Plan Review Details - Permit 07071033
Plan Review Stops For Permit 07071033
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-12-31 Cont ID  
Sent By shill Date 2008-12-31 Time 08:31 Rev Time 0.00
Received By shill Date 2008-12-31 Time 08:31 Sent To  
Notes
2008-12-31 08:31:44REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-09-15 Cont ID  
Sent By shill Date 2008-09-15 Time 10:43 Rev Time 0.00
Received By shill Date 2008-09-15 Time 10:43 Sent To  
Notes
2008-09-15 10:47:01****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. DOCUMENTS PREPARED BY A LANDSCAPE ARCHITECT AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS FS481.
  
 2. IT IS NOT CLEAR WHAT HAS BEEN REVISED. SHEET LP1 WAS
 SUBMITTED AS A REVISION BUT DOES NOT SHOW ANY CHANGES
 AND SHWS SAME REVISION DATE AS THE RECORD SET. PLEASE
 CLEARLY INDICATE ALL CHANGES WITH CLOUDS AND REVISION
 NUMBERS/DATES.
  
 3. THE PREVIOUS REVISION, A1 PREPARED BY JASON HANCHUK,
 PE WAS ISSUED WITH THE FOLLOWING PROVISOS:
  
 PROVIDE DESIGNER OF RECORD REVIEW
  
 PROVIDE STRUCTURAL LETTER FOR 4'6 HIGH COLUMN RATHER
 THAN 4' (OR REVISE PLAN)
  
 PLEASE NOTE THAT THE PROVISO REFERRED TO THE PLAN
 PREPARED BY JASON HANCHUK, PE. THE LAND DESIGN SOUTH
 PLAN SHOWS A 4'6" COLUMN, BUT THE ENGINEERING IS FOR A
 4' COLUMN. EITHER REVISE THE LAND DESIGN SOUTH PLAN TO
 CORRELATE WITH THE ENGINEERING (SHOW A 4' COLUMN), OR
 PROVIDE A LETTER FROM JASON HANCHUK, PE STATING THAT
 THE COLUMN DESIGN ON A1 IS ACCEPTABLE FOR A 4'6"
 COLUMN, OR PROVIDE A LETTER FROM J. HANCHUK, PE
 ADDRESSING THIS ISSUE.
  
 4. PLEASE SEE THE FOOTING PHOTOGRAPHS. THE SOIL DOES
 NOT APPEAR COMPACTED. PLEASE ADDRESS.
  
 5. THE LETTER FROM THE SURVEYOR STATES THAT THE BERM IS
 LOCATED A FEW INCHES FROM THE PROPERTY LINE. SEE
 FBC*109.3.10, IMPACT OF CONSTRUCTION. HOW HAS DRAINAGE
 BEEN ADDRESSED? IT APPEARS THAT THE BERM WILL DRAIN
 ONTO THE ADJACENT PARCEL IF NO PROVISIONS FOR DRAINAGE
 HAVE BEEN MADE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-07-17 Cont ID  
Sent By shill Date 2008-07-17 Time 12:18 Rev Time 0.00
Received By shill Date 2008-07-17 Time 12:18 Sent To  
Notes
2008-07-17 12:18:59PROVISO -
  
 PROVIDE DESIGNER OF RECORD REVIEW
 PROVIDE STRUCTURAL LETTER FOR 4'6 HIGH COLUMN RATHER
 THAN 4' (OR REVISE PLAN)

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-07-01 Cont ID  
Sent By shill Date 2008-07-01 Time 14:19 Rev Time 0.00
Received By shill Date 2008-07-01 Time 14:19 Sent To Z
Notes
2008-07-01 14:30:06****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.ALL SUBMITTALS, DELEGATED ENGINEERING ARE TO BE
 REVIEWED BY THE DESIGNER OF RECORD FOR THE PROJECT.
 THIS MAY BE DONE WITH A SHOP DRAWING REVIEW STAMP OR A
 LETTER.
  
 2.THE COLUMN AND FENCE DETAIL ON LP1 SHOWS A COLUMN
 WHICH IS 4.5' HIGH TO ACCOMODATE A 4' HIGH FENCE.THE
 NEW DETAIL SUBMITTED SHOWS A 4' HIGH COLUMN.PLEASE
 CORRELATE THE COLUMN DETAIL WITH THE APPROVED PLAN.
 THE APPROVED PLAN DOES NOT SHOW COLUMN LOCATIONS, FENCE
 LOCATION IS NOT CLEAR, AND IT IS ALSO NOT CLEAR HOW A
 4' HIGH COLUMN WITH A CAP CAN BE CONSTRUCTED TO SUPPORT
 THE 4' HIGH FENCE AND GATE. ARE THE COLUMNS SHOWN AS A
 SQUARE WITH AN X?PLEASE PROVIDE A LEGEND.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-02-07 Cont ID  
Sent By shill Date 2008-02-07 Time 15:25 Rev Time 0.00
Received By shill Date 2008-02-07 Time 15:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-04 Cont ID  
Sent By shill Date 2007-09-04 Time 17:39 Rev Time 0.00
Received By shill Date 2007-09-04 Time 17:39 Sent To  
Notes
2007-09-04 17:39:39****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PLAN CHECK ONLY.PERMIT APPLICATION REQUIRED.
  
 2.) SHOW SLOPE OF PAVERS, FBC11-4.1.2, FBC11-4.3.6,
 FBC11-4.3.7, FBC11-4.3.8.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-02-28 Cont ID  
Sent By btrobaug Date 2008-02-28 Time 15:22 Rev Time 0.00
Received By btrobaug Date 2008-02-28 Time 15:20 Sent To PC
Notes
2008-02-28 15:22:26 
  
 SPOKE WITH NELSON DOZIER ABOUT THE SERVICE, THE PLANS
 SUBMITTED ARE SUFFICIENT./WRT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-01-24 Cont ID  
Sent By btrobaug Date 2008-01-24 Time 11:59 Rev Time 0.00
Received By btrobaug Date 2008-01-24 Time 10:54 Sent To  
Notes
2008-01-24 11:59:48 
  
  
 APPLICATION #07071033
 ELECTRICAL PLAN REVIEW
 2207 TAMARIND AVE
 1/24/08
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE A SITE PLAN INDICATING THE LOCATION OF THE
 SERVICE FOR THE IRRIGATION SYSTEM.
  
 2} TWO SETS OF PLANS ARE REQUIRED FOR REVIEW, ONLY ONE
 RISER DIAGRAM WAS SUBMITTED. 106.1 FBC AS AMENDED.
  
 3} THE ENGINEER OF RECORD MUST SEAL THE DOCUMENTS WITH
 A SEAL ACCEPTABLE TO THE BOARD PER 61G15-23.001, SIGN
 AND DATE SAME PER 471 FS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-12 Cont ID  
Sent By btrobaug Date 2007-08-20 Time 11:25 Rev Time 0.00
Received By btrobaug Date 2007-08-20 Time 11:17 Sent To P
Notes
2007-08-20 11:25:16 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS
 AMENDED.TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW PER 106.1 FBC AS AMENDED. SUBMIT ELECTRICAL
 PLANS FOR THIS PROJECT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-12-23 Cont ID  
Sent By adarroug Date 2008-12-23 Time 09:46 Rev Time 0.00
Received By adarroug Date 2008-12-23 Time 09:46 Sent To Z
Notes
2008-12-23 09:46:54TO "Z" BOX/REV--FOR LANDSCAPE REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-09-10 Cont ID  
Sent By adarroug Date 2008-09-10 Time 14:48 Rev Time 0.00
Received By adarroug Date 2008-09-10 Time 14:48 Sent To B
Notes
2008-09-10 14:49:12TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-09-02 Cont ID  
Sent By adarroug Date 2008-09-02 Time 16:44 Rev Time 0.00
Received By adarroug Date 2008-09-02 Time 16:44 Sent To Z
Notes
2008-09-02 16:46:13TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-23 Cont ID  
Sent By adarroug Date 2008-06-23 Time 14:55 Rev Time 0.00
Received By adarroug Date 2008-06-23 Time 14:55 Sent To B
Notes
2008-06-23 14:55:58TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-10 Cont ID  
Sent By mmiller Date 2008-01-10 Time 15:34 Rev Time 0.00
Received By mmiller Date 2008-01-10 Time 15:33 Sent To  
Notes
2008-01-10 15:34:15SENT TO COMM BOARD # 10 MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-16 Cont ID  
Sent By adarroug Date 2007-08-16 Time 09:53 Rev Time 0.00
Received By adarroug Date 2007-08-16 Time 09:53 Sent To  
Notes
2007-08-16 09:53:14TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-08 Cont ID  
Sent By adarroug Date 2007-09-04 Time 11:27 Rev Time 0.00
Received By adarroug Date 2007-08-02 Time 14:24 Sent To  
Notes
2007-08-02 14:24:13TO "Z" BOX

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-12-23 Cont ID  
Sent By rkussner Date 2008-12-23 Time 13:28 Rev Time 0.00
Received By rkussner Date 2008-12-23 Time 13:28 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-01-23 Cont ID  
Sent By mperson Date 2008-01-23 Time 10:33 Rev Time 0.00
Received By mperson Date 2008-01-23 Time 10:33 Sent To  
Notes
2008-01-23 10:41:25****************PROVISO****************
 PER FS 489.105 (3) (M) PLUMBING CONTRACTOR: THE 1"
 FEBCO PRESSURE VACUUM BREAKER FOR THE POTABLE WATER
 SUPPLY FOR THE IRRIGATION SYSTEM SHALL BE INSTALLED BY
 A LICENSED PLUMBING CONTRACTOR. (SEPERATE PERMIT
 REQUIRED)
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-08-20 Cont ID  
Sent By btrobaug Date 2007-12-12 Time 16:34 Rev Time 0.33
Received By mperson Date 2007-08-20 Time 13:15 Sent To B
Notes
2007-08-20 13:38:40DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 NOTE: THE SUBMITTED PLANS ARE FOR PLAN REVIEW ONLY, NOT
 FOR PERMIT.
  
 1. PER FBC-2004 CHAPTER 1 SECTION 105.1, AS AMENDED AN
 IRRIGATION PERMIT IS REQUIRED. PER CHAPTER 481, FLORIDA
 STATUTES, PART II THE PRINTED NAME AND LICENSE OF THE
 PERSON SEALING IRRIGATION DRAWINGS REQUIRED IN TITLE
 BLOCK. PER CHAPTER 481, FLORIDA STATUTES, SECTION
 481.219(3) THE CERTIFICATE OF AUTHORIZATION NUMBER FOR
 THE LANDSCAPE ARCHITECTURAL FIRM REQUIRED IN TITLE
 BLOCK.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-09-09 Cont ID  
Sent By jroach Date 2008-09-09 Time 08:53 Rev Time 0.00
Received By jroach Date 2008-09-09 Time 08:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2008-01-22 Cont ID  
Sent By jroach Date 2008-01-22 Time 19:47 Rev Time 0.00
Received By jroach Date 2008-01-22 Time 19:47 Sent To  
Notes
2008-01-22 19:48:10***PROVISO***
  
 1) SITE LIGHTING SHALL BE SHIELDED/REFLECTED AWAY FROM
 THE ADJACENT RESIDENTIAL HOMES.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-15 Cont ID  
Sent By jroach Date 2007-08-15 Time 17:39 Rev Time 0.00
Received By jroach Date 2007-08-15 Time 17:39 Sent To I
Notes
2007-08-15 17:42:01***FAILED***
  
 1) PHOTOMETRIC PLAN SHALL BE SUBMITTED TO, AND APPROVED
 BY, THE CITY'S POLICE DEPARTMENT - CRIME PREVENTION
 UNIT (KELLY CARSILLO - 822-1620).PHOTOMETRIC LEVELS
 SHALL NOT EXCEED 0.5 FOOTCANDLES WHEN MEASURED AT THE
 RESIDENTIAL PROPERTY LINES, UNLESS THE POLICE
 DEPARTMENT REQUIRES OTHERWISE.
  
 QUESTONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.