Plan Review Details - Permit 07080336
Plan Review Stops For Permit 07080336
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-04 Cont ID  
Sent By amorse Date 2007-10-04 Time 16:41 Rev Time 0.00
Received By amorse Date 2007-10-04 Time 16:41 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-18 Cont ID  
Sent By amorse Date 2007-09-18 Time 17:05 Rev Time 0.00
Received By amorse Date 2007-09-18 Time 17:05 Sent To PC
Notes
2007-09-18 17:05:52 
  
 DENIED
  
 COMMENT FROM THE FIRST REVIEW HAS NOT BEEN CORRECTED,
 THE WORD "CERTIFICATE" ON ALL ENGINEER EMBOSSED SEALS
 IS NO LONGER COMPLIANT WITH FPBE RULES. PLEASE SEE
 ATTACHED LETTER THAT WAS PROVIDED TO THE BUILDING DEPT
 BY FLORIDA BOARD OF PROFESSIONAL ENGINEERS.
  
 1)PER FLORIDA ADMINISTRATIVE CODE 61G15-23.001(1) AND
 THE BOARD OF PROFESSIONAL ENGINEERS THE SEAL BEING USED
 BY THE PROFESSIONAL ENGINEER OF RECORD HAS BEEN
 OBSOLETE SINCE DEC. 31, 2005. PLEASE HAVE THE ENGINEER
 PROVIDE NEW DRAWINGS WITH THE CORRECT SEAL
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-04 Cont ID  
Sent By btrobaug Date 2007-09-18 Time 13:23 Rev Time 0.00
Received By amorse Date 2007-09-04 Time 18:53 Sent To PC
Notes
2007-09-04 18:53:43 
  
  
 DENIED
  
 1)PER FLORIDA ADMINISTRATIVE CODE 61G15-23.001(1) AND
 THE BOARD OF PROFESSIONAL ENGINEERS THE SEAL BEING USED
 BY THE PROFESSIONAL ENGINEER OF RECORD HAS BEEN
 OBSOLETE SINCE DEC. 31, 2005. PLEASE HAVE THE ENGINEER
 PROVIDE NEW DRAWINGS WITH THE CORRECT SEAL
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-01 Cont ID  
Sent By btrobaug Date 2007-10-01 Time 11:46 Rev Time 0.00
Received By btrobaug Date 2007-10-01 Time 11:46 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-09-18 Cont ID  
Sent By btrobaug Date 2007-09-18 Time 13:42 Rev Time 0.00
Received By btrobaug Date 2007-09-18 Time 13:41 Sent To B
Notes
2007-09-18 13:42:23 
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 THE ENGINEER OF RECORD MUST SEAL THE DOCUMENTS WITH A
 SEAL ACCEPTABLETO THE BOARD PER 61G15-23.001, AND
 ILLUSTRATED IN SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-18 Cont ID  
Sent By btrobaug Date 2007-08-20 Time 14:30 Rev Time 0.00
Received By btrobaug Date 2007-08-20 Time 14:28 Sent To B
Notes
2007-09-18 13:27:35 
  
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 THE ENGINEER OF RECORD MUST SEAL THE DOCUMENTS WITH A
 SEAL ACCEPTABLETO THE BOARD PER 61G15-23.001, AND
 ILLUSTRATED IN SAME.
  
 THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG
 WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-24 Cont ID  
Sent By adarroug Date 2007-09-24 Time 12:12 Rev Time 0.00
Received By adarroug Date 2007-09-24 Time 12:12 Sent To E
Notes
2007-09-24 12:12:26TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-14 Cont ID  
Sent By adarroug Date 2007-09-14 Time 08:49 Rev Time 0.00
Received By adarroug Date 2007-09-14 Time 08:49 Sent To E
Notes
2007-09-14 08:50:04TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-09-04 Time   Rev Time 0.00
Received By adarroug Date 2007-08-13 Time 11:01 Sent To  
Notes
2007-08-13 11:01:17TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2007-08-14 Cont ID  
Sent By choops Date 2007-08-14 Time 11:43 Rev Time 0.00
Received By choops Date 2007-08-14 Time 11:43 Sent To E
Notes
2007-08-14 11:43:26ALL ILLUMINATED SIGNS MUST CONFORM TO THE CITY OF WEST
 PALM BEACH ZONING AND LAND DEVELOPMENT REGULATIONS,
 SECTIONS 94-402(B) , 94-406 , AND ANY OTHER
 RESTRICTIONS DESIGNATED BY THE ZONING DISTRICT IN WHICH
 IT IS LOCATED.