Plan Review Details - Permit 07070949
Plan Review Stops For Permit 07070949
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-12-07 Cont ID  
Sent By jgomez Date 2007-12-07 Time 12:52 Rev Time 0.00
Received By jgomez Date 2007-12-07 Time 12:33 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-11-13 Cont ID  
Sent By jgomez Date 2007-11-13 Time 14:02 Rev Time 0.00
Received By jgomez Date 2007-11-13 Time 12:38 Sent To PC
Notes
2007-11-13 14:50:12BUILDING REVIEW THIRD CHECKLIST.
 REVIEW UNDER EXISTING BUILDING CODE 2004, FLORIDA
 RESIDENTIAL CODE 2004 AND FBC 2004 WITH 2007
 REVISIONS.
  
 1- PROVIDE COMPLETE ENGINEERING PACKAGE FOR CHANCE
 HELICAL PIER FOUNDATION SYSTEM TO BE APPLIED TO THIS
 HOUSE AS REQUIRED ON SHEET S-1 BY ENGINEER OF RECORD
 AND BY ICC-ES LISTED REPORT ER-5110.(REPEAT COMMENT).
 INFORMATION SUBMITTED DOESN'T PROVIDE THIS
 INFORMATION.
  
  
 ***NOTE: ENGINEERING REQUIREMENTS WHERE DISCUSSED OVER
 THE PHONE WITH LADY FROM THE COMPANY SUPPLYING THE
 CHANCE HELICAL FOUNDATION SYSTEM. SHE CALLED ME TO
 CLARIFYTHAT PRODUCT APPROVAL WAS NOT REQUIRED. SHE
 TOLD ME THAT THE COMPANY'SENGINEER WILL BE PROVIDING
 THE REQUIRED ENGINEERING, BUT IT WAS NOT SUBMITTED THIS
 TIME.
  
 2- ENGINEER OF RECORD LETTER APPROVING THE FOUNDATION
 SYSTEM NEEDS TO HAVE ENGINEER'S ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATE AND
 SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE.
  
 3- SOIL TEST REPORT SUBMITTED:
 A) ENGINEER NEEDS TO SIGN AND SEAL THE REPORT AND
 PROVIDE HIS INFORMATION AS REQUIRED BY SEC.
 61G15-23.002 OF FLORIDA ADMINISTRATIVE CODE. REPORT
 SUBMITTED WAS SIGNED ONLY BY THE PROJECT COORDINATOR,
 DAVID ALKER.
  
 B) ENGINEERING FIRM NEEDS TO PROVIDE THE FIRM'S
 CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED BY SEC.
 61G15-23.002.
  
 4- TYPICAL STAIR DETAIL 4/A3 DOESN'T MATCH STRUCTURAL
 PLANS. (REPEAT COMMENT).STRUCTURAL PLANS DON'T SHOW
 WOOD POSTS. THERE IS NOT 2X6LANDING. REVISE AS
 REQUIRED.
  
 5-PLEASE MAKE SURE ALL PRODUCT APPROVALS SUBMITTED
 ARE REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO
 FBC 2004. SOME OF THE PRODUCT APPROVALS WERE NOT
 STAMPED WITH THE REVIEW STAMP.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-12 Cont ID  
Sent By jgomez Date 2007-10-12 Time 17:18 Rev Time 0.00
Received By jgomez Date 2007-10-12 Time 17:18 Sent To M
Notes
2007-10-12 17:26:50RESIDENTIAL ADDITION BUILDING REVIEW SECOND CHECKLIST.
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE, 2004
 EXISTING BUILDING CODE AND 2004 FBC.
  
 1- RECORDED NOTICE OF COMMENCEMENT SUBMITTED STATES
 THAT EXPIRATION DATE IS SEPTEMBER, 25, 2007.REVISE
 EXPIRATION DATE AND RE-RECORD DOCUMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 2- CHANCE HELICAL PIER FOUNDATION SYSTEM REQUIRES
 PRODUCT APPROVAL AS REQUIRED BY DCA RULE 9B-72.
 INFORMATION SUBMITTED IS NOT AN APPROVED FLORIDA
 PRODUCT APPROVAL. PROVIDE EITHER A FLORIDA PRODUCT
 APPROVAL OR DADE COUNTY NOA. THEN, ARCHITECT TO REVIEW
 AND APPROVE SUCH PRODUCT APPROVAL AS REQUIRED BY SEC.
 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 3-A) CHANCE HELICAL PIER FOUNDATION SYSTEM REQUIRES
 COMPLETE ENGINEERING ANALYSIS AS REQUIRED BY
 INFORMATION SUBMITTED AND BY NOTE ON FOUNDATION PLAN
 SHEET S-1. PROVIDE COMPLETE INFORMATION. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 B) PROVIDE SOIL TEST REPORT AS REQUIRED BY
 INFORMATION SUBMITTED AND REQUIREDFOR ENGINEER
 ANALYSIS OF THIS FOUNDATION SYSTEM. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 4- TYP. STAIR DETAIL 4/A3 DOESN'T MATCH PLANS. REVISE
 AS REQUIRED AND SHOW HANDRAIL HEIGHT TO VERIFY
 COMPLIANCE WITH SEC.R311.5.6.1 OF 2004 FLORIDA
 RESIDENTIAL CODE.
  
 5- SHEET S-1: REVISE ALL STRUCTURAL CONNECTORS
 USP/SIMPSON SPECIFIED ON FIRST FLOOR AND LOW ROOF
 FRAMING/BRACING PLAN. NEED TO SPECIFYWOOD TO MASONRY
 CONNECTORS WHERE REQUIRED. REVISE PLAN AND DETAILS ON
 SHEET S-2 AS REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004. REPEAT COMMENT.
  
 ***NOTE: SEE CATALOG FOR PROPER CONNECTORS THAT ARE
 DESIGNED FOR WOOD TO MASONRY APPLICATIONS. CONNECTORS
 SPECIFIED ON PLAN AREDESIGNED FOR WOOD TO WOOD
 APPLICATIONS. ALSO, PROVIDE COMPLETE ENGINEERING
 ANALYSIS FOR NUMBER AND TYPE OF FASTENERS THAT DIFFER
 FROM THOSE TESTED AND PUBLISHED BY THE MANUFACTURER.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 6- POLYSET ROOF TILE ADHESIVE NOA 04-1116.01 SUBMITTED
 CAN'T BE USED FOR THE ROOF TILE NOA SUBMITTED BECAUSE
 IT NEEDS TO BE LISTED IN THE ROOF TILE NOA IN ORDER TO
 VERIFY THE MOMENT OF RESISTANCE. SEE LIMITATIONS ON
 POLYSET NOA SUBMITTED.NEED TO PROVIDE PRODUCT
 APPROVAL FOR ADHESIVE THAT IS LISTED IN THE ROOF TILE
 PRODUCT APPROVAL. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
 ALSO, REVISE ROOF ATTACHMENT DETAIL ON SHEET S-2 AS
 REQUIRED TO MATCH PRODUCT APPROVALS SUBMITTED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-23 Cont ID  
Sent By jgomez Date 2007-08-23 Time 08:19 Rev Time 0.00
Received By jgomez Date 2007-08-23 Time 07:45 Sent To PC
Notes
2007-08-23 10:45:21SINGLE FAMILY RESIDENCE ADDITION BUILDING REVIEW FIRST
 CHECKLIST.
 REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC 2004
 WITH 2006/2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 2- BRING DRAWINGS TO PALM BEACH COUNTY (2300 N. JOG RD
 (561)233-5115) TO VERIFY IF IMPACT FEES ARE DUE. BRING
 BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF IMPACT
 FEES ARE DUE.
  
 3- SHEET G-1:
 A) TOTAL ROOF BOTTOM CHORD LOADS DON'T ADD UP
 CORRECTLY. REVISE AS REQUIRED.
  
 B) REVISE MASONRY NOTE #1. SEE SEC. R606.4 OF 2004
 FLORIDA RESIDENTIAL CODE FOR MINIMUM ALLOWABLE STRESS
 OF CONCRETE MASONRY UNITS.
  
 C) REVISE PLAN NOTE #3.SEE FBC 2004 AND 2004
 FLORIDA RESIDENTIAL CODE FOR CORRECT SECTIONS TO BE
 CITED.
  
 D) REVISE PLAN NOTE #7. WHERE IS THE TABLE 2405.3 &
 .3A REFERENCED IN THIS NOTE?. NONE FOUND IN THE CODE.
 REVISE AS REQUIRED.
  
 E) REVISE FRAMING NOTE #15. SEE ASTM C926 AND ASTM
 C1063 FOR CORRECT NAIL SIZEAND MINIMUM EMBEDMENT
 REQUIREDAT HORIZONTAL FRAMING MEMBERS.
  
 4- SPECIFY INSULATION ON WALL SEPARATING GARAGE FROM
 A/C AREA. SEE ENERGY CALCULATIONS.
  
 5- PROVIDE COMPLETE SPECIFICATIONS FOR SEPARATION OF
 GARAGE FROM OTHER LIVING AREAS TO SHOW COMPLIANCE WITH
 SECTION R309 OF 2004 FLORIDA RESIDENTIAL CODE.PROVIDE
 COMPLETE SPECS FOR DOORAND CEILING CONSTRUCTION.
  
 6- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC 2004.
 IF USINGNAILS OR SCREWS SPECIFY TYPE AND NUMBER. IF
 USING ADHESIVE SPECIFY TYPE AND PROVIDE PRODUCT
 APPROVAL AS REQUIRED BY DCA RULE 9B-72.
  
 7- HANDRAIL DETAILS SHOWN ON SHEET A-3 DON'T APPLY TO
 THIS PROJECT. REVISE AS REQUIRED. PROVIDE COMPLETE
 DETAILS/SPECS TO SHOW COMPLIANCE WITH SEC. R311.5.6 OF
 2004 FLORIDA RESIDENTIAL CODE.
  
 8- PROVIDE DETAILS/SPECS AT STAIRWAY SHOWING COMPLIANCE
 WITHSEC. R602.1.2(3) OF 2004 FLORIDA RESIDENTIAL CODE
 REGARDING FIREBLOCKING.
  
 9- PROVIDE COMPLETE ENGINEERING FOR "CHANCE HELICAL
 PILE-SS150"REQUESTED ON FOUNDATION PLAN. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 10- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) ALL USP AND SIMPSON STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS AND DETAILS.
 *** NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND SHEET WHERE CONNECTOR IS TO SAVE PAPER.
  
 B) WINDOW MULLIONS. AND, CLEARLY INDICATE FASTENING
 TO VERIFY COMPLIANCE WITH DESIGN PRESSURES CALCULATED
 BY THE ARCHITECT. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
  
 11- ALL PRODUCT APPROVALS TO BE REVIEWED AND APPROVED
 IN WRITING (NOT SIGNING AND SEALING) BY THE DESIGNER OF
 RECORD AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO
 FBC 2004.
  
 12- ENERGY CALCULATIONS:
 A) REVISE JURISDICTION NUMBER. THIS CITY IS 604700,
 NOT 601000.
  
 B) CLARIFY ITEM 8(B):WHERE IS THE SLAB ON GRADE
 EDGE INSULATION OF R-11 LOCATED? IDENTIFY ON PLANS.
  
 C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 13- PROVIDE DETAIL/SECTION THRU GARAGE EXTERIOR MASONRY
 WALL SHOWING INSULATION SHOWN ON ENERGY CALCULATIONS.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 14- SHEET A-3: THICKNESS OF PLYWOOD ROOF SHEATHING
 SHOWN ON TYP. 2ND STORY WOOD FRAMED WALLSECTION
 DOESN'T MATCH SIZE SPECIFIED ON DIAPHRAGM SCHEDULE ON
 SHEETS-2. REVISE AS REQUIRED.
  
 15- SHEET S-1:
 A) REVISE ALL STRUCTURAL CONNECTORS USP/SIMPSON
 SPECIFIED ON FIRST FLOOR AND LOW ROOF FRAMING/BRACING
 PLAN. NEED TO SPECIFY WOOD TO MASONRY CONNECTORS WHERE
 REQUIRED.REVISE PLAN AND DETAILSON SHEET S-2 AS
 REQUIRED.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 B) DETAIL 4/S2SHOWN ON FIRST FLOOR FRAMING PLAN
 DOESN'T WORK.NEED TO SHOW SECOND FLOOR WALL. DETAIL
 ONLY SHOWS CONNECTION FROM MASONRY WALL TO ROOF TRUSS.
 REVISE AS REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 C) SECOND FLOOR FRAMING PLAN:NEED TO SPECIFY
 CONNECTOR AT THE OTHER END OF GIRDER TRUSS FRAMING
 STAIRWAY OPENING. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-10-04 Cont ID  
Sent By btrobaug Date 2007-10-04 Time 12:11 Rev Time 0.00
Received By btrobaug Date 2007-10-04 Time 11:34 Sent To P
Notes
2007-10-04 12:12:30 
  
 TO JOHN'S DESK./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-06 Cont ID  
Sent By btrobaug Date 2007-08-06 Time 08:53 Rev Time 0.00
Received By btrobaug Date 2007-08-06 Time 06:52 Sent To M
Notes
2007-08-06 08:53:48 
 DENIED/INCOMPLETE INFORMATION
  
 1} NOT KNOWING THE SERVICE CALCULATION FOR THE
 RESIDENCE AS IT WAS CALCULATED WITH THE EQUIPMENT
 PRESENT AR THE TIME, AND DUE TO 230.90 EXCEPTION #3,
 WHICH READS AS FOLLOWS:
 "EXCEPTION NO. 3: TWO TO SIX CIRCUIT BREAKERS OR SETS
 OF FUSES SHALL BE PERMITTED AS THE OVERCURRENT DEVICE
 TO PROVIDE THE OVERLOAD PROTECTION. THE SUM OF THE
 RATINGS OF THE CIRCUIT BREAKERS OR FUSES SHALL BE
 PERMITTED TO EXCEED THE AMPACITY OF THE SERVICE
 CONDUCTORS, PROVIDED THE CALCULATED LOAD DOES NOT
 EXCEED THE AMPACITY OF THE SERVICE CONDUCTORS",A LOAD
 CALCULATION FOR THE SERVICE IS REQUIRED TO CONFIRM THE
 SERVICE CONDUCTORS ARE OF ADEQUATE CAPACITY FOR THE
 ADDED LOADS. SEE 220.83, 2005 NEC.
  
 2} THE WATER HEATER ON THE PLAN WAS NOT INCLUDED IN THE
 PANEL SCHEDULE SUBMITTED. ADD TOTHE CALCULATION IF
 THIS EQUIPMENT IS BEING ADDED. SEE ARTICLE 422.13 FOR
 125%. SHOW THE LOCATION OF THEDISCONNECTING MEANS PER
 422.31. ALSO SEE 422.16 REGARDING FLEXIBLE CORDS, THIS
 UNIT WILL MOST LIKELY BE REQUIRED TO BE HARDWIRED.
  
 3} THE LOADS ADDED OIN THE PANEL SCHEDULE , SHEET A-3,
 ARE LABLED FOR A KITCHEN AND FAMILY ROOM,YET THE
 ADDITION SUBMITTED FOR REVIEW CONTAINS A STUDIO AND
 BATHROOM, PLEASE CLARIFY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-02-25 Cont ID  
Sent By adarroug Date 2008-02-25 Time 11:00 Rev Time 0.00
Received By adarroug Date 2008-02-25 Time 11:00 Sent To M
Notes
2008-02-25 11:01:16TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-07 Cont ID  
Sent By adarroug Date 2007-11-07 Time 09:25 Rev Time 0.00
Received By adarroug Date 2007-11-07 Time 09:25 Sent To P
Notes
2007-11-07 09:26:06TO "P" BOX/RESUB--NEW SHEETS FOR "P"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-27 Cont ID  
Sent By adarroug Date 2007-09-27 Time 10:59 Rev Time 0.00
Received By adarroug Date 2007-09-27 Time 10:59 Sent To Z
Notes
2007-09-27 11:00:10TO "Z" BOX/RESUB--NEW "PLUMB" SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-23 Cont ID  
Sent By jgomez Date 2007-08-23 Time 10:45 Rev Time 0.00
Received By jgomez Date 2007-07-30 Time 13:20 Sent To  
Notes
2007-07-30 13:21:10TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-02-25 Cont ID  
Sent By tgordon Date 2008-02-25 Time 16:02 Rev Time 0.30
Received By tgordon Date 2008-02-25 Time 16:02 Sent To  
Notes
2008-02-25 16:03:29REVISION TO MECHANICAL PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-10-15 Cont ID  
Sent By tgordon Date 2007-10-15 Time 12:04 Rev Time 0.30
Received By tgordon Date 2007-10-15 Time 12:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-08-06 Cont ID  
Sent By tgordon Date 2007-08-06 Time 11:07 Rev Time 0.30
Received By tgordon Date 2007-08-06 Time 11:07 Sent To P
Notes
2007-08-06 11:27:09*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) THE MECHANICAL PLANS NEED THE JOB ADDRESS ON THEM,
 SEE 2004 FBC, CITY WPB AMEND. 106.1.3.
  
 3) THE MECHANICAL PLANS SHOW THE 12" SUPPLY DUCT GOING
 TO THE RETURN AIR PLENUM, PLEASE CORRECT.
  
 4) MECHANICAL PLANS SHOW TWO EXISTING AIR HANDLER UNITS
 BEING RELOCATED TO THE NEW ADDITION, PLEASE SHOW THE
 SUPPLY AND RETURN AIR DUCTS THAT WILL BE CONNECTED TO
 THE PLENUMS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-12-07 Cont ID  
Sent By jleech Date 2007-12-07 Time 14:36 Rev Time 0.00
Received By jleech Date 2007-12-07 Time 14:36 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-10-12 Cont ID  
Sent By jleech Date 2007-10-12 Time 07:15 Rev Time 0.00
Received By jleech Date 2007-10-12 Time 07:15 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-08-07 Cont ID  
Sent By jleech Date 2007-08-07 Time 08:58 Rev Time 0.00
Received By jleech Date 2007-08-07 Time 08:49 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-10-02 Cont ID  
Sent By choops Date 2007-10-02 Time 09:03 Rev Time 0.00
Received By choops Date 2007-10-02 Time 09:03 Sent To E
Notes
2007-10-02 09:03:57***APPROVED - RESUB #1***
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-31 Cont ID  
Sent By choops Date 2007-07-31 Time 13:28 Rev Time 0.00
Received By choops Date 2007-07-31 Time 13:28 Sent To E
Notes
2007-07-31 13:30:56***FAILED***
  
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT SURVEY
 SHOWING THE SCOPE OF WORK WITH SETBACK DIMENSIONS FROM
 PROPOSED ADDITION TO PROPERTY LINES.
  
 2)INDICATE ON SURVEYS/SITE PLANS ANY PROPOSED A/C
 EQUIPMENT WITH SETBACK DIMENSIONS TO PROPERTY LINES.
  
 3)SHOW ELEVATION DIMENSIONS FROM GRADE TO THE
 MIDPOINT OF THE ROOF'S PITCH (OF THE ADDITION).
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720