2007-08-29 07:58:20 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| 1.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER |
| OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER), |
| FBC*106.3.3. |
| |
| 2.)SEE OPENING 3.IT APPEARS THAT THE REQUIRED .5 |
| FACTOR FOR A 2" EDGE DISTANCE WAS APPLIED TO THE |
| BOTTOM, BUT IS REQUIRED AT THE TOP. |
| |
| 3.)SPANS SHOULD BE THE BLADE LENGTH.FOR WALL MOUNT |
| CONNECTIONS, THE BLADE LENGTH IS ALWAYS LONGER THAN THE |
| OPENING HEIGHT.PLEASE REVISE. |
| |
| 4.)THE MASTER PERMIT 06031357 WAS ISSUED WITH A |
| PROVISO TO REVISE SHEETS SP2 AND SP3.I MADE THIS |
| PROVISO ON 9/29/06 AT PERMIT ISSUANCE, WITH REQUESTS ON |
| 1/2/07 AND 3/28/07, AS FOLLOWS: |
| |
| "THIS PERMIT WAS ISSUED WITH A PROVISO TO REVISE SHEETS |
| SP2 AND SP3.THE ORIGINAL PLAN, SHEET SP3, WAS |
| REDLINED PER AGREEMENT WITH ARCHITECT.RAMP SECTION 3 |
| IS TO COMPLY WITH FBC11-4.8.4(2), THE BOTTOM OF EACH |
| RAMP SHALL HAVE NOT LESS THAN 72 INCHES OF STRAIGHT AND |
| LEVEL CLEARANCE.PLAN STILL SHOWS 60IN." |
| |
| THE REVISED SHEETS HAVE NOT BEEN SUBMITTED.PLEASE |
| SUBMIT AT THIS TIME. |
| |
| |