Plan Review Details - Permit 07080199
Plan Review Stops For Permit 07080199
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-09-25 Cont ID  
Sent By shill Date 2007-09-25 Time 11:28 Rev Time 0.00
Received By shill Date 2007-09-25 Time 11:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-14 Cont ID  
Sent By shill Date 2007-09-14 Time 14:55 Rev Time 0.00
Received By shill Date 2007-09-14 Time 14:55 Sent To  
Notes
2007-09-14 15:02:41****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)THE SITE SPECIFIC IS FOR A 10'8" X 16'9"
 ENCLOSURE, SURVEY SHOWS 12X19.
  
 NEW COMMENT:
  
 2.)PROVIDE INFORMATION REGARDS TO THE CONNECTION TO
 THE CONCRETE DECK.THE DRAWING PROVIDED STATES THAT
 DESIGN WILL BE BY OTHERS BUT I WAS UNABLE TO LOCATE A
 MINIMUM FOOTER REQUIREMENT.PROVIDE A DETAIL FOR THE
 PROPOSED FOOTER.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-09-04 Cont ID  
Sent By shill Date 2007-09-04 Time 18:18 Rev Time 0.00
Received By shill Date 2007-09-04 Time 18:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-09-25 Cont ID  
Sent By btrobaug Date 2007-09-25 Time 07:06 Rev Time 0.00
Received By btrobaug Date 2007-09-25 Time 07:01 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-14 Cont ID  
Sent By btrobaug Date 2007-09-14 Time 13:15 Rev Time 0.00
Received By btrobaug Date 2007-09-14 Time 13:15 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-15 Cont ID  
Sent By btrobaug Date 2007-08-15 Time 11:17 Rev Time 0.00
Received By btrobaug Date 2007-08-15 Time 11:14 Sent To B
Notes
2007-08-15 11:17:32 
  
 CLARIFY WHERE THE ENCLOSURE IS TO BE CONSTRUCTED.
 680.26(B)(5) METAL WIRING METHODS AND EQUIPMENT.
 METAL-SHEATHED CABLES AND RACEWAYS, METAL PIPING, AND
 ALL FIXED METAL PARTS EXCEPT THOSE SEPARATED FROM THE
 POOL BY A PERMANENT BARRIER SHALL BE BONDED THAT ARE
 WITHIN THE FOLLOWING DISTANCES OF THE POOL:
 EXAMPLES OF FIXED METAL PARTS BOUND BY THIS REQUIREMENT
 INCLUDE METAL FENCES, METAL AWNINGS, METAL DOOR FRAMES,
 AND METAL WINDOW FRAMES.
 (1) WITHIN 1.5 M (5 FT) HORIZONTALLY OF THE INSIDE
 WALLS OF THE POOL
 (2) WITHIN 3.7 M (12 FT) MEASURED VERTICALLY ABOVE THE
 MAXIMUM WATER LEVEL OF THE POOL, OR ANY OBSERVATION
 STANDS, TOWERS, OR PLATFORMS, OR ANY DIVING
 STRUCTURES.
  
 THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY
 THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-17 Cont ID  
Sent By adarroug Date 2007-09-17 Time 14:48 Rev Time 0.00
Received By adarroug Date 2007-09-17 Time 14:48 Sent To Z
Notes
2007-09-17 14:48:26TO "Z" BOX/RESUB--NEW ELECT. SHEETS SUBMITTED

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-12 Cont ID  
Sent By adarroug Date 2007-09-12 Time 11:22 Rev Time 0.00
Received By adarroug Date 2007-09-12 Time 11:22 Sent To Z
Notes
2007-09-12 11:23:10TO "Z" BOX/RESUB--NEEDS STAMP FOR "BLDG"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-12 Cont ID  
Sent By adarroug Date 2007-09-04 Time 11:22 Rev Time 0.00
Received By adarroug Date 2007-08-07 Time 17:32 Sent To  
Notes
2007-08-07 17:32:54SENT TO ZONING BOX

Review Stop Z ZONING
Rev No 3 Status P Date 2007-09-19 Cont ID  
Sent By choops Date 2007-09-19 Time 13:15 Rev Time 0.00
Received By choops Date 2007-09-19 Time 13:15 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-09-13 Cont ID  
Sent By choops Date 2007-09-13 Time 11:05 Rev Time 0.00
Received By choops Date 2007-09-13 Time 11:05 Sent To E
Notes
2007-09-13 11:08:21***FAILED***
  
  
 REPEAT COMMENT:
  
 1)DIMENSIONS OF PROPOSED SCREEN ENCLOSURE ARE NOT
 CONSISTANT BETWEEN SURVEY AND DETAIL
 PROVIDED...CLARIFY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-09 Cont ID  
Sent By choops Date 2007-08-09 Time 17:17 Rev Time 0.00
Received By choops Date 2007-08-09 Time 17:17 Sent To E
Notes
2007-08-09 17:19:36***FAILED***
  
  
 1)CLARIFY SCOPE OF WORK ON SURVEYS, WHERE EXACTLY IS
 ENCLOSURE GOING.
  
 2)PROVIDE SETBACK DIMENSIONS TO ALL PROPERTY LINES
 FROM THE ENCLOSURE
  
 3)DIMENSIONS DO NOT MATCH BETWEEN SURVEY AND DETAIL
 PROVIDED.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720