Plan Review Details - Permit 07070940
Plan Review Stops For Permit 07070940
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-10-02 Cont ID  
Sent By jgomez Date 2007-10-02 Time 11:16 Rev Time 0.00
Received By jgomez Date 2007-10-02 Time 11:15 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-09-04 Cont ID  
Sent By jgomez Date 2007-09-04 Time 10:52 Rev Time 0.00
Received By jgomez Date 2007-09-04 Time 10:52 Sent To PC
Notes
2007-09-04 10:57:14SIGN BUILDING REVIEW FIRST CHECKLIST.
 REVIEW DONE UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- ENGINEER TO PROVIDE ALL HIS INFORMATION AS REQUIRED
 BY CHAPTER 471 FLORIDA STATUTE AND SEC. 61G15-23.002 OF
 FLORIDA ADMINISTRATIVE CODE.
  
 2- ENGINEER TO PROVIDE ALL WIND LOAD DESIGN INFORMATION
 AS REQUIRED BYSEC. 1609.1 FBC 2004. AND ALSO SPECIFY
 CODES TO BE USED.
  
 3- PROVIDE COMPLETE SPECIFICATIONS FOR SIGN MOUNTING TO
 RESIST WIND LOADS CALCULATED ON ITEM 2 ABOVE.CHANNEL
 LETTERS AND US PRIME LOGO. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-18 Cont ID  
Sent By btrobaug Date 2007-09-18 Time 11:27 Rev Time 0.00
Received By btrobaug Date 2007-09-14 Time 06:50 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-07 Cont ID  
Sent By btrobaug Date 2007-08-07 Time 13:33 Rev Time 0.00
Received By btrobaug Date 2007-08-07 Time 13:25 Sent To B
Notes
2007-08-07 13:33:26 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 2005 NEC,2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONE COMPLIANT WITH THE FOLLOWING:
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} A DISCONNECTING MEANS PER 600.6 FOR THE CIRCUITS
 REQUIRED BY 600.5 SHOULD BE LOCATED ON THE PLAN.
  
 2} THE ENGINEER WHO SIGNED AND SEALED THE PLAN MUST
 PROVIDE A TITLE BLOCK WITH INFORMATION PER
 61G15-23.002(2) FAC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-12 Cont ID  
Sent By adarroug Date 2007-09-12 Time 14:24 Rev Time 0.00
Received By adarroug Date 2007-09-12 Time 14:24 Sent To E
Notes
2007-09-12 14:25:03TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-04 Cont ID  
Sent By jgomez Date 2007-09-04 Time 11:00 Rev Time 0.00
Received By jgomez Date 2007-07-30 Time 13:29 Sent To  
Notes
2007-07-30 13:29:18TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2007-08-02 Cont ID  
Sent By choops Date 2007-08-02 Time 09:32 Rev Time 0.00
Received By choops Date 2007-08-02 Time 09:32 Sent To E
Notes
2007-08-02 09:35:00PROVISO:ALL ILLUMINATED SIGNS MUST CONFORM TO THE
 CITY OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS, SECTIONS 94-402(B) , 94-406 , AND ANY
 OTHER RESTRICTIONS DESIGNATED BY THE ZONING DISTRICT IN
 WHICH IT IS LOCATED.