Plan Review Stops For Permit 07080268 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2008-01-23 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2008-01-23 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2008-01-23 |
Time |
12:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2007-11-19 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-11-19 |
Time |
10:30 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-11-19 |
Time |
07:56 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-08-25 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-08-25 |
Time |
13:11 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-08-25 |
Time |
08:43 |
Sent To |
|
|
Notes |
2007-08-25 13:10:59 | | | BUILDING PLAN REVIEW | | PERMIT: 07080268 | | ADD: 3901 36TH CT. | | CONT: ARCCW INC. | | TEL: (561)201-5340 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW: 1ST | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | YOUR ANTICIPATED COOPERATION. | | | | 2)WPB ADMIN CODE 106.3* PRODUCT | | APPROVALS. THOSE PRODUCT WHICH ARE | | REGULATED BY DCA RULE 9B-72 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | FOR JURISDICTIONAL APPROVAL. | | | | 3)110.2* W. P. B. ADMINISTRATIVE | | CODE, INFORMATION THAT IS REQUIRED FOR | | RECORD KEEPING & FOR CERTIFICATE OF | | OCCUPANCY: | | A) THE EDITION OF THE CODE UNDER WHICH | | THE PROJECT IS DESIGNED. | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | WITH THE PROVISIONS OF CHAPTER 3. | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | IN CHAPTER 6, TABLE 601. | | D) THE OCCUPANT LOAD, SEE 1004. | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | PROVIDED | | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. | | G) ANY SPECIAL STIPULATIONS & CONDITIONS | | OF THE BUILDING PERMIT | | . ------------------------------------- | | ) NUMBER OF UNITS | | ) NUMBER OF FLOORS | | ) NUMBER OF BEDROOMS | | ) NUMBER OF ROOMS | | ) NUMBER OF BEDROOMS | | ) SQ. FT. LIV SPACE/ FL | | ) SQ. FT. FOOTPRINT | | | | 4)ARE THE NEW WINDOWS IMPACT WINDOWS? ACCORDING TO | | THE PRODUCT APPORVALS THEY ARE. IF NOT PROVIDE THE | | CORRECT PRODUCT APPROVALS. ALL PRODUCT APPROVALS SHALL | | BE APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR | | TO SUBMITTAL. | | | | 5)THE SHUTTER INSTALLATION SCHEDULE SUBMITTED IS | | MISSING SOME REQUIRED INFORMATION. ALSO ON THE PRODUCT | | APPROVAL, CIRCLE THE ITEMS WHICH WILL BE USED. EACH | | OPENING SHALL HAVE ITS OWN INFORMATION STATED ON THE | | SCHEDULE. INDICATE THE FASTENING METHOD FROM PAGE #2 OR | | #3. | | | | 6)PROVIDE ELEVATION DRAWINGS SHOWING WHAT IS ABOVE | | THE FIRE DAMAGE AREA. WHAT MATERIAL WILL BE USED TO | | REPLACE EXISTING FLOOR ABOVE? IS THE AREA ABOVE THE | | FIRE DAMAGE CEILING PART OF APT #105 OR IS IT A | | DIFFERENT UNIT? PLEASE INDICATE IF THERE IS MORE THAN | | ONE UNIT AFFECTED BY THE FIRE. | | | | 7)INDICATE THE GRADE AND SPECIES OF WOOD WHICH WILL | | BE USED TO DO THE FLOOR JOIST REPAIR. FBC. 2308.8 | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2008-01-28 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-01-28 |
Time |
10:14 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-01-28 |
Time |
10:14 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2008-01-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-01-15 |
Time |
20:17 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-01-15 |
Time |
20:17 |
Sent To |
|
|
Notes |
2008-01-15 20:17:57 | ** DENIED 3RD REVIEW ** | | | | 1) NOTE: PLEASE SEE THE NOTES FROM PREVIOUS REVIEWS | | WHICH CLEARLY STATE PLANS MUST CONTAIN A DESIGN | | PROFESSIONAL TAKING RESPONSIBILITY OF THE PLANS PER | | 481.229, 471.025 OR 468. | | PLEASE SEE NONE OF THESE HAVE BEEN DONE. | | THE PREVIOUS PLANS CONTAINED A TITLE BLOCK FOR AN | | ENGINEER AND NOW THAT TITLE BLOCK HAS BEEN REMOVED? | | | | 2) NOTE: PLEASE SEE THE LOAD CALCULATIONS AS SUBMITTED | | ARE NOW ONLY BEING SUBMITTED FOR THE FIRST TIME UNDER | | RESIDENTIAL FOR THE FIRST REVIEW. | | PLEASE SEE NEC 220.60 AS THE HIGHER OF THE TWO LOADS | | FOR A/C SHALL BE FIGURED. AS THE OVER CURRENT | | PROTECTION FOR THE CU IS SHOWN SUBSTANTIALLY HIGHER IS | | THIS LOAD FOR THE CU HIGHER? | | IF SO, PLEASE ADJUST CALCULATIONS. | | PLEASE KNOW IF THIS NOT HIGHER THEN THESE ARE OK. | | | | PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW WERE NOT | | COMPLETELY ADDRESSED BY LISTING THE ARC FAULT PROTECTED | | CIRCUITS AS REQUIRED PER 408.4 AND 210.12. INSTEAD THE | | CODE SECTION WAS QUOTED ON THE PLANS. | | | | ** PLEASE SEE ITEM # 2 FOR THE ABOVE MAY BE PART OF A | | PROVISO HOWEVER THE PLANS SHALL CONTAIN A DESIGN | | PROFESSIONAL AS STATED ABOVE. | | | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-11-09 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-11-09 |
Time |
16:48 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-11-09 |
Time |
16:48 |
Sent To |
|
|
Notes |
2007-11-09 16:49:59 | ** DENIED 2ND REVIEW ** | | | | ** AS STATED ON PREVIOUS REVIEW, PLEASE SUBMIT | | COMPLETED PLANS FOR MINIMUM NEC COMPLIANCE. | | PLEASE SEE MANY OF THE CODE SECTIONS PREVIOUSLY GIVEN | | ARE NOT ON PLANS. | | | | | | 1) NOTE:PLEASE REFERENCE ALL CODES ON PLANS AS | | PREVIOUSLY STATED AND REQUIRED BY FBC. | | 2004 FBC/W2006 REVISIONS. | | 2005 NFPA-70 | | 2002 NFPA-72 | | 2003 NFPA-101 | | | | ** SOME OF THESE MAY BE SHOWN ALREADY. | | | | 2) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR | | RESIDENTIAL DWELLING. NEC 220 | | | | 3) NOTE: PLEASE SEE MIN VA FOR WASHER/LAUNDRY CIRCUIT | | SHALL MEET 220.53. | | 1500 MIN. | | | | 4) NOTE: PLEASE CORRELATE RISER WITH ACTUAL ELECTRICAL | | SERVICE AT LOCATION. | | PLANS INDICATE A METER CENTER AND RISER SHOWS A | | SEPARATE SERVICE WITH METER MAIN COMBO PANEL. | | THESE ARE NOT COORDINATED OR CLEAR. | | 230.2 | | FBC 106.3.5.4, 106.1.2 | | | | 5) NOTE: PLANS ARE NOT SIGNED DATED OR SEALED BY THE | | DESIGNER OF RECORD. | | FS471.025 | | | | 6) NOTE: PLEASE LIST ALL ARC FAULT CIRCUITS PER 210.12 | | | | 7) NOTE: PLANS MISSING EGRESS LIGHTING AT DOOR. 210.70, | | LS 101 7.8 | | | | 8) NOTE: PLANS MISSING A/C CU DISCONNECT, GFI ETC. | | PLEASE SEE 210.8A, 210.63, 440.11 | | | | PLEASE SUBMIT COMPLETED PLANS. | | | | | | ** PLEASE KNOW AS THERE ARE ITEMS WHICH ARE NOT SHOWN | | AT THIS TIME, A COMPLETE REVIEW FOR CODE COMPLIANCE CAN | | NOT BE DONE. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-08-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-08-27 |
Time |
20:27 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-08-27 |
Time |
20:27 |
Sent To |
|
|
Notes |
2007-08-27 20:28:01 | 2007-08-27 20:28:01 | | | | ** DENIED ** | | | | 1) NOTE: PLEASE SEE FBC R313 AS NEW SMOKE ALARM/DICTION | | DEVICES ARE REQUIRED INSIDE AND OUTSIDE ALL SLEEPING | | ROOMS. NFPA-72 11.5.1.1, 11.8.3 | | | | 2) NOTE: PLEASE INDICATE THE NEW AIC RATING FOR NEW | | MAINS AND SERVICE EQUIPMENT. | | 110.9, FBC 106.1.2, 106.1.1 | | | | 3) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING | | CONDUCTOR AFTER THE FIRST MEANS OF DISCONNECT AS | | REQUIRED PER 250.110, 250.122, 250.24 ETC. | | | | 4) NOTE: PLEASE SEE THE RISER SEEMS TO SHOW ONLY ONE | | SERVICE AND NO INDICATION OF THE EXISTING OTHER MAINS | | ETC. | | THIS IS AN APARTMENT, AS APPLIED AND PLEASE SHOW THE | | BUILDING SERVICE, LOCATION ETC. 230.70,230.71,230.72. | | | | 5) NOTE: PLEASE INDICATE THE CIRCUITS WHICH ARE | | REQUIRED TO BE SPECIFIC TO ROOMS ARE AREAS IN WHICH | | THEY FEED. | | PLEASE SHOW THE CIRCUITING ON PLANS AND CORRELATE WITH | | THE SUBMITTED PANEL SCHEDULE. | | 408.4, 240.4, 310.16. | | FBC 106.3.5.1.2, 106.3.5.4, 106.1.2, 106.1.1 | | | | 6) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION ON THE | | AHU IS TOO HIGHFOR THE 5KW HEAT SHOWN. | | PLEASE ADJUST. (30AMP)? | | | | 7) NOTE: PLEASE SEE THE MINIMUM LOAD FOR THE WATER | | HEATER IS TO BE SIZED AT 125%. | | 422.13 | | ADJUST LOAD CALCULATIONS. | | | | | | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2008-01-24 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-01-24 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-01-24 |
Time |
10:04 |
Sent To |
E |
|
Notes |
2008-01-24 10:19:37 | *****APPROVED**** | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | BEEN ADDRESSED;PLAN SHEETS A-2 AND A-4 WERE STAMPED, | | INITIALED, AND DATED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2007-11-16 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2007-11-16 |
Time |
10:34 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2007-11-16 |
Time |
10:34 |
Sent To |
|
|
Notes |
2007-11-16 10:43:19 | ***DENIED*** | | | | 1) OK | | | | 2) OK | | | | 3) SHEET A2 HAS BEEN REFERENCED FOR CORRECTION BUT NO | | NOTE WAS FOUND. PLEASE BE ADVISED THAT IN ADDITION TO | | APPLICABLE BUILDING CODES, WORK, SPECIFICALLY LIFE | | SAFETY SHALL COMPLY WITH NFPA 101, 2003 EDITION. | | | | 4) SHEET A2 WAS REFERENCED FOR CORRECTION BUT NO NOTE | | WAS FOUND. PLEASE ADD TO PLANS. | | | | 5) INTERIOR FINISH CLASSIFICATION TO BE PROVIDED IN | | TERMS OF CLASS A,B,ORC. INFORMATION SHALL BE SPECIFIC | | TO THIS SCOPE OF WORK AND NOT GENERAL. | | | | 6) SMOKE ALARM LOCATIONS HAVE BEEN ADDED TO PLANS. | | SHEET A4 DOES REFERENCE SMOKE DETECTORS UNDER | | ELECTRICAL NOTES. PLEASE CORRELATE INFORMATION AS THE | | TERM SMOKE DETECTOR WOULD INDICATE A FIRE ALARM | | SYSTEM. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-08-29 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-08-29 |
Time |
15:41 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-08-29 |
Time |
15:12 |
Sent To |
|
|
Notes |
2007-08-29 15:35:45 | *****UNSAT**** | | | | | | 1.ON SHEET A1, THE SITE MAP REFERENCES NORHTWEST 36TH | | STREET, NORTHWEST 36TH COURT, AND AUSTRALIAN BOULEVARD. | | THE CORRECT VERBAGE FOR THOSE ROADWAYS ARE:36TH | | STREET, 36TH COURT, AND NORTH AUSTRALIAN AVENUE. | | | | 2.THE UNIT NUMBER OF THE ADDRESSED PROJECT LOCATED IN | | THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET AND ALSO | | SHOWN ON THE SITE MAP DOES NOT CORRELATE WITH THE UNIT | | NUMBER (105-B) AS RECORDED IN THE CITY'S PERMITTING | | SYSTEM OR THAT ON THE PERMIT APPLICATION. | | | | 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | REFERENCED. | | | | 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 | | | | 5.SPECIFY THE INTERIOR FINISH MATERIAL FOR ANY | | REPLACED DRYWALL AND/OR CEILING IN TERMS OF CLASS A, | | CLASS B, OR CLASS C. | | | | 6.SHOW THE LOCATION OF THE SMOKE ALARMS IN THE UNIT. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2008-01-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-01-15 |
Time |
09:40 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-01-15 |
Time |
09:40 |
Sent To |
|
|
Notes |
2008-01-15 09:41:13 | TO "BOB"#3 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-11-07 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-07 |
Time |
16:06 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-07 |
Time |
16:06 |
Sent To |
|
|
Notes |
2007-11-09 11:51:19 | TO "BOB"#13 | 2007-11-07 16:06:33 | WAITING FOR "BOB" |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-08-31 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-08-31 |
Time |
16:36 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-08-09 |
Time |
09:50 |
Sent To |
|
|
Notes |
2007-08-23 13:28:18 | TO "BOB"#11 | 2007-08-09 09:51:41 | WAITING FOR COMM BOARD. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2007-08-24 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-08-24 |
Time |
08:50 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2007-08-24 |
Time |
08:50 |
Sent To |
|
|
Notes |
2007-08-24 08:50:50 | NO MECHANICAL PLANS SUBMITTED, AND NO | | MECHANICAL PERMIT NUMBER APPLIED FOR AT | | THIS TIME. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2007-08-31 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-08-31 |
Time |
16:29 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-08-31 |
Time |
16:29 |
Sent To |
|
|
Notes |
2007-08-31 16:31:13 | NOTE: THERE ARE NO PLUMBING PLANS SUBMITTED, AND NO | | PLUMBING PERMT NUMBER APPLIED FOR AT THIS TIME. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2007-08-27 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-08-27 |
Time |
15:31 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-08-27 |
Time |
15:31 |
Sent To |
|
|
Notes |
2007-08-27 15:31:16 | *ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK | | DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE. |
|
|