Plan Review Details - Permit 07070987
Plan Review Stops For Permit 07070987
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-08-28 Cont ID  
Sent By btrobaug Date 2007-08-28 Time 07:23 Rev Time 0.00
Received By btrobaug Date 2007-08-28 Time 07:16 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-02 Cont ID  
Sent By btrobaug Date 2007-08-02 Time 08:34 Rev Time 0.00
Received By btrobaug Date 2007-08-02 Time 07:53 Sent To I
Notes
2007-08-02 08:34:16 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.3.4.3.FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-21 Cont ID  
Sent By adarroug Date 2007-08-21 Time 16:03 Rev Time 0.00
Received By adarroug Date 2007-08-21 Time 16:03 Sent To E
Notes
2007-08-21 16:03:36TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-02 Cont ID  
Sent By btrobaug Date 2007-08-02 Time 08:34 Rev Time 0.00
Received By btrobaug Date 2007-08-01 Time 09:12 Sent To PC
Notes
2007-08-01 09:13:07TO "E" BOX