Plan Review Details - Permit 07080345
Plan Review Stops For Permit 07080345 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-09-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-07 |
Time |
14:12 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-07 |
Time |
14:12 |
Sent To |
M |
|
Notes |
2007-09-07 14:12:35 | TO "M" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-08-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-30 |
Time |
15:52 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-30 |
Time |
15:52 |
Sent To |
M |
|
Notes |
2007-08-30 15:52:58 | TO "M" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-08-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-14 |
Time |
15:52 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-13 |
Time |
14:26 |
Sent To |
|
|
Notes |
2007-08-13 14:26:54 | TO "M" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2007-09-12 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-09-12 |
Time |
12:17 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2007-09-12 |
Time |
12:16 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2007-09-04 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-09-04 |
Time |
09:06 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-09-04 |
Time |
09:06 |
Sent To |
|
|
Notes |
2007-09-04 09:27:45 | PLAN REVIEW UNDER THE 2001 FLORIDA BUILDING CODE & | | REFERENCED CODES, CITY OF WEST PALM BEACH AMENDMENTS TO | | CHAPTER 1 (WPB), FLORIDA ADMINISTRATIVE CODE (FAC), AND | | FLORIDA STATUTES (FS). | | | | *** DENIED *** | | 1) COOLING LOAD CALCULATIONS SUBMITTED ARE CALLING FOR | | 18,439 SENSIBLE BTU'S, MECHANICAL PLANS ARE CALLING FOR | | 30,400 SENSIBLE BTU'S. THE MECHANICAL PLANS SENSIBLE | | BTU'S MAY ONLY BE 20% MORE THAN THE COOLING LOAD | | CALCULATIONS, SEE 2001 FBC 13-607.1.ABC.1.1. PLEASE | | CORRECT. | | | | 2) PLEASE SUBMIT TWO (2) COPIES OF THE ENERGY | | CALCULATIONS AND COOLING LOAD CALCULATIONS. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-08-14 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-08-14 |
Time |
09:47 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-08-14 |
Time |
09:47 |
Sent To |
|
|
Notes |
2007-08-14 09:54:44 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2005, 2006 REVISIONS, AND CHAPTER | | 1 CITY OF WEST PALM BEACH AMENDMENTS. | | | | *** DENIED *** | | 1) THEIR ARE NO APPROVED MECHANICAL PLANS WITH MASTER | | PERMIT #05061829, PLEASE SUBMIT MECHANICAL PLANS FOR | | REVIEW, SEE 2004 FBC, CITYWPB AMEND. 106.3.5.4 (10). | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | 3) SUBMIT TWO COPIES OF THE ENERGY CALCULATIONS AND | | COOLING LOAD CAL'S. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL: [email protected]. |
|
|
|