Plan Review Stops For Permit 07070989 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-08-02 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-08-02 |
Time |
07:48 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-08-02 |
Time |
06:59 |
Sent To |
I |
|
Notes |
2007-08-02 07:47:40 | | | | | DENIED/INCOMPLETE INFORMATION | | | | 1} PROVIDE A RISER DIAGRAM FOR THE SERVICE THATS IN THE | | DESCRIPTION ON THE APPLICATION. | | | | 2}PROVIDE A SITE PLAN INDICATING THE LOCATION OF THE | | SERVICE. | | | | THE PLANS FOR THE TRAILERS DO NOT NEED TO BE SUBMITTED, | | UNLESS THEY ARE BEING INTERNALLY WIRED UNDER THIS | | APPLICATION, IF SO ADJUST THE VALUE TO REFLECT SAME. | | | | THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 | | FS, RESPECTIVELY. | | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL | | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES | | APPLY. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|