Plan Review Details - Permit 07070946
Plan Review Stops For Permit 07070946
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-10-04 Cont ID  
Sent By jgomez Date 2007-10-04 Time 16:28 Rev Time 0.00
Received By jgomez Date 2007-10-04 Time 16:28 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-04 Cont ID  
Sent By jgomez Date 2007-09-04 Time 09:33 Rev Time 0.00
Received By jgomez Date 2007-09-04 Time 09:30 Sent To PC
Notes
2007-09-04 09:48:06SIGN BUILDING REVIEW FIRST CHECKLIST.
 REVIEW DONE UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- SHEET A-0.1
 A) NEED TO BE SIGNED AND SEALED BY THE ARCHITECT AS
 REQUIRED BY CHAPTER 481 FLORIDA STATUTE.
  
 B)ARCHITECT NEEDS TO PROVIDE ALL HIS INFORMATION
 IN THE TITLE BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF
 FLORIDA ADMINISTRATIVE CODE.
  
 2- ENGINEER TO PROVIDE ALL THE WIND LOAD INFORMATION AS
 REQUIRED BY SEC. 1609.1 FBC 2004 AND SPECIFY CODES FOR
 WHICH STRUCTURE WAS DESIGNED.
  
 3- INFORMATION SUBMITTED ON SHEET A-0.1 DOESN'T MATCH
 INFORMATION SUBMITTED BY ENGINEER. REVISE AS REQUIRED
 TO MATCH.
  
 4- PROVIDE CURRENT RECORDED NOTICE OF COMMENCEMENT AS
 REQUIRED BY SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: ALSO, USE REVISED NOTICE OF COMMENCMENT FORM
 AND MAKE SURE CONTRACTOR' SINFORMATION AND COMPLETE
 SCOPE OF WORK IS PROVIDED.
  
 5-A) ENGINEERED DRAWINGS TO PROVIDE COMPLETE SIGN
 FRAMEWORK AND CONSTRUCTION SPECIFICATIONS. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 B) ENGINEERED DRAWINGS TO BE CLEAR COPIES. DRAWINGS
 SUBMITTED ARE NOT LEGIBLE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-10-01 Cont ID  
Sent By btrobaug Date 2007-10-01 Time 11:19 Rev Time 0.00
Received By btrobaug Date 2007-10-01 Time 11:13 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-07 Cont ID  
Sent By btrobaug Date 2007-08-07 Time 13:21 Rev Time 0.00
Received By btrobaug Date 2007-08-07 Time 13:12 Sent To B
Notes
2007-08-07 13:21:50 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS,2005
 NEC, AND FOUND NONE COMPLIANT WITH THE FOLLOWING:
  
  
 1} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS,
 CONDUIT AND CONDUCTOR SIZE AND TYPE, AND THE LOCATION
 FOR EQUIPMENT BEING WIRED UNDER THIS PERMIT .106.5 FBC
 AS AMENDEED.
  
 2} INDICATE COMPLIANCE WITH 600.6 FOR THE DISCONNECTING
 MEANS.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-25 Cont ID  
Sent By adarroug Date 2007-09-25 Time 08:40 Rev Time 0.00
Received By adarroug Date 2007-09-25 Time 08:40 Sent To Z
Notes
2007-09-25 08:40:53TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-04 Cont ID  
Sent By jgomez Date 2007-09-04 Time 09:48 Rev Time 0.00
Received By jgomez Date 2007-07-30 Time 13:29 Sent To  
Notes
2007-07-30 13:29:56TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2007-09-28 Cont ID  
Sent By choops Date 2007-09-28 Time 17:13 Rev Time 0.00
Received By choops Date 2007-09-28 Time 17:13 Sent To E
Notes
2007-09-28 17:14:30APPROVED PER SIGN PLAN FOR PREMIER PARK PD

Review Stop Z ZONING
Rev No 1 Status F Date 2007-08-02 Cont ID  
Sent By choops Date 2007-08-02 Time 10:20 Rev Time 0.00
Received By choops Date 2007-08-02 Time 10:20 Sent To E
Notes
2007-08-02 10:22:34***FAILED***
  
  
 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY SHOWING
 SCOPE OF WORK AND STREETS SURROUNDING SUBJECT
 PROPERTY.
  
 2)PLEASE INDICATE ANY EXISTING SIGNS, IF ANY, WITH:
 LOCATION, SQUARE FOOTAGE, AND SETBACKS TO PROPOSED
 SIGN.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved