Plan Review Details - Permit 07080248
Plan Review Stops For Permit 07080248
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-04 Cont ID  
Sent By amorse Date 2007-09-04 Time 17:46 Rev Time 0.00
Received By amorse Date 2007-09-04 Time 17:46 Sent To PC
Notes
2007-09-04 18:05:21 
  
 DENIED
  
 1)WIND DESIGN DATA ON SITE SPECIFIC DRAWINGS SHALL
 CONTAIN WIND EXPOSURE CATEGORY PER
 1603.1.4 FBC
  
 2)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 3)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE
 PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR
 SETBACKS
  
 4)ELEVATIONS SHOW A WALL HEIGHT OF 9'-0" IS THIS A
 FLAT ROOF ?
  
 5)PLEASE CLARIFY THE FIRST ROOF BEAM ON THE RIGHT
 SIDE IS ATTACHED AT THE CORNER AND IS 25'-0" LONG AS
 MAX LENGTH FOR 2X8 BEAMS IS 29'-4"
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-09-04 Time   Rev Time 0.00
Received By mmiller Date 2007-08-08 Time 18:41 Sent To  
Notes
2007-08-08 18:41:36SENT TO ZONING BOX MMILLER

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-10 Cont ID  
Sent By choops Date 2007-08-10 Time 11:07 Rev Time 0.00
Received By choops Date 2007-08-10 Time 11:07 Sent To B
Notes
2007-08-10 11:08:47***FAILED***
  
  
 1) PLEASE PROVIDE TWO (2) COPIES OF A CURRENT SURVEY
 SHOWING THE SCOPE OF WORK WITH DIMENSIONS AND SETBACK
 DIMENSIONS TO THE PROPERTY LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720


Account Summary | Usage Policy | Privacy Policy