Plan Review Details - Permit 07080397
Plan Review Stops For Permit 07080397
Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2007-08-14 Time 13:11 Sent To  
Notes
2007-08-14 13:12:01TO "P" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-06 Cont ID  
Sent By rregueir Date 2007-09-06 Time 15:35 Rev Time 0.00
Received By rregueir Date 2007-09-06 Time 15:06 Sent To  
Notes
2007-09-06 15:06:47----------------DENIED---------------
  
 FBC 2004 W/ 2005 AND 2006 REVISIONS.
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLANS SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE, RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 FBC 106.1.1.
  
 2. THE WORK PROPOSED A LOUNGE AREA TO BE CONVERTED TO A
 PUBLIC RESTROOM. THIS CONSTITUTES AN INTERIOR REMODEL
 AND AS SUCH, AN INTERIOR REMODEL PERMIT IS REQUIRED. IN
 CONJUNCTION, SEPARATE SUB PERMITS ARE REQUIRED FOR ALL
 PLUMBING, ELECTRICAL AND MECHANICAL WORK AS REQUIRED TO
 CONVERT THIS SPACE IN A CODE COMPLIANT MANNER.
  
 3. THE PLANS WHICH WERE SUBMITTED CONTAIN AN
 ARCHITECT'S TITLE BLOCK. THIS WOULD MAKE OBS AND
 ASSOCIATES, AIA THE DESIGNERS OF RECORD FOR THIS
 PROJECT. AS SUCH, HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA, AS REQUIRED BY
 FLORIDA STATUTE. FBC 106.1
  
 4. PUBLIC TOILET ROOMS REQUIRE MECHANICAL VENTILATION
 AT A RATE OF 50 CFM PER WATER CLOSET OR URINAL IN
 ACCORDANCE WITH FBC,M TABLE 403.3.
  
 5. PROVISIONS SHALL BE MADE TO PROVIDE THE MINIMUM RATE
 OF VENTILATION WHENEVER THE SPACE IS OCCUPIED IN
 ACCORDANCE WITH FBC,M 401.2
  
 6. ALL AIR BEING SUPPLIED TO SUCH SPACES SHALL BE
 EXHAUSTED, INCLUDING ANY AIR SUPPLIED IN EXCESS OF THAT
 REQUIRED PER TABLE 403.3, AND IS PROHIBITED FROM BEING
 RECIRCULATED IN ACCORDANCE WITH FBC,M 403.2.1(3).
  
 7. PROVIDE EQUIPMENT SCHEDULE SHOWING EXHAUST FAN BEING
 USED, CFM AND ELECTRICAL RATINS. ALSO SHOW SIZE AND
 LOCATION OF DUCTWORK PER FBC 106.3.5.1.4.
  
 8. SHOW MECHANICAL EXHAUST TERMINATION LOCATION WHICH
 IS IN COMPLIANCE WITH FBC,M 401.5
  
 9. SHOW EXHAUST OUTDOOR OPENING PROTECTION IN
 ACCORDANCE WITH FBC,M 401.6
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-06 Cont ID  
Sent By mperson Date 2007-09-06 Time 09:31 Rev Time 0.00
Received By mperson Date 2007-09-06 Time 09:31 Sent To E
Notes
2007-09-06 14:44:40DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING WITH 2006 REVISIONS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
 ** FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. THE SUBMITTED DRAWINGS NEED TO BE SIGNED AND
 SEALED: IF THE DESIGN PROFESSIONAL IS AN ARCHITECT
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE AS PROVIDED FOR
 IN CHAPTER 481, FLORIDA STATUTES, PART 1, THEN HE OR
 SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA, AS REQUIRED BY FLORIDA STATUTE. THE FOLLOWING IS
 REQUIRED IN THE TITLE BLOCK.
  
 FAC-61G1-16.004 TITLE BLOCK:
 A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
  
 2. ONLY ONE SANITARY AND WATER ISOMETRIC RISER DIAGRAM
 WAS SUBMITTED PER FBC-2004 CHAPTER 1, CITY OF WEST PALM
 BEACH AMENDMENTS, SECTION 106.1 TWO (2) SETS OF PLANS
 ARE REQUIRED AND DRAWINGS MUST BE RESUBMITTED IN A
 DRAFTMAN LIKE MANNER.
  
 3. PLEASE SUBMIT A SEPERATE EXISTING FLOOR PLAN LAYOUT
 AND A SEPERATE PROPOSED FLOOR PLAN LAYOUT OF THE WOMENS
 BATHROOM INCLUDING TOILET STALL LAYOUTS, PER FBC-2004
 CHAPTER 1, SECTION 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELAVENT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 4. PER FBC-2004 PLUMBING WITH 2006 REVISIONS SECTION
 405.3.2 PUBLIC LAVATORIES. IN EMPLOYEE AND PUBLIC
 TOILET ROOMS, THE REQUIRED LAVATORY SHALL BE LOCATED IN
 THE SAME ROOM AS THE REQUIRED WATER CLOSET. THE
 SUBMITTED PLANS ARE INDICATING THE THREE PROPOSED WATER
 CLOSETS IN A ROOM (LOUNGE) ADJACENT TO THE EXISTING
 WOMENS BATHROOM. THIS IS NOT COMPLIANT.
  
 5. PER FBC-2004 PLUMBING WITH 2006 REVISIONS SECTIONS
 310 WASHROOM AND TOILET ROOM REQUREMENTS.
  
 A} SECTION 310.1, LIGHT AND VENTILATION. WASHROOMS AND
 TOILET ROOMS SHALL BE ILLUMINATED AND VENTILATED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING
 ANDFLORIDA BUILDING CODE, MECHANICAL.
  
 B} SECTION 310.2, LOCATION OF FIXTURES AND PIPING.
 PIPING, FIXTURES OR EQUIPMENT SHALL NOT BE LOCATED IN
 SUCH A MANNER AS TO INTERFERE WITH THE NRMAL OPERATION
 OF WINDOWS, DOORS OR OTHER MEANS OF EGRESS OPENINGS.
  
 C} SECTION 310.3, INTERIOR FINISH. INTERIOR FINNISH
 SURFACES OF TOILET ROOMS SHALL COMPLY WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 D} SECTION 310.4, WATER CLOSET COMPARTMENT. EACH WATER
 CLOSET UTILIZED BY THE PUBLIC OR EMPLOYEES SHALL OCUPY
 A SEPERATE COMPARTMENT WITH WALLS OR PARTITIONS AND A
 DOOR ENCLOSING THE FIXTURES TO ENSURE PRIVACY.
  
 6. PER FBC-2004 CHAPTER 11 SECTION 11-4.1.6(2)
 ALTERATIONS TO AN AREA CONTAINING A PRIMARY FUNCTION.
 (PROPOSED WOMENS BATHROOM) PLEASE PROVIDE A READILY
 ACCESSIBLE BATHROOM OR PROVE ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO ALTERED AREAS
 SHALL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20 PERCENT OF THE COST
 OF THE ALTERATION TO THE PRIMARY FUNCTION AREA.
  
 7. PLEASE PROVIDE THE FOLLOWING ADA REQUIREMENTS FOR
 THE PROPOSED WOMENS BATHROOM PER FBC-2004 CHAPTER 11
 THE FOLLOWING SECTIONS:
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
  
 A} 11-4.16.2 CLEAR FLOOR SPACE.
  
 B}11-4.16.3 HEIGHT.
  
 C} 11-4.16.4 GRAB BARS.
  
 D} 11-4.16.5 FLUSH CONTROLS.
  
 E} 11-4.16.6 DISPENSERS.
  
 ** 11-4.17 TOILET STALLS (DETAIL REQUIRED)
  
 A} 11-4.17.1 LOCATION.
  
 B} 11-4.17.2 WATER CLOSETS.
  
 C} 11-4.17.3 SIZE & LOCATION.
  
 D} 11-4.17.4 TOE CLEARANCES.
  
 E} 11-4.17.5 DOORS.
  
 F} 11-4.17.6 GRAB BARS.
  
 ** 11-4.19 LAVATORIES & MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
  
 A} 11-4.19.2 HEIGHT & CLEARANCES.
  
 B} 11-4.19.3 CLEAR FLOOR SPACE.
  
 C} 11-4.19.4 EXPOSED PIPES & SURFACES.
  
 D} 11-4.19.5 FAUCETS.
  
 E} 11-4.19.6 MIRRORS.
  
 8. NOTE: THERE ARE NO OTHER PERMIT APPLICATIONS FOR
 THIS PROPOSED WOMENS BATHROOM. THE VALUE IS TO LOW FOR
 THIS PROJECT PER FBC-2004, CHAPTER 1, SECTION 108.3,
 BUILDING PERMIT VALUATION: IF IN THE OPINION OF THE
 BUILDING OFFICIAL, THE CLAIMED VALUATION OF THE
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIORFINISH, NORMAL
 SITE WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS ECT.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. PLEASE ADJUST THIS VALUE ON THE RESUBMITTAL.
 THE SUBMITTED JOB COST INVOICES ARE INVALID WITHOUT
 THEM BEING SIGNED.
  
 9. PROVIDE A NOTICE OF COMMENCEMENT RECORDED WITH THE
 CLERK OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved