Plan Review Stops For Permit 07080427 |
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
P |
Date |
2007-09-10 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-09-10 |
Time |
10:17 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-09-10 |
Time |
10:17 |
Sent To |
PC |
|
Notes |
2007-09-10 10:22:27 | ****************PROVISO**************** | | A} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR | | VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED | | IMMEDIATELY AHEAD OF EACH MP REGULATOR. | | | | IF DRYER ROOM IS A CONFINED SPACE, OPENINGS REQUIRED | | PER SECTION 304.5 OR SECTION 304.6 SHALL BE INSTALLED. | | MINIMUM 1,100 CUBIC FEET REQUIRED. | | | | IF WATER HEATER ROOM IS A CONFINED | | SPACE, OPENINGS REQUIRED PER SECTION | | 304.5 OR SECTION 304.6 SHALL BE | | INSTALLED. | | MINIMUM 2,500 CUBIC FEET REQUIRED. | | | | REVIEW BY MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL: [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-09-10 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-09-10 |
Time |
10:22 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-08-15 |
Time |
09:14 |
Sent To |
|
|
Notes |
2007-08-15 09:14:35 | TO "G" BOX |
|
|
|