Plan Review Details - Permit 07080345
Plan Review Stops For Permit 07080345
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-07 Cont ID  
Sent By adarroug Date 2007-09-07 Time 14:12 Rev Time 0.00
Received By adarroug Date 2007-09-07 Time 14:12 Sent To M
Notes
2007-09-07 14:12:35TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-30 Cont ID  
Sent By adarroug Date 2007-08-30 Time 15:52 Rev Time 0.00
Received By adarroug Date 2007-08-30 Time 15:52 Sent To M
Notes
2007-08-30 15:52:58TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-30 Cont ID  
Sent By adarroug Date 2007-08-14 Time 15:52 Rev Time 0.00
Received By adarroug Date 2007-08-13 Time 14:26 Sent To  
Notes
2007-08-13 14:26:54TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-09-12 Cont ID  
Sent By tgordon Date 2007-09-12 Time 12:17 Rev Time 0.25
Received By tgordon Date 2007-09-12 Time 12:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-09-04 Cont ID  
Sent By tgordon Date 2007-09-04 Time 09:06 Rev Time 0.30
Received By tgordon Date 2007-09-04 Time 09:06 Sent To  
Notes
2007-09-04 09:27:45PLAN REVIEW UNDER THE 2001 FLORIDA BUILDING CODE &
 REFERENCED CODES, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (WPB), FLORIDA ADMINISTRATIVE CODE (FAC), AND
 FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) COOLING LOAD CALCULATIONS SUBMITTED ARE CALLING FOR
 18,439 SENSIBLE BTU'S, MECHANICAL PLANS ARE CALLING FOR
 30,400 SENSIBLE BTU'S. THE MECHANICAL PLANS SENSIBLE
 BTU'S MAY ONLY BE 20% MORE THAN THE COOLING LOAD
 CALCULATIONS, SEE 2001 FBC 13-607.1.ABC.1.1. PLEASE
 CORRECT.
  
 2) PLEASE SUBMIT TWO (2) COPIES OF THE ENERGY
 CALCULATIONS AND COOLING LOAD CALCULATIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-08-14 Cont ID  
Sent By tgordon Date 2007-08-14 Time 09:47 Rev Time 0.30
Received By tgordon Date 2007-08-14 Time 09:47 Sent To  
Notes
2007-08-14 09:54:44PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER
 1 CITY OF WEST PALM BEACH AMENDMENTS.
  
 *** DENIED ***
 1) THEIR ARE NO APPROVED MECHANICAL PLANS WITH MASTER
 PERMIT #05061829, PLEASE SUBMIT MECHANICAL PLANS FOR
 REVIEW, SEE 2004 FBC, CITYWPB AMEND. 106.3.5.4 (10).
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 3) SUBMIT TWO COPIES OF THE ENERGY CALCULATIONS AND
 COOLING LOAD CAL'S.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].