Plan Review Details - Permit 07080266
Plan Review Stops For Permit 07080266
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-01 Cont ID  
Sent By mjacobs Date 2007-09-01 Time 13:33 Rev Time 0.00
Received By mjacobs Date 2007-09-01 Time 08:14 Sent To  
Notes
2007-09-01 13:33:40 
 BUILDING PLAN REVIEW
 PERMIT: 07080266
 ADD: 3111- 45TH STREET #8
 CONT: JOE SCHMIDT CONST. INC.
 TEL: (561)248-8860
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)SUBMIT AN EXISTING AND PROPOSED FLOOR PLAN OF THE
 PROJECT INDICATING THE DEMOLITION OF ANY WALLS OR
 SYSTEMS. IF THE DRY CLEANING BUSINESS IS IN OPERATION,
 INDICATE ON THE PLANS, IF NOT STATE THE PREVIOUS
 OCCUPANCY. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED. FBC 106.1.1
  
 4) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR RECORD KEEPING.
  
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT IS
 DESIGNED. WITH THE AMENDED REVISIONS
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004. OK.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 . -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
  
 5)106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. THE PRODUCT APPROVALS ARE
 MISSING THE STATE COVER SHEETS WITH THE FL#, AND SHALL
 BE REVIEWED AND APPROVED IN ?WRITING? BY THE DESIGNER
 OF RECORD. PROVIDE PRODUCT APPROVAL FOR THE BIRD
 SCREEN.
  
 6)INDICATE THE USE OF EACHROOM, INCLUDING THE TWO
 HOUR SEPARATION SECTION AND SHOW THE TYPE OF CEILING
 THROUGHOUT THE AREA. THE PLANS SHALL BE DIMENSIONED PER
 FBC 106.1.1
  
 7)SHOW IN DETAIL HOW THE COUNTER WILL MEET THE
 REQUIREMENTS OF FBC 11-7(2) (I) WHERE A PORTION OF THE
 MAIN COUNTER IS A MINIMUM OF 36 INCHES IN LENGTH AND A
 MAXIMUM HEIGHT OF 36 INCHES. SUBMIT ELEVATION
 DRAWINGS.
  
 8)SHOW THE WALL ASSEMBLY OF THE EXISTING WALL SHOWING
 HOW IT MEETS THE TWO HOUR RATING AS STATED ON THE
 DRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-09-06 Cont ID  
Sent By btrobaug Date 2007-09-06 Time 15:19 Rev Time 0.00
Received By btrobaug Date 2007-09-06 Time 13:10 Sent To  
Notes
2007-09-06 13:33:22 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN
 PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE
 EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE
 PLAN.
  
 2} INDICATE PER 230.2 WHY ANOTHER SERVICE AT THIS
 LOCATION IS WARRANTED. ALSO SEE 230.72.
  
 3} INDICATE COMPLIANCE WITH THE APPLICABLE SECTIONS OF
 CHAPTER 13 ENERGY EFFICIENCY, FBC.
  
 4} SEE 306.2 FOR OCCUPANCY CLASSIFICATION OF A DRY
 CLEANER, F-1. CHANGE ON SHEET A1.
  
 5}INDICATE COMPLIANCE WITH NFPA-32, DECLARE PLANT
 TYPE SO THAT ELECTRICAL INSTALLATION CLASS AND DIVISION
 CAN BE DETERMINED.
  
 6} PROVIDE AN EQUIPMENT SCHEDULE FOR EQUIPMENT BEING
 INSTALLED, WITH SPECIFICATIONS AND ELECTRICAL
 REQUIREMENTS.
  
 7} COMPLY WITH NFPA-79 WHERE APPLICABLE.
  
 PLEASE REMOVE OLD SHEETS, INSERT NEW
 ONES, SUBMIT OLD SHEETS TO EXPEDITE
 REVIEW AND SUBMIT WRITTEN RESPONSE TO
 THE COMMENTS MADE IN THIS REVIEW.
  
 INDICATE THE CODE CYCLES THIS PROJECT WAS DESIGNED
 UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES FOR CLARITY
 IN THE FIELD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-09-07 Cont ID  
Sent By mwennerg Date 2007-09-07 Time 14:46 Rev Time 0.00
Received By mwennerg Date 2007-09-07 Time 14:46 Sent To  
Notes
2007-09-07 14:54:01***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING CODES AND NFPA
 32, WORK SHALL COMPLY WITH NFPA 101, 2003 EDITION.
  
 2) PLEASE PROVIDE INFORMATION REGARDING TYPE OF
 SOLVENTS THAT WILL BE USED, AND ANY OTHER HAZARDOUS
 PRODUCTS USED FOR THIS PROCESS.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER REMODEL.
  
 4) NO SMOKING SIGNS WILL BE REQUIRED TO BE POSTED
 INSIDE THE PLANT.
  
 5) WHAT MEASURES WILL BE TAKEN TO PREVENT THE LEAKING
 OR SPILL OF HAZARDOUS PRODUCTS?
  
 6) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-09-05 Cont ID  
Sent By mperson Date 2007-09-05 Time 13:16 Rev Time 0.00
Received By mperson Date 2007-09-05 Time 13:16 Sent To  
Notes
2007-09-05 13:43:21DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET P-1 GAS RISER DIAGRAM: PLEASE CORRELATE THE
 TYPE OF GAS BEING USED. "GAS NOTES" ARE INDICATING A
 NATURAL GAS SIZING TABLE FOR 0.5 PSI AND THE "GAS
 TABLE" IS INDICATING LP SERVICE LOAD AND LP APPLIANCE.
 THIS IS CONFUSING, PLEASE CLEARLY INDICATE THE GAS TYPE
 ON THE RESUBMITTAL. PER FBC-2004 CHAPTER 1 SECTION
 106.1.1, CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE, AND EXTENT OF
 THE WORK PROPOSED.
  
 2. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 NOTE: THERE IS NO CLEAR INDICATION OF THE DELIVERY
 PRESSURE BEING INDICATED ON THE PRINTS OTHER THAN THE
 SIZING TABLE IN THE "GAS NOTES". PLEASE DO THIS ON THE
 RESUBMMITTAL.
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: PLEASE SUBMIT MANUFACTURER SPECIFICATION SHEETS
 FOR THE DRYER AND THE BOILER WITH THE MANUFACTURER
 NAME, MODEL NUMBER, BTU LOAD, AND A LISTING FROM A
 NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) ON THE
 RESUBMITTAL.
  
 4. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 5. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 6.6.1.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK
 ON THE INDICATED PLAN SHEETS BY THIS PLANS EXAMINER FOR
 REFERENCE FOR THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2007-08-08 Time   Rev Time 0.00
Received By mmiller Date 2007-08-08 Time 18:50 Sent To  
Notes
2007-08-31 10:44:11TO "BOB"#3
2007-08-08 18:50:31WAITING FOR BOB BOARD #03

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-08 Cont ID  
Sent By dpalmer Date 2007-09-08 Time 15:07 Rev Time 0.00
Received By dpalmer Date 2007-09-08 Time 15:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-09-07 Cont ID  
Sent By tgordon Date 2007-09-07 Time 08:42 Rev Time 1.00
Received By tgordon Date 2007-09-07 Time 08:42 Sent To  
Notes
2007-09-07 09:12:26PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) THE ENGINEER J. DAVID PUGA PRINTED NAME AND LICENSE
 NUMBER IN TITLE BLOCK IS NOT LEGIBLE, SEE FAC
 61G15-23.002 (2). PLEASE CORRECT.
  
 2) SHOW TYPE OF DRY CLEANING SYSTEM I, II, III, IV, OR
 V. SEE MECH. CH. 2. AND SHOW HOW THE PLANT WILL COMPLY
 WITH MECH. 502.6, 502.6.1, AND 502.6.2 REGARDING
 VENTILATION.
  
 3) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE
 GAS BOILER AND GAS CLOTHES DRYER.
  
 4) STATE ON PLAN IF GAS CLOTHES DRYER IS TYPE 1 OR 2.
 IF TYPE 2 PROVIDE A DETAIL SHOWING INSTALLATION OF THE
 EXHAUST TO COMPLY WITH MECH. 504.7 REGARDING 6"
 CLEARANCE.
  
 5) SHOW HOW THE GAS CLOTHES DRYER COMPLIES WITH MECH.
 504.5 REGARDING MAKE-UP AIR.
  
 6) STATE OR SHOW WERE THE CLOTHES DRYER EXHAUST WILL
 TERMINATE. IF AT THE SIDE WALL IT MAY NOT TERMINATE
 NEAR THE WATER CHILLER, SEE MECH. 501.2.
  
 7) SHOW COMPLIANCE WITH MECH. 1004.3 GUARDING 18"
 CLEARANCE AROUND GAS BOILER.
  
 8)PLEASE SUBMIT PRODUCT APPROVAL FOR THE 24X24 WALL
 LOUVERS, SEE FS 553.842(1) AND FAC RULE 9B-72,
 9B-72.005, AND FAC 9B-72.010(31)(C).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-04 Cont ID  
Sent By mperson Date 2007-09-05 Time 14:36 Rev Time 0.00
Received By mperson Date 2007-09-04 Time 14:36 Sent To G
Notes
2007-09-04 16:54:06DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING W/2006 REV.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
 ** FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE SUBMIT A SEPERATE EXISTING FLOOR PLAN
 DRAWING INDICATING THE DEMOLITION OF ANY WALLS OR
 SYSTEMS AND A SEPERATE FLOOR PLAN DRAWING OF THE
 PROPOSED PROJECT. IF THIS IS AN EXISTING DRYCLEANING
 BUSSINESS IN OPERATION PLEASE INDICATE THIS ON THE
 RESUBMITTAL. IF NOT PLEASE STATE THE PREVIOUS OCCUPANCY
 PER FBC-2004 CHAPTER 1, SECTION 106.1.1, CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE, AND EXTENT OF THE WORK PROPOSED.
  
 2. SHEET P-1 SANITARY RISER DIAGRAM: PER FBC-2004
 PLUMBING WITH 2006 REVISIONS TABLE 709.2 THE 3 INCH FS
 TRAPS ARE INDICATING THE WRONG DRAINAGE FIXTURE UNIT
 VALUE OF (2 FU) THE CORRECT DRAINAGE FIXTURE UNIT VALUE
 IS (5 FU) FOR A 3 INCH TRAP. PLEASE REFERENCE THE RED
 LINE CORRECTIONS OF THIS AND THE UNDERGROUND
 COMBINATION WASTE AND VENT PIPING.
  
 3. SHEET P-1 SANITARY RISER DIAGRAM IS INDICATING THE
 FS-1 BOILER ROOM FLOOR DRAIN WITH A 3 INCH TRAP AND
 SHEET P-2 FIXTURE CONNECTION SCHEDULE IS INDICATING THE
 FS-1 BOILER ROOM FLOOR DRAIN WITH A 4 INCH TRAP. PLEASE
 CORRELATE AND CORRECT THIS ON THE RESUBMITTAL PER
 FBC-2004 CHAPTER 1 SECTION 106.1.1. ALSO IF FS-1 HAS A
 4 INCH TRAP PLEASE ADJUST THE (DFU) ACCORDINGLY ON
 SHEET P-1 SANITARY RISER DIAGRAM.
  
 4. PER FBC-2004 PLUMBING WITH 2006 REVISIONS A
 DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1 AND SHALL
 BE ADA COMPLIANT PER FBC-2004 CHAPTER 11 THE FOLLOWING
 SECTIONS:
  
 A} 11-4.15, DRINKING FOUNTAINS AND WATER COOLERS
 ELEVATION DETAIL REQUIRED.
  
 B} 11-4.15.2, SPOUT HEIGHT.
  
 C} 11-4.15.3, SPOUT LOCATION.
  
 D} 11-4.15.4, CONTROLS.
  
 E} 11-4.15.5, CLEARENCES (1)(2).
  
 F} 11-4.1.3 (10) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN CAAORDANCE TO 11-4.15 AND ONE ACCESSIBLE TO THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS CAN BE
 ACCOMODATED BY THE USE OF A "HI-LO" FOUNTAIN OR BY SUCH
 OTHER MEANS AS WOULD ACHIEVE THE REQUIRED ACCESSIBILITY
 FOR EACH GROUP ON EACH FLOOR).
  
 5. PLEASE PROVIDE INFORMATION THST THE EXISTING
 RESROOM IS ADA COMPLIANT WITH AN ELEVATION DETAIL PER
 FBC-2004 CHAPTER 11 THE FOLLOWING SECTIONS:
  
 **WATER CLOSETS
 A} 11-4.16.2, CLEAR FLOOR SPACE.
  
 B} 11-4.16.3, HEIGHT.
  
 C} 11-4.16.4, GRAB BARS.
  
 D} 11-4.16.5, FLUSH CONTROLS.
  
 E} 11-4.16.6, DISPENSERS.
  
 **LAVATORIES AND MIRRORS
 A} 11-4.19.2, HEIGHT AND CLEARANCES.
  
 B} 11-4.19.3, CLEAR FLOOR SPACE.
  
 C} 11-4.19.4, EXPOSED PIPES AND SURFACES.
  
 D} 11-4.19.5, FAUCETS.
  
 E} 11-4.19.6, MIRRORS.
  
 6. SHEET P-2 EQUIPMENT DRAIN DETAIL: PLEASE INDICATE
 THE INDIRECT DRAIN LINE REQUIRED AIR GAP PER FBC-2004
 PLUMBING WITH 2006 REVISIONS SECTION 802.2.1 THE AIR
 GAP BETWEEN THE INDIRECT WASTE PIPE AND THE FLOOD LEVEL
 RIM OF THE WASTE RECEPTOR SHALL BE A MINIMUM OF TWICE
 THE EFFECTIVE OPENING OF THE INDIRECT WASTE PIPE AND
 CORRELATE THE FIXTURE CONNECTION SCHEDULE (REMARKS) TO
 REFLECT AIR GAP ON ITEMS 1, 2, 6, 7, 8, 9, 10, 12, 13,
 14, 15 AND 16 AS PER THE INDICATED DETAIL INSTEAD OF
 AIR BREAK.
  
 7. SHEET P-1 AND M-1 ARE INDICATING A GAS FIRED
 BOILER: PER FBC-2004 PLUMBING WITH 2006 REVISIONS
 SECTION 701.7,WASTEWATER WHEN DISCHARGED INTO THE
 BUILDING DRAINAGE SYSTEM SHALL BE AT A TEMPERATURE NOT
 HIGHER THAN 140 DEGREES F. WHEN HIGHER TEMPERATURES
 EXIST, APPROVED COOLING METHODS SHALL BE PROVIDED. ARE
 THE EQUIPMENT INDIRECT WASTES INTO THE DRAINAGE SYSTEM
 GOING TO BE GREATER THAN 140 DEGREES F? IF SO, PLEASE
 CLEARLY INDICATE THIS ON THE RESUBMITTAL IN RELATION TO
 NOTE 7 ON SHEET P-1 "FOR ALL FLOOR SINKS (FS) THE FIRST
 TEN FEET OF UNDERGROUND DRAIN PIPING SHALL BE CAST IRON
 BEFORE TRANSITIONING OVER TO PVC".
 NOTE: PER FBC-2004 PLUMBING WITH 2006 REVISIONS TABLE
 702.2 CPVC IS NOT APPROVED FOR UNDERGROUND BUILDING
 DRAINAGE. PLEASE DELETE "CPVC" ON THE RESUBMITTAL.
  
 8. SHEET P-1 COMPRESSED AIR GENERAL NOTES: NOTE NUMBER
 3, INDICATES SCHEDULE 40. PLEASE CLEARLY INDICATE THE
 PROPOSED MATERIAL TYPE OF SCHEDULE 40 ON THE
 RESUBMITTAL.
 NOTE: PER MANUFACTURER'S SPECIFICATIONS PVC PIPE IS
 NOT ACCEPTABLE FOR COMPRESSED AIR.
  
 9. SHEET P-2 FIXTURE CONNECTION SCHEDULE ITEM 17, LINT
 INTERCEPTOR: PLEASE ADD THE FOLLOWING "LINT INTERCEPTOR
 TO BE INSTALLED PER FBC-2004 PLUMBING WITH 2006
 REVISIONS SECTION 1003.6" ON THE RESUBMITTAL.
  
 10. SHEET P-2 GENERAL PLUMBING NOTES: PLEASE DELETE
 NOTE D.2 "PROVIDE WATER HAMMER ARRESTOR 18" HIGH, NEXT
 LARGER SIZE THAN PIPE SERVING FIXTURE" (NOTE: WHAT YOU
 ARE DISCRIBING IS AN AIR CHAMBER, AIR CHAMBERS ARE NO
 LONGER ALLOWED) AND ADD IN ITS PLACE THE FOLLOWING "
 PER FBC-2004 PLUMBING WITH 2006 REVISIONS SECTION 604.9
 WATER HAMMER ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED. WATER HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER'S SPECIFICATIONS. WATER HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010" ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK ON
 THE INDICATED PLAN SHEETS BY THIS PLAN EXAMINER FOR
 REFERENCE FOR THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2007-09-07 Cont ID  
Sent By choops Date 2007-09-07 Time 17:26 Rev Time 0.00
Received By choops Date 2007-09-07 Time 17:26 Sent To  
Notes
2007-09-07 17:27:06*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.