW FLOOR PLAN AT THAT LOCATION.
 IF DOORS OR WINDOWS ARE BEING CHANGED, SUBMIT PRODUCT
 APPROVALS FOR THE NEW ITEMS.
  
 8)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 9) FBC R301.2.1.2 REQUIRES GLAZED OPENINGS TO BE IMPACT
 PROTECTED. PROVIDE PRODUCT APPROVALS FOR IMPACT
 PROTECTION PRODUCTS AT NEW GLAZED AREAS.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2007-11-01 Cont ID  
Sent By mjacobs Date 2007-08-31 Time 13:45 Rev Time 0.00
Received By rmcdouga Date 2007-08-31 Time 13:43 Sent To B
Notes
2007-08-31 13:45:09SENT TO ROBERT MC DOUGAL DESK FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-11-30 Cont ID  
Sent By dpalmer Date 2007-11-30 Time 08:40 Rev Time 0.00
Received By dpalmer Date 2007-11-30 Time 08:39 Sent To  
Notes
2007-11-30 08:40:09** REDLINED PLANS.
  
 1) NOTE: LOAD CALCULATIONS STILL INDICATE AC HEAT LOAD
 *AT 100 PERCENT OR 40 PERCENT. THE LOAD WAS FIGURED
 CORRECTLY HOWEVER PLANS STILL SHOW 40 PERCENT WHICH IS
 NOT PERMITTED IN THE CODE.
  
 2) NOTE: PLEASE SEE MISPRINT NOW FOR CONDUCTORS FOR
 SERVICE. SHOWS A DIFFERENT SYMBOL FOR THE 2/0 AND 1/0.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-10-31 Cont ID  
Sent By dpalmer Date 2007-10-31 Time 11:43 Rev Time 0.00
Received By dpalmer Date 2007-10-31 Time 10:34 Sent To  
Notes
2007-10-31 11:43:17 
 ** DENIED 2ND REVIEW**
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW.
  
 1) NOTE: AS STATED ON PREVIOUS REVIEW, ALL CURRENT
 RELEVANT CODES SHALL BE STATED ON PLANS.
 2005 NFPA-70
 2002 NFPA-72
 2004 FBC W/2006 REVS.
  
 2) NOTE: THE VALUE WAS CHANGED ON PERMIT APPLICATION
 PER RE-SUB COVER SHEET. THIS WAS NOT CHANGED ON
 APPLICATION BY CONTRACTOR ONLY ON RE-SUB COVER SHEET.
 ** THIS IS NOTED FOR INFORMATIONAL PURPOSE TO
 CONTRACTOR ONLY.
  
 3) NOTE: PLEASE SEE CIRCUITING ON PANEL SCHEDULE
 SUBMITTED IS NOT ACCEPTABLE USING *GENERAL LIGHTS* AND
 *RECEPTACLES*.
 PLEASE SEE 408.4 AND THE FOLLOWING TEXT EXTRACTED FROM
 COMMENTARY.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4, FBC 106.1.2
  
 4) NOTE: PLEASE SEE NFPA-72 FOR DEFINITIONS OF SMOKE
 DETECTION DEVICES. THESE ARE SHOWN AS SD FOR SMOKE
 DETECTORS. IF THESE ARE SMOKE DETECTORS BY DEFINITION,
 PLEASE INCLUDE SYSTEM WHICH INCLUDE FIRE ALARM PANEL,
 HORN DEVICES ETC.
 IF THESE ARE SMOKE ALARMS WHICH DETECT AND SOUND AND
 ALARM, PLEASE ADJUST TO SA.
 PLEASE ALSO SEE THE STUDY WHICH IS AN ADAPTABLE
 SLEEPING ROOM IS REQUIRED TO CONTAIN SMOKE DETECTION
 DEVICE INSIDE AND OUTSIDE THIS ROOM.
 NFPA-72 , 11.5.1.1.1, 11.8.3
  
 5) NOTE: PLEASE CLARIFY 210.12 FOR ARC FAULT
 PROTECTION. PLEASE LIST.
  
 6) NOTE: RISER INDICATES *OPTIONAL* FOR REQUIRED
 ELECTRICAL CODE ITEMS.
 PLANS MAY NOT CONTAIN *OPTIONAL* FOR FINAL RECORD SETS
 OF DRAWINGS. THE DOCUMENT MUST SHOW AN ACCURATE RECORD
 OF WORK DONE/INSTALLED.
 FBC 106.1.2, 106.5, 110.1.2 ETC.
  
 7) NOTE: PLEASE ALSO THE EQUIPMENT GROUNDING CONDUCTOR
 IS LISTED AS *OPTIONAL* BEFORE AND AFTER MAIN. PLEASE
 SEE 250.6, 250.24B AS AN EQUIPMENT GROUNDING CONDUCTOR
 IS REQUIRED AFTER THE FIRST MEANS OF DISCONNECTAND
 SHALL NOT BE INSTALLED BEFORE THE FIRST MEANS OF
 DISCONNECT.
  
 8) NOTE: PLANS SHOW HOT WATER HEATER AS BEING PLUGGED
 IN WHICH IS NOT PERMITTED.
 422.30, 422.31
  
 9) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING
 KITCHEN COUNTER SPACE SHALL BE GFI.
  
 10) NOTE: PLEASE BE SURE PLANS ARE DETAILED TO ALL
 ITEMS WHICH ARE GOING TO BE NEW AND WHICH ARE GOING TO
 REMAIN AS EXISTING. AS THE SCOPE OF WORK APPEARS THE
 ENTIRE HOUSE IS BEING REWIRED, MUST COMPLY WITH CURRENT
 NEC 2005 ETC AS NOTED ABOVE.
 THERE ARE ITEMS WHICH COULD NOT BE COMMENTED ON AS THE
 SCOPE OF WORK IS NOT CLEARLY DEFIED.
  
 11) NOTE: PLEASE INCLUDE THE TYPE OF RECESSED LIGHTING
 FIXTURES TO MEET FBC 13-606.1.ABC.1.2.4
  
 12) NOTE: PLEASE SEE THERE ARE SYMBOLS ON PLANS WHICH
 ARE NOT ON ELECTRICAL SYMBOL LEGEND. PLEASE COORDINATE
 AND COMPLETE.
 FOR EXAMPLE: RECESSED LIGHTS, WATER HEATER ETC. FBC
 106.1.2 ADDITIONAL INFORMATION/COORDINATION.
  
 13) NOTE: PANEL SCHEDULE INDICATES A SPRINKLER PUMP
 HOWEVER THERE IS NO PUMP AND DISCONNECT ON PLANS.
 PLEASE SHOW. FBC 106.1.2, 106.3.5.4
  
 14) NOTE: PLEASE SEE THERE ARE SEVERAL CIRCUITS ON
 PANEL SCHEDULE WHICH SHOW #2 FOR THE WIRE SIZE. THIS
 APPEARS TO BE A MISPRINT FOR #12?
 408.4, 310.16, FBC 106.1.2, 106.3.5.4
  
 15) NOTE: PLEASE SEE MISSING RECEPTACLE(S) ALONG
 COUNTER SPACE AS REQUIRED PER 210.52C1 (DISHWASHER
 COUNTER).
  
 16) NOTE: PLEASE SEE MISSING RECEPTACLE(S) PER 210.52.
  
 2FT OR MORE OF WALL SPACE.
  
 17) NOTE: PLEASE SEE NEC 220 AS THE HEAT LOAD ON
 CALCULATIONS MENTIONS TO BE DONE AT 100 PERCENT OR 40
 PERCENT. WHERE DOES THE CODE PERMIT THIS TO BE DONE AT
 40 PERCENT FOR THIS DWELLING UNIT FOR ONE A/C SYSTEM?
 PLEASE SEE 220, 220.60, 220.80 ETC.
  
 18) NOTE: PLEASE SEE 210.70 AND LS 101 7.8 AS A LIGHT
 FIXTURE OF SOME TYPE WILL BE REQUIRED AT THE REAR
 EGRESS.
  
 19) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.53 AS THE
 NOOK RECEPTACLES SHALL BE PART OF ONE OR *MORE* OF THE
 SMALL APPLIANCE CIRCUITS. THIS AREA IS THE SAME AS THE
 DINING ROOM WHICH INDICATES THE ADDITIONAL CIRCUIT WITH
 LOAD AT 1500VA.
  
  
 ** AS THERE ARE SOME ITEMS NOT YET ON PLANS AND OR
 SHOWN THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW
 WHICH CAN NOT BE MADE AT THIS TIME.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-31 Cont ID  
Sent By dpalmer Date 2007-08-31 Time 15:25 Rev Time 0.00
Received By dpalmer Date 2007-08-31 Time 15:01 Sent To B
Notes
2007-08-31 15:25:23 
  
 ** DENIED**
  
  
  
 1) NOTE: PLEASE SUBMIT COMPLETED ELECTRICAL PLANS FOR
 SHOWING NEW OR EXISTING ELECTRICAL MEETING CURRENT
 NFPA-70 NEC, NFPA-72 AND NFPA-101.
 PLEASE ALSO SEE FBC 2004 W/2006 REVISIONS.
 THE PLANS SUBMITTED COMPARE TO THE FLOOR LAYOUT OF THE
 EXISTING *SALES OFFICES* IS COMPLETELY DIFFERENT.
 PLEASE SEE FBC 106.3.5.4 AND CODES NOTED ABOVE FOR ALL
 ELECTRICAL TO COMPLY WITH THE CURRENT CODES ALSO BASED
 ON THE CHANGE IN OCCUPANCY.
 ** SOME ASPECTS OF THE BUILDING OR STRUCTURE MAY
 ALREADY COMPLY FOR THE ELECTRICAL CODE AND FBC FOR
 RESIDENCE.
  
 2) NOTE: PLEASE KNOW WHEN SUBMITTING PLANS, PLEASE BE
 SURE ALL PLANS ARE SIGNED, DATED AND SEALED BY THE
 RESPECTIVE DESIGNER(S) OF RECORD AS REQUIRED PER FS 481
 AND 471
  
 3) NOTE: PLEASE KNOW AS THE PLANS SUBMITTED FOR THE
 CHANGE AND SCOPE IS COMPLETELY DIFFERENT THAN THE
 PERMIT APPLICATION, THE VALUE FOR THE COMPLETE SCOPE OF
 WORK SHALL COMPLY WITH THE FBC 108.3 TO INCLUDE ALL
 LABOR, MATERIALS, EQUIPMENT, DESIGN COST ETC AS STATED
 IN THE CODE.
 MINIMUM VALUATION TABLES MAY BE USED FOR SCOPE OF WORK
 AS SHOWN ON PLANS AND MAY ALSO BE ADJUSTED BY THIS
 OFFICE ONCE THE ACTUAL COMPLETE SCOPE HAS BEEN
 DETERMINED.
  
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2007-08-30 Cont ID  
Sent By mawillia Date 2007-08-30 Time 11:57 Rev Time 0.00
Received By mawillia Date 2007-08-30 Time 11:37 Sent To  
Notes
2007-08-30 11:57:04*****NOT REQUIRED*****
  
  
 THIS CONVERSION OF A BUSINESS OCCUPANCY BACK TO ITS
 ORIGINAL RESIDENTIAL OCCUPANCY (SINGLE FAMILY DWELLING)
 DOES NOT REQUIRE A FIRE PLAN REVIEW.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-27 Cont ID  
Sent By adarroug Date 2007-11-27 Time 12:32 Rev Time 0.00
Received By adarroug Date 2007-11-27 Time 12:32 Sent To  
Notes
2007-11-29 15:32:14TO "BOB"#9
2007-11-27 12:33:06WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-23 Cont ID  
Sent By adarroug Date 2007-10-23 Time 09:05 Rev Time 0.00
Received By adarroug Date 2007-10-23 Time 09:05 Sent To  
Notes
2007-10-30 14:42:12TO "BOB"#1
2007-10-23 09:06:33WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-12 Cont ID  
Sent By jleech Date 2007-09-12 Time 13:49 Rev Time 0.00
Received By jleech Date 2007-08-15 Time 13:44 Sent To  
Notes
2007-08-27 13:54:53TO "BOB"#16
2007-08-15 13:45:32WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-10-31 Cont ID  
Sent By tgordon Date 2007-10-31 Time 13:59 Rev Time 0.30
Received By tgordon Date 2007-10-31 Time 13:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-04 Cont ID  
Sent By tgordon Date 2007-09-04 Time 16:29 Rev Time 0.25
Received By tgordon Date 2007-09-04 Time 16:29 Sent To P
Notes
2007-09-04 16:44:08PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 TO CHANGE THE FLOOR PLAN FROM THE SALES OFFICE MODEL
 2255 TO A SINGLE FAMILY RESIDENCE MODEL 2255-L. FLOOR
 PLANS SUBMITTED SHOW THE INTERIOR LAY-OUT TO UNDER GO A
 MAJOR CHANGE.
  
 1) PLEASE SUBMIT MECHANICAL PLANS FOR REVIEW.
  
 2) SUBMIT ENERGY CALCULATIONS, SEE 13-101.3.2.
  
 3) SUBMIT COOLING LOAD CALCULATIONS, SEE
 13-607.1.ABC.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-11-17 Cont ID  
Sent By jleech Date 2007-11-17 Time 06:15 Rev Time 0.00
Received By jleech Date 2007-11-17 Time 06:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-12 Cont ID  
Sent By jleech Date 2007-09-12 Time 13:44 Rev Time 0.00
Received By jleech Date 2007-09-12 Time 13:44 Sent To  
Notes
2007-09-12 13:47:35DENIED;
 1. PLANS TO BE SIGNED AND SEALED.
 2. SHOW PLUMBING CHANGES OR MARK ON PLANS " NO PLUMBING
 WORK TO BE DONE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-08-27 Cont ID  
Sent By choops Date 2007-08-27 Time 15:18 Rev Time 0.00
Received By choops Date 2007-08-27 Time 15:18 Sent To  
Notes
2007-08-27 15:18:43*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.