Plan Review Details - Permit 07080049
Plan Review Stops For Permit 07080049
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-07-11 Cont ID  
Sent By shill Date 2008-07-11 Time 13:30 Rev Time 0.00
Received By shill Date 2008-07-11 Time 13:30 Sent To  
Notes
2008-07-11 13:31:29REVISED A102, A105, A106

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-21 Cont ID  
Sent By shill Date 2007-11-21 Time 11:28 Rev Time 0.00
Received By shill Date 2007-11-21 Time 11:28 Sent To  
Notes
2007-11-21 11:30:37***PROVISOS***
  
 1.)YKK DOOR - PRESSURE TO BE DIVIDED BY 1.33, SEE
 FLORIDA STATE PRODUCT APPROVAL.
  
 2.)ROOF HATCH PRODUCT APPROVAL TO BE SUBMITTED PRIOR
 TO INSTALLATION.
  
 3.)RETAIL COUNTERS TO COMPLY WITH FBC11-4.7.2, SUBMIT
 SHOP DRAWINGS PRIOR TO INSTALLATION.
  
 4.)SUBMIT ROOF PRODUCT APPROVALS WITH ROOF PERMIT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-11-21 Cont ID  
Sent By shill Date 2007-11-21 Time 09:13 Rev Time 0.00
Received By shill Date 2007-11-21 Time 09:13 Sent To  
Notes
2007-11-21 09:49:17****CORRECTIONS****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 FROM PREVIOUS LIST:
  
 1.)PLEASE INCLUDE A RESPONSE LETTER.THIS HELPS TO
 EXPEDITE PLAN REVIEW.
  
 2.)NOC; REQUIRED BY FS713.13.
  
 3.)PLANS WILL BE REDLINED TO INCUDE 2007 AMENDMENTS
 IF AGREED BY ARCHITECT.
  
 4.)ADDRESSED.
  
 5.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72.
  
 5A.I HAVE PRINTED YKK DOOR PRODUCT APPROVAL FOR YOU.
 PLEASE SEE THE NOTE AT THE BOTTOM OF THE PRODUCT
 APPROVAL.THE DESIGN PRESSURES ARE TO BE REDUCED BY
 DIVIDING BY 1.33 OR BY BEING CERTIFIED BY AN ENGINEER.
 SEE SHEET 3.NOT ALL OF THE GLASS OPTIONS ARE
 COMPLIANT WITH THE DESIGN PRESSURE REQUIREMENT OF -55.3
 FOR THE 3'0' X 8'0' DOOR WHEN DIVIDED BY 1.33.PLEASE
 CIRCLE WHICH GLASS OPTION YOU ARE USING.
  
 5F.PRODUCT APPROVAL FOR THE ROOF HATCH CAN BE A
 PROVISO ITEM AS STATED IN THE PREVIOUS LIST.A CO HOLD
 HAS BEEN PLACED ON THIS PERMIT SUBJECT TO THIS
 REQUIREMENT.PLEASE NOTE THAT THE PLAN SPECIFIES A
 BILCO ROOF HATCH, BUT THE PRODUCT APPROVAL PACKAGE
 SUBMITTED REFERS TO NYSTROM BUILDNG PRODUCTS ROOF
 HATCH.
  
 6C.SHEET A103 HAS SEVERAL COUNTER AREAS, RETAIL PARTS
 BOUTIQUE, SERVICE TECH AREA AND CASHIERS STATION.
 PLEASE REVIEW REQUIREMENTS FOR SERVICE COUNTERS FOR
 SALES OR DISTRIBUTION OF GOODS TO THE PUBLIC
 FBC11-4.7.2 AND PROVIDE ELEVATIONS SHOWING COMPLIANCE.
  
 IT IS NOT CLEAR HOW THIS WAS ADDRESSED.NO ELEVATIONS
 OR NOTES SHOWING CODE COMPLIANCE WERE PROVIDED.
  
 7A)A ROOF PRODUCT APPROVAL WAS SUBMITTED, BUT THIS IS
 FOR A WOOD DECK.SP1 STATES THAT THIS IS TYPE IIB,
 NONCOMBUSTIBLE.PLEASE CORRELATE.
  
 7B.)THE ROOF PRODUCT APPROVAL REFERS TO GENERAL
 LIMITATION #9, NO ENHANCED FASTENING ALLOWED AND THE
 APPROVED ASSEMBLIES LISTED ARE LIMITED TO -45PSF.
 SPECIFY ROOF DESIGN PRESSURES AND SUBMIT PRODUCT
 APPROVAL FOR THE CORRECT ROOF DECK TYPE AND WHICH MEETS
 OR EXCEEDS THE DESIGN PRESSURES.AN APPROVED ASSEMBLY
 WILL BE REQUIRED TO BE SELECTED ALONG WITH ENHANCED
 FASTENING PATTERN WHEN APPLYING FOR THE ROOF PERMIT.
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-12 Cont ID  
Sent By jwitmer Date 2007-09-12 Time 15:50 Rev Time 7.70
Received By jwitmer Date 2007-09-10 Time 13:41 Sent To  
Notes
2007-09-12 15:57:53BUILDING PLAN REVIEW
 SEPT. 10, 2007
 PERMIT: 07080049
 ADD: 2345 OKEECHOBEE BLVD
 CONT: POPPER AND ASSOCIATES
 TEL: (561)719-7131
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3A) SHEET SP-1 CODE SUMMERY, THE PLANS FAIL TO INDICATE
 AS TO WHICH EDITION OF THE CODE THIS BUILDING IS BEING
 DESIGNED TO. 2004 FLORIDA BUILDING CODE W/ 2006
 AMENDMENTS.
  
 3B) THE PERMIT APPLICATION AND PLAN INDICATE THAT THE
 WORK TO BE COMPLETED UNDER THIS PERMIT IS A COMMERCIAL
 REMODEL. PLEASE SEE 2004 EXISTING BUILDING CODE-
 BUILDINGW/ 2006 AMENDMENTS. PLEASE INDICATE ON THE
 PLANS AS WELL AS THE LEVEL OF ALTERATIONS?
  
 4A) SHEET A-102 THERE IS 2 NEW COLUMNS ON COLUMN LINE
 A-2 & COLUMN LINE A-6 PLEASE PROVIDE A CUT SECTION
 THROUGH THIS AREA, PLAN ARE NOT CLEAR AS TO THE
 ANCHORING TO SLAB AND OR MAIN RESISTING SYSTEM FROM THE
 ROOF THROUGH TO THE FOUNDATION.
  
 4B) SHEET A-102 PLEASE PROVIDE A CUT SECTION THROUGH AT
 GRADE TO INDICATE HOW THE COMPONENTS WILL ENTER ACT AT
 GRADE OR IF SIDEWALK AT AIDE WALK.
 2603.9.2 CLEARANCE BETWEEN EARTH AND FOAM PLASTICS
 APPLIED TO THE EXTERIOR WALL SHALL BE NOT LESS THAN 6
 INCHES (152 MM).
  
 5A) SHEET A-102 INDICATES THAT THE EXISTING STOREFRONT
 WILL BE REUSED, BUT THE PRODUCT APPROVALS SUBMITTED
 HAVE ALUMIGLASS CURTAIN WALL SYSTEM AS PART OF THE
 PACKAGE.
 NOTE: THIS REPORT IF TO BE USED WILL NEED TO DIVIDE THE
 PRESSURES BY 1.33 FOR HAVE A FLORIDA LICENSED P.E.
 RESEARCH THE FASTENING SYSTEM. BEFORE THE 2004 FBC
 MANUFACTURES TOOK STEEL INCREASES OF 1.33% ON THE
 FASTENING SYSTEM.
  
 5B) SHEETS A-101 AND A-102 BOTH INDICATE THE USE OF
 EXTERIOR BI-FOLD DOORS, A 3?-0?
 WIDE EXTERIOR SWING DOOR AND A 6?-0? WIDE SWING DOOR.
 THE WERE NO PRODUCT APPROVALS SUBMITTED FOR THESE
 OPENINGS AT ALL. 1609.1.4.
  
 5C) THERE ARE NO DETAIL SHEETS HOW THE BI-FOLD DOORS
 AND SWING DOORS WERE TESTED AS AN ASSEMBLY, NOTE IS
 THERE A DOOR JAMB ON THE LATCH SIDE OF THE SWING DOOR,
 DOES THE BI-FOLD DOOR HAVE WHAT TYPE OF LOCKING
 ASSEMBLY THAT ALLOWS THE SWING DOOR TO LOCK INTO ITS
 RAILS? 106.1.2* ADDITIONAL INFORMATION REQUIRED.
  
 5D) SUBMITTED ALSO ARE STORM SHUTTER PRODUCT APPROVALS
 BUT THERE IS NO KEY PLAN INDICATING TO WHICH OPENINGS
 THEY ARE TO BE PLACED? SHEET A-107 NOTE INDICATES NEW
 STOREFRONTS WITH BI-FOLD DOORS, ARE THE STOREFRONT
 WINDOWS GETTING REPLACED?
  
 5E)EASTERN METAL ALSO WILL REQUIRE A FLORIDA COVER
 SHEET.PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 5F) SHEET A-102 ALSO INDICATES THE USE OF A NEW ROOF
 HATCH. RULE 9B-72 REQUIRES A PRODUCT APPROVAL FOR SUCH
 ROOF OPENINGS. CURRENTLY THERE ARE NONE AVAILABLE BUT
 THERE ARE MANUFACTURERS CURRENTLY UNDERGOING TESTING
 AND CERTIFICATION THROUGH MIAMI-DADE TESTING PROGRAM.
 THIS ISSUE WILL BE A PROVISO:THAT IF THE MANUFACTURER
 DOES NOT ACQUIRE A ACCEPTANCE REPORT THROUGH THE STATE
 OR MIAMI-DADE THEN THE
 MANUFACTURER WILL BE REQUIRED TO SUBMIT TO THE CITY AND
 ACQUIRE A LOCAL PRODUCT APPROVAL BEFORE A CERTIFICATE
 OF COMPLETION WILL BE ISSUED. RULE 9B-72, 106.3.3.*
  
 6A) SHEET A-103 STAIR# A111 HAS A PASSAGEWAY TO THE
 EXTERIOR OF THE BUILDING,THIS STAIRWAY HAS 2 DOORS
 WHERE THE 18 ? IS MISSING ON THE PULL SIDE AT THE
 LATCH.
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH IN THE REQUIRED
 CLEARANCES SHALL BE CLEAR & LEVEL.
  
 6B) SHEET A-103 SERVICE TECH ROOM# 119 PLEASE SEE DOORS
 IN SERIES: 11-4.13.7 TWO DOORS IN SERIES.THE MINIMUM
 SPACE BETWEEN TWO HINGED OR PIVOTED DOORS IN SERIES
 SHALL BE 48 INCHES (1219 MM) PLUS THE WIDTH OF ANY DOOR
 SWINGING INTO THE SPACE. DOORS IN SERIES SHALL SWING
 EITHER IN THE SAME DIRECTION OR AWAY FROM THE SPACE
 BETWEEN THE DOORS [SEE FIGURE 26 (A)].
  
 6C) SHEET A-103 HAS SEVERAL COUNTER AREAS, RETAIL PARTS
 BOUTIQUE, SERVICE TECH AREA AND CASHIERS STATION. ALL
 SHOW VARIOUS DETAILS ON EITHER SHEET A-12 AND A-14.
 THESE SHEETS ARE NOT INCLUDED IN THESE PLANS OR
 INDEX.PLEASE REVIEW REQUIREMENTS FOR SERVICE COUNTERS
 FOR SALES OR DISTRIBUTION OF GOODS TO THE PUBLIC.
 11-4.7.2. PROVIDE ELEVATIONS SHOWING COMPLIANCE.
  
 6D) SHEET A-103 THE WOMEN?S RESTROOM A117 HAS 2 DOORS
 IN SERIES, 1A117B AND DOOR 2A117B THE SECOND DOOR DOES
 NOT INDICATE WHAT THE USAGE WILL BE? PLEASE REVIEW
 11-4.13.7 TWO DOORS IN SERIES.
  
 7)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTINGREPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 A) ROOF HATCH
 B) EFIS SYSTEMS
 C) ROOF ASSEMBLIES- WORK ON THE ROOF
  
 8)PLEASE MAKE CORRECTION AS TO WORK THAT WILL BE
 COMPLETED ON THE 2ND FLOOR IS RELATED TO A/C. PERMIT
 APPLICATION.
  
  
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-07-24 Cont ID  
Sent By btrobaug Date 2008-07-24 Time 10:25 Rev Time 0.00
Received By btrobaug Date 2008-07-24 Time 09:14 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-06-03 Cont ID  
Sent By dpalmer Date 2008-06-03 Time 12:12 Rev Time 0.00
Received By dpalmer Date 2008-06-03 Time 12:12 Sent To PC
Notes
2008-06-03 12:12:15** DENIED REVIEW FOR REVISIONS **
  
  
 ** PLEASE REVISE AND COORDINATE REVISIONS MADE TO
 PLANS.
  
 1) NOTE: PLEASE SEE THERE ARE ITEMS NOW OFF AND MISSING
 FROM THE PLANS WHICH WERE LOCATED ON PREVIOUS PLANS
 WHICH ARE JUST NO LONGER ON PLANS.
 FOR EXAMPLE:
 PLEASE SEE DRIVE SIGNS WHICH USED TO BE CIRCUIT L-30.
 PLEASE SEE SOFFIT NEON WHICH USED TO BE ON PLANS ON
 EAST SIDE OF BUILDING ALSO.
 THESE ARE A COUPLE OF EXAMPLES WHICH COORDINATION IS
 NEEDED. THIS MAY NOT BE AN EXHAUSTED LIST.
 FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND
 ADDITIONAL INFORMATION.
 NEC 408.4
  
 2) NOTE: PLEASE SEE THE PLANS HAVE HAD SEVERAL REVISED
 CIRCUITS FOR LIGHTING ETC YET THE SCHEDULE ON E-300 HAS
 NOT BEEN REVISED.
 FBC 106.1.2, NEC 408.4
 13-415.1.ABC.1.1, 13-413.1.ABC.2.1, .2.2.
  
 3) NOTE: PLEASE KNOW THE LOCK-OFF DEVICE WHICH IS SHOWN
 FOR CIRCUIT L12 FOR EMERGENCY LIGHTS/EXIT LIGHTS SHALL
 BE AN INTEGRAL PART OF THE BREAKER. MAY NOT BE OF A
 SNAP ON/CLIP ON TYPE. THIS WILL BE FIELD VERIFIED. THIS
 IS BEING SHOWN AS AN EXCEPTION TO 700.12E WHICH
 REQUIRES ALL EMERGENCY LIGHTS AND EXIT LIGHTS TO BE
 CIRCUITED TO LOCAL BRANCH CIRCUIT.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-11-19 Cont ID  
Sent By dpalmer Date 2007-11-19 Time 13:55 Rev Time 0.00
Received By dpalmer Date 2007-11-19 Time 13:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-09 Cont ID  
Sent By dpalmer Date 2007-11-09 Time 12:54 Rev Time 0.00
Received By dpalmer Date 2007-11-09 Time 12:54 Sent To  
Notes
2007-11-09 12:54:51** DENIED **
  
  
 1) NOTE:PLEASE SEE THE LIGHTING POWER CALCULATIONS
 FOR DESIGN AND ALLOWANCES ARE DIFFERENT ON ELECTRICAL
 PLANS ON SHEET E-300 THAN ON THE METHOD *C* AS
 SUBMITTED ALONG WITH SUBMITTALS.
 PLEASE SEE 13-415.2 AND COORDINATE PLANS/CALCULATIONS.
 FOR EXAMPLE: MAXIMUM LIGHTING POWER ALLOWANCE AS LISTED
 ON SHEET METHOD *C* IS SHOWN AS 7,983, YET TABLE
 CALCULATIONS ON SHEET E-300 SHOWS DESIGN AT 11,397.
 THIS EXCEEDS THE MAXIMUM AS STATED ON FORM 400C-04.
  
 THE LPD ON THE TABLES DOE HOWEVER SHOW A DESIGN LESS
 THAN THE ALLOWANCE ON THIS SAME SHEET.
 PLEASE EXPLAIN AND COORDINATE THESE DIFFERENCES.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTIONS SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-25 Cont ID  
Sent By dpalmer Date 2007-08-25 Time 18:56 Rev Time 0.00
Received By dpalmer Date 2007-08-25 Time 18:16 Sent To  
Notes
2007-08-25 18:56:302007-08-25 18:56:30
  
 *** DENIED ***
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE THE FOLLOWING NOTES FOR FBC CHAPTER
 13.
 PLANS INDICATE SEPARATE SPACE CONTROL FOR MOST AREAS,
 HOWEVER PLEASE CLARIFY AREAS SUCH AS THE MANAGER'S
 OFFICES,A108 AND SOME OTHER SEPARATE SPACES.
 13-415.1.ABC.1.2
 PLEASE SUBMIT INFORMATION FOR MAXIMUM TIMES FOR THE
 OVER RIDE AND OCCUPANCY SENSOR TYPE DEVICES AS SHOWN ON
 PLANS. THESE COULD NOT BE LOCATED ON THE SYMBOL LEGEND
 AND INFORMATION THE TYPE OF THE DEVICES. PLEASE SEE THE
 BATHROOMS ARE INDICATING A OC DEVICE WHICH IS OK,
 HOWEVER PLEASE EXPAND ON THE TYPE OF DEVICE. WILL THIS
 BE A COMBINATION DEVICE WHICH PROVIDES COVERAGE FOR
 BLIND SPOTS , STALLS. (ULTRASONIC TYPE?)
 PLEASE SUBMIT THE TIMED SCHEDULING INFORMATION. THE
 PLANS INDICATE THE LIGHTING TO A TIME CLOCK HOWEVER NO
 INFORMATION OR DETAIL FOR THIS WAS SUBMITTED OR COULD
 BE LOCATED ON PLANS.
 PLEASE PROVIDE OVER RIDE DEVICES, LOCATIONS AND TIMES
 PER 13-415.1.ABC.1.1, .1.2.
 PLEASE SEE MECHANICAL REVIEW COMMENTS WITH RESPECT TO
 ENERGY CALCULATIONS. PLEASE BE SURE THE INPUT DATA
 COORDINATES WITH THE PLANS.
 PLEASE PROVIDE LIGHTING POWER PERFORMANCE CALCULATIONS
 PER 13-415.2.
 PLEASE SEE PLEASE KNOW AT THIS TIME NOT REVIEW FOR
 LIGHTING COMPLIANCE CAN BE DONE FOR INTERIOR AND
 EXTERIOR LIGHTING POWER ALLOWANCES. PLEASE SEE
 13-415.2, 13-415.2.ABC.1.2, 13-415.2.ABC.1.3,
 13-415.2.ABC.1.1
  
 3) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF THE
 EMERGENCY/EXIT LIGHTS. THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES. PLEASE SHOW AND ADJUST
 CIRCUITING.
  
 4) NOTE: PLEASE IDENTIFY THE CIRCUITS ON THE PANEL
 SCHEDULE AS NEW OR EXISTING. SOME OF THESE ARE ALREADY
 DONE FOR THE NEW A/C EQUIPMENT.
 PLEASE SEE THESE CAN BE SIMPLY DONE BY AN *E* OR *N* ON
 THE BRANCH CIRCUITS ON PANEL SCHEDULE OR AN *ASTERISK*
 WITH A NOTE AT THE BOTTOM OF PANEL SCHEDULE OR BY ANY
 OTHER MEANS DECIDED BY THE DESIGN PROFESSIONAL.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-12-04 Cont ID  
Sent By mawillia Date 2007-12-04 Time 10:18 Rev Time 0.00
Received By mawillia Date 2007-12-04 Time 09:36 Sent To  
Notes
2007-12-04 10:08:30*****APPROVED*****
  
  
 PLAN SHEETS A-101, A-103, A-112, E-100, E-101, 102, AND
 E-103,WERE STAMPED, INITIALED, AND DATED.PLAN SHEET
 FS-101 WAS PREVIOUSLY FIRE-STAMPED(09/28/07) BY M.R.
 WENNERGREN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-09-28 Cont ID  
Sent By mwennerg Date 2007-09-28 Time 16:09 Rev Time 0.00
Received By mwennerg Date 2007-09-28 Time 16:09 Sent To  
Notes
2007-09-28 16:22:45***APPROVED***
  
 PLANS APPEAR TO BE CODE COMPLIANT HOWEVER PLEASE SEE
 THE FOLLOWING COMMENTS:
  
 1) IN ADDITION TO FIRE SPRINKLER REMODEL, SEPARATE SHOP
 DRAWINGS AND PERMIT IS REQUIRED FOR FIRE ALARM
 REMODEL.
  
 2) NEW DUCT SMOKE DETECTOR INSTALLATIONS SHALL INITIATE
 A GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-06-30 Cont ID  
Sent By adarroug Date 2008-06-30 Time 14:19 Rev Time 0.00
Received By adarroug Date 2008-06-30 Time 14:19 Sent To B
Notes
2008-06-30 14:20:03TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-06-26 Cont ID  
Sent By shill Date 2008-06-26 Time 16:18 Rev Time 0.00
Received By shill Date 2008-06-26 Time 16:18 Sent To E
Notes
2008-06-26 16:18:32TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-30 Cont ID  
Sent By adarroug Date 2008-05-30 Time 08:21 Rev Time 0.00
Received By adarroug Date 2008-05-30 Time 08:21 Sent To E
Notes
2008-05-30 08:22:14TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-08 Cont ID  
Sent By adarroug Date 2008-05-08 Time 16:33 Rev Time 0.00
Received By adarroug Date 2008-05-08 Time 16:33 Sent To M
Notes
2008-05-08 16:33:36TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-11 Cont ID  
Sent By adarroug Date 2008-04-11 Time 10:36 Rev Time 0.00
Received By adarroug Date 2008-04-11 Time 10:36 Sent To M
Notes
2008-04-11 10:38:54TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-10-24 Cont ID  
Sent By adarroug Date 2007-10-24 Time 09:22 Rev Time 0.00
Received By adarroug Date 2007-10-24 Time 09:22 Sent To  
Notes
2007-11-07 15:41:03TO "COMM" BD#62
2007-10-24 09:22:32WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-28 Cont ID  
Sent By lmartine Date 2007-09-28 Time 16:30 Rev Time 0.00
Received By lmartine Date 2007-08-03 Time 14:45 Sent To  
Notes
2007-09-22 10:32:00MOVED TO SPACE #62, 9/22 DVP.
2007-08-23 13:55:14TO "COMM" BD#38
2007-08-03 14:46:05WAITING FOR "COMM" BD

Review Stop L LANDSCAPING
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rkussner Date 2008-02-27 Time 15:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-05-20 Cont ID  
Sent By tgordon Date 2008-05-20 Time 14:41 Rev Time 1.00
Received By tgordon Date 2008-05-20 Time 14:41 Sent To  
Notes
2008-05-20 14:42:19REVISION TO MECH. PLANS M-100, M-200, AND M-400.
 RECIVED SUBMITTAL FOR DUCTSOX.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2008-04-29 Cont ID  
Sent By rregueir Date 2008-04-29 Time 16:55 Rev Time 0.00
Received By rregueir Date 2008-04-29 Time 13:58 Sent To PC
Notes
2008-04-29 16:55:27REVIEW #: REVISION 2
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE DESIGN OF THE NEW DUCTWORK IN THE SHOWROOM IS
 UNCLEAR. IT LOOKS AS IF IT MAY BE SOME TYPE OF
 DUCT-SOCK SYSTEM, BUT IT IS NOT IDENTIFIED ON THE
 PLANS. PLEASE CLARIFY. FBCM 603.1, FBCB 106.1.1
  
 2. IF A DUCT SOCK TYPE SYSTEM IS USED, PLEASE PROVIDE
 SUBMITTAL DATA SHOWING WHICH TYPE OF SYSTEM IS TO BE
 USED AS WELL AS LISTING AND TESTING DATA. NONMETALLIC
 DUCTS SHALL BE CONSTRUCTED WITH CLASS 0 OR CLASS 1 DUCT
 MATERIAL IN ACCORDANCE WITH UL 181 PER FBCM 603.4.
  
 3. PLEASE SEE PROVISO FROM PREVIOUS PLAN REVIEW. ALL
 PROVISO ITEMS ARE TO BE ADDRESSED IN REVISION PRIOR TO
 INSPECTION. THIS WAS A CONDITION OF PERMIT AND HAS NOT
 BEEN ADDRESSED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-11-24 Cont ID  
Sent By rregueir Date 2007-11-24 Time 15:50 Rev Time 0.00
Received By rregueir Date 2007-11-24 Time 15:43 Sent To  
Notes
2007-11-24 15:49:09*****************PROVISO******************
 1. FLOAT SWITCH FOR RTU'S TO BE INSTALLED INTERNALLY ON
 PRIMARY DRAIN PAN, NOT INLINE ON PRIMARY CONDENSATE
 LINE, IN ACCORDANCE WITH FBC,M 307.2.3(2).
  
 2. PROVIDE DETAIL FOR CONDENSING UNIT ATTACHMENT AS
 WELL AS ADDITIONAL SUPPORTS TO BE INSTALLED AS CALLED
 FOR BY NOTE ON M-200. SHOW COMPLIANCE WITH FBC,M 301.13
 AND FBC CH.16.
 NOTE:REVIES PLANS ACCORDINGLY TO SHOW COMPLIANCE WITH
 THESE PROVISOS PRIOR TO INSPECTION.
  
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-08-22 Cont ID  
Sent By rregueir Date 2007-08-22 Time 16:02 Rev Time 0.00
Received By rregueir Date 2007-08-22 Time 10:43 Sent To  
Notes
2007-08-22 16:02:14REVIEW #: 1
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE OR
 A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF FBC, EXISTING BUILDING.
 PLEASE INCLUDE THE LEVEL OF ALTERATION IN THE CODE
 SUMMARY SECTION OF PG SP-1.
  
 2.RENOVATED COMMERCIAL BUILDINGS SHALL, WHEN
 APPLICABLE (SEE SECTION 202 OF FBC CH.13), COMPLY WITH
 THE PRESCRIPTIVE REQUIREMENTS CONTAINED IN FORM 400C OR
 WITH METHOD B OF SUBCHAPTER 13-4 FOR INSULATION, HVAC
 SYSTEMS, LIGHTING, WATER HEATING SYSTEMS AND EXTERIOR
 ENVELOPE COMPONENTS BEING RETROFITTED OR REPLACED IN
 ACCORDANCE WITH FBC 13-101.1.3. PROVIDE ENERGY
 CALCULATIONS ON FORM 400B OR 400C SIGNED AND SEALED PER
 FBC 13-103.1.1.1.
  
 3. DUCT SMOKE DETECTORS SHALL BE CONNECTED TO THE
 BUILDING FIRE ALARM SYSTEM PER FBC,M 606.4.1.
  
 4. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL IN
 ACCORDANCE WITH FBC,M 307.2.1 AND FBC 1503.6.
  
 5. SHOW MEANS OF AUXILIARY DRAIN PROTECTION FOR RTU'S
 PER FBC,M 307.2.3. A WATER LEVEL DETECTION DEVICE
 (FLOAT SWITCH) IN THE PRIMARY DRAIN PAN OF THE RTU'S
 WILL SATISFY THIS REQUIREMENT.
  
 6. PG M-400 VERTICAL AC DETAIL: THIS DETAIL SHOWS A
 FLOAT SWITCH ON THE SECONDARY DRAIN OUTLET. THE SUPPLY
 AIR UNIT SCHEDULE CALLS FOR AN AUXILIARY DRAIN PAN W/
 FLOAT SWITCH. PLEASE CLARIFY WHICH METHOD IS TO BE USED
 OR PROVIDE BOTH. FBC,M 307.2.3
  
 7. PROVIDE A COMPREHENSIVE AIR BALANCE SCHEDULE WHICH
 INCLUDES EXHAUST AIR TOTALS TO SHOW THE BUILDING TO BE
 PRESSURISED WITH RESPECT TO THE OUTDOORS PER FBC
 13-409.1.ABC.2.
  
 8. SHOW BY WHAT MEANS THE OUTDOOR AIR FOR AC-1 AND AC-2
 IS PROVIDED. OUTDOOR AIR INTAKES ARE TO BE LOCATED IN
 COMPLIANCE WITH FBC,M 401.5 AND 401.6.
  
 9. PG M-100: DUCTS FOR AC-1 AND AC-2 ARE SHOWN
 PENETRATING THE 2ND FLOOR SLAB. SHOW HOW THESE OPENINGS
 ARE TO BE PROTECTED IN ACCORDANCE WITH FBC,M 607.5.
  
 10. PG M-400 RTU DETAIL: THERE IS NO SUCH THING AS
 TABLE 1606.1.4 IN THE FLORIDA BUILDING CODE. PROVIDE
 COMPLETE DETAIL AND WIND LOAD CALCULATIONS SHOWING HOW
 ALL OUTDOOR EQUIPMENT (RTU'S AND CU'S) IS TO BE SECURED
 TO MEET WIND LOAD REQUIREMENTS PER FBC,M 301.13 AND FBC
 CH.16.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-12-03 Cont ID  
Sent By mperson Date 2007-12-03 Time 08:02 Rev Time 0.00
Received By mperson Date 2007-12-03 Time 07:59 Sent To  
Notes
2007-12-03 09:29:41****************PROVISO****************
 PER TABLE *403.1 (2) (B) MINIMUM NUMBER OF REQUIRED
 PLUMIBNG FIXTURES:
  
 **WATER CLOSETS: 1 PER 25 FOR THE FIRST 50 AND 1 PER
 50 FOR THE REMAINER EXCEEDING 50.
  
 **LAVATORIES: 1 PER 40 FOR THE FIRST 50 AND 1 PER 80
 FOR THE REMAINDER EXCEEDING 50.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-09-17 Cont ID  
Sent By kstevens Date 2007-09-17 Time 08:42 Rev Time 0.00
Received By kstevens Date 2007-09-15 Time 19:01 Sent To  
Notes
2007-09-17 08:58:28DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 EXISTING BUILDING CODE
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. INDICATED THE LEVEL OF ALTERATION PER SECTIONS 303,
 304 OR 305.
  
 2. SHT SP-1 OCCUPANCY LOAD. MINIMUM FACILITIES AS SHOWN
 ARE NOT CORRECT. THREE W/C'S AND 3 LAVS REQUIRED.
 PLEASE CORRECT MINIMUM FACILITIES SHOWN.
  
 3. MORE INFORMATION REQUIRED. PLEASE PROVIDE AN
 EXISTING FLOOR PLAN PRIOR TO ALTERATIONS TO DETERMINE
 THE EXTENT OF THE CHANGES TO THE FLOOR PLAN. SECTION
 106.1.2.
  
 4. PER SECTION 606.1 EXIST. BLDG. CODE, A BUILDING,
 FACILITY OR ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE. THE STALLS IN
 ROOMS A117 & A118 SHALL MEET THE REQUIREMENTS OF
 11-4.17.3 EXCEPTION NEW CONTRUCTION (1) & (2). A LAV IS
 REQUIRED IN THE STALL, AND THE W/C SHALL BE LOCATED IN
 THE CORNER DIAGONAL TO THE DOOR. PLEASE SHOW
 COMPLIANCE.
  
 5. SUBMIT A DETAIL & ELEVATION FOR THE TECH LUNCH ROOM
 SINK. SHOW COMPLIANCE WITH SECTION 11-4.24 WITH ALL
 SUBSECTIONS FOR THE SINK. FORWARD APPROACH IS REQUIRED
 AND THE CABINET DOORS ARE NOT ALLOWED IN THE CLEAR
 FLOOR SPACE.
  
 6. SHT P-100 ALL DEMO'D PIPING BEING CAPPED. IN THE
 REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED. SECTION 704.5. INDICATED HOW THE
 CAPPING OF THE PIPING WILL COMPLY.
  
 7. SHT P-100 SANITARY RISER DIAGRAM. ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT TO THE
 WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE WET VENT.
 SECTION 909.1. THE SINK IN THE TECH LUNCH ROOM SHALL
 CONNECT DOWNSTREAM OF THE TOILET ROOM FIXTURES.
  
 8. A WATER RISER DIAGRAM FOR ALL NEW WORK IS REQUIRED
 PER SECTION 106.3.5.1.3(3)(10)(13). PLEASE SUBMIT A
 WATER RISER DIAGRAM SHOWING ALL PIPE SIZES, VALVES AND
 WATER HAMMER ARRESTORS, (IF REQUIRED BY SECTION
 604.9).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status N Date 2007-10-31 Cont ID  
Sent By adavila Date 2007-10-31 Time 09:57 Rev Time  
Received By adavila Date 2007-10-30 Time 17:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2007-08-29 Cont ID  
Sent By adavila Date 2007-08-29 Time 09:01 Rev Time 0.00
Received By adavila Date 2007-08-29 Time 09:01 Sent To  
Notes
***NONE***