Plan Review Details - Permit 07071044
Plan Review Stops For Permit 07071044
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-22 Cont ID  
Sent By shill Date 2007-08-22 Time 08:47 Rev Time 0.00
Received By shill Date 2007-08-22 Time 08:47 Sent To  
Notes
2007-08-22 08:48:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PROVIDE ENGINEERING TO SHOW HOW THE PREFAB SLAB
 AND ANCHORING WILL COMPLY WITH FBC1609.1.3, FBC R301.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-07 Cont ID  
Sent By btrobaug Date 2007-08-07 Time 16:30 Rev Time 0.00
Received By btrobaug Date 2007-08-07 Time 16:00 Sent To M
Notes
2007-08-07 16:30:15 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 THIS REVIEW IS FOR COMPLIANCE WITH THE 2005 NEC AND
 THE 2004 FBC, 2006 REVISION.
  
 1} THE LOAD CALCULATION GIVEN FOR THE PANEL SERVED BY
 THE GENERATOR( 34.1 KW), EXCEEDS THE OUTPUT LOAD OF THE
 25K GENERATOR THAT WAS SUBMITTED IN VIOLATION OF
 702.5.
  
 2} THE 5' SETBACK REQUIRED FOR A COMBUSTABLE SURFACE IS
 NOT BEING MAINTAINED AT THE PROPERTY LINE, IF A WOODEN
 FENCE IS OR COULD BE INSTALLED. ALSO THE BUILDING
 MATERIAL FOR THE RESIDENCE NEEDS TO BE STATED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-08-13 Cont ID  
Sent By mperson Date 2007-08-13 Time 13:10 Rev Time 0.33
Received By mperson Date 2007-08-13 Time 13:10 Sent To B
Notes
2007-08-13 13:17:27DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. PLEASE REFERENCE ZONING REVIEW NOTES AND ELECTRICAL
 REVIEW NOTE #2 IN REFERENCE TO PLACEMENT OF THE
 GENERATOR AND PLEASE CORRELATE THE GAS DRAWING ON THE
 RESUBMITTAL.
  
 2. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: THIS INCLUDES THE EXISTING NAT/GAS SYSTEM. PLEASE
 REFERENCE THE PERMIT INFORMATION ATTACHED TO THESE GAS
 REVIEW NOTES INDICATING SAID ADDRESS HAS NAT/GAS.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THIS INCLUDES THE EXISTING NAT/GAS SYSTEM. PLEASE
 REFERENCE THE PERMIT INFORMATION ATTACHED TO THESE GAS
 REVIEW NOTES INDICATING SAID ADDRESS HAS NAT/GAS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-22 Cont ID  
Sent By shill Date 2007-08-22 Time 08:48 Rev Time 0.00
Received By shill Date 2007-08-01 Time 10:21 Sent To  
Notes
2007-08-01 10:21:59TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-08-08 Cont ID  
Sent By tgordon Date 2007-08-08 Time 10:47 Rev Time 0.15
Received By tgordon Date 2007-08-08 Time 10:47 Sent To G
Notes
2007-08-08 10:49:13*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL: [email protected].

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-02 Cont ID  
Sent By choops Date 2007-08-02 Time 12:06 Rev Time 0.00
Received By choops Date 2007-08-02 Time 12:06 Sent To E
Notes
2007-08-02 12:09:27***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS ON SURVEYS FROM
 PROPOSED GENERATOR TO PROPERTY LINES.MUST BE A
 MINIMUM OF 3.5' FROM SIDE PROPERTY LINES.AS PER THE
 CITY OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS, SECTION 94-305(B)(4):MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN FOUR FEET INTO A
 SETBACK.(NOTE:REQUIRED SIDE SETBACK = 7.5')
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720
  