Plan Review Details - Permit 07071047
Plan Review Stops For Permit 07071047
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-17 Cont ID  
Sent By shill Date 2007-10-17 Time 14:30 Rev Time 0.00
Received By shill Date 2007-10-17 Time 14:30 Sent To  
Notes
2007-10-17 14:30:31****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST, NOT ADDRESSED:
  
 1.)ENGINEERING REQUIRED FOR THE PRECAST SLAB AND
 ANCHORING TO SHOW HOW THE SLAB WILL RESIST LOADS OF
 FBC16 AND FBC R CHAPTER 3.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-11 Cont ID  
Sent By shill Date 2007-09-11 Time 09:16 Rev Time 0.00
Received By shill Date 2007-09-11 Time 09:16 Sent To  
Notes
2007-09-11 09:17:50****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)ENGINEERING REQUIRED FOR THE PRECAST SLAB AND
 ANCHORING TO SHOW HOW THE SLAB WILL RESIST LOADS OF
 FBC16 AND FBC R CHAPTER 3.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-28 Cont ID  
Sent By btrobaug Date 2007-09-28 Time 12:09 Rev Time 0.00
Received By btrobaug Date 2007-09-28 Time 11:20 Sent To P
Notes
2007-09-28 12:09:34 
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-08 Cont ID  
Sent By btrobaug Date 2007-08-08 Time 11:01 Rev Time 0.00
Received By btrobaug Date 2007-08-08 Time 09:37 Sent To M
Notes
2007-08-08 10:54:45 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE A LOAD CALCULATION FOR THE
 LOAD INTENDED TO BE SERVED. 215.5. 702.5, 2005NEC
  
 2} PROVIDE A PANEL SCHEDULE FOR THE
 PANEL AND CIRCUITS SUPPLIED FROM THE GENERATOR.
 106.3.5.4 FBC AS
 AMENDED, 408.4, 2005 NEC.
  
 3} THE 5' SETBACK REQUIRED FOR A COMBUSTIBLE SURFACE IS
 NOT BEING MAINTAINED AT THE PROPERTY LINE, IF A FENCE
 OF COMBUSTIBLE MATERIAL IS INSTALLED. ALSO THE BUILDING
 MATERIAL FOR THE RESIDENCE NEEDS TO BE STATED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
2007-08-08 10:37:32 
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-10-05 Cont ID  
Sent By mperson Date 2007-10-05 Time 11:57 Rev Time 0.00
Received By mperson Date 2007-10-05 Time 11:57 Sent To M
Notes
2007-10-05 13:11:03DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **OK**
  
 2.. **NO** COMMET NOT ADDRESSED
 BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: THIS INCLUDES THE EXISTING NAT/GAS SYSTEM. PLEASE
 REFERENCE THE ATTACHED PERMIT INFORMATION INDICATING
 NAT/GAS TO A WATER HEATER, DRYER AND FUTURE BBQ AT SAID
 ADDRESS. IF THE GAS METER INDICATED ON THE DRAWING IS
 FOR THE GENERATOR ONLY AND THERE IS A SEPERATE METER
 FOR THE OTHER APPLIANCES PLEASE CLEARLY INDICATE THIS
 ON THE RESUBMITTAL.
  
 3. **NO** COMMENT NOT ADDRESSED
 SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: REFERENCE COMMENT #2.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-08-13 Cont ID  
Sent By mperson Date 2007-08-13 Time 13:53 Rev Time 0.33
Received By mperson Date 2007-08-13 Time 13:53 Sent To B
Notes
2007-08-13 14:06:11DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. SEE ZONING REVIEW NOTE #1 AND ELECTRICAL REVIEW
 NOTE #3 IN REFERENCE TO THE PLACEMENT OF THE GENERATOR
 AND CORRELATE THE GAS ISOMETRIC IF NEEDED.
  
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: THIS INCLUDES THE EXISTING NAT/GAS SYSTEM. PLEASE
 REFERENCE THE ATTACHED PERMIT INFORMATION ATTACHED TO
 THE GAS REVIEW INDICATING NAT/GAS AT SAID ADDRESS.
  
 3. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THS INCLUDES THE EXISTING NAT/GAS SYSTEM. PLEASE
 REFERENCE THE ATTACHED PERMIT INFORMATION ATTACHED TO
 THE GAS REVIEW INDICATING NAT/GAS AT SAID ADDRESS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
  
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-21 Cont ID  
Sent By adarroug Date 2007-09-21 Time 14:24 Rev Time 0.00
Received By adarroug Date 2007-09-21 Time 14:24 Sent To Z
Notes
2007-09-21 14:24:45TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-11 Cont ID  
Sent By shill Date 2007-09-11 Time 09:18 Rev Time 0.00
Received By shill Date 2007-08-01 Time 10:20 Sent To  
Notes
2007-08-01 10:20:37TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-10-12 Cont ID  
Sent By tgordon Date 2007-10-12 Time 09:11 Rev Time 0.20
Received By tgordon Date 2007-10-12 Time 09:11 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-08-08 Cont ID  
Sent By tgordon Date 2007-08-08 Time 11:28 Rev Time 0.20
Received By tgordon Date 2007-08-08 Time 11:28 Sent To G
Notes
2007-08-08 11:30:25*** DENIED ***
 1) SEE ZONING AND ELECTRICAL REVIEW NOTES, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].

Review Stop Z ZONING
Rev No 2 Status P Date 2007-09-26 Cont ID  
Sent By choops Date 2007-09-26 Time 11:56 Rev Time 0.00
Received By choops Date 2007-09-26 Time 11:56 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-02 Cont ID  
Sent By choops Date 2007-08-02 Time 11:28 Rev Time 0.00
Received By choops Date 2007-08-02 Time 11:28 Sent To E
Notes
2007-08-02 11:32:57***FAILED***
  
  
 1)PROPOSED GENERATOR ENCROACHES TOO FAR INTO
 REQUIRED SETBACK. (NOTE: REQUIRED SIDE SETBACK OF 7.5
 FEET)
  
 PURSUANT TO SECTION 94-305(B)(4) OF THE CITY OF WEST
 PALM BEACH ZONING AND LAND DEVELOPMENT REGULATIONS:
 MECHANICAL EQUIPMENT.MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN FOUR FEET INTO A SETBACK.
  
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720