Plan Review Details - Permit 07070989
Plan Review Stops For Permit 07070989
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-02 Cont ID  
Sent By btrobaug Date 2007-08-02 Time 07:48 Rev Time 0.00
Received By btrobaug Date 2007-08-02 Time 06:59 Sent To I
Notes
2007-08-02 07:47:40 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} PROVIDE A RISER DIAGRAM FOR THE SERVICE THATS IN THE
 DESCRIPTION ON THE APPLICATION.
  
 2}PROVIDE A SITE PLAN INDICATING THE LOCATION OF THE
 SERVICE.
  
 THE PLANS FOR THE TRAILERS DO NOT NEED TO BE SUBMITTED,
 UNLESS THEY ARE BEING INTERNALLY WIRED UNDER THIS
 APPLICATION, IF SO ADJUST THE VALUE TO REFLECT SAME.
  
 THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES
 APPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-02 Cont ID  
Sent By btrobaug Date 2007-08-02 Time 07:50 Rev Time 0.00
Received By btrobaug Date 2007-08-01 Time 08:54 Sent To PC
Notes
2007-08-01 08:55:07TO "E" BOX