2007-07-25 17:18:42 | BUILDING PLAN REVIEW |
| PERMIT: |
| ADD: |
| CONT: |
| TEL: (561)###-#### |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| TWO SETS OF PRODUCT APPROVAL SHALL BE SUBMITTED. |
| _OK___1.)A NOTICE OF COMMENCEMENT MUST BE FILED |
| WITH THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, |
| FS713.13. |
| |
| ____2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| INFORMATION ON THE APPLICATION, SEE ATTACHED |
| POLICY:MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / |
| AREA OF EACH ROOF TYPE |
| |
| ____3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG |
| |
| ____4.)FOR THE FLAT DECK, SELECT THE APPROVED |
| ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS. |
| |
| ____5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| FASTENING FOR CORNER AND PERIMETER ZONES. |
| |
| ____ 6.)SEE PRODUCT LIMITATION #7.CALCULATIONS |
| PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| CONSULTANT REQUIRED FOR ENHANCED FASTENING. |
| |
| |
| 2) FBC 1609.6.2.2THE SYSTEM SELECTED |
| FROM THE SUBMITTED FLAT ROOF PRODUCT |
| SHALL HAVE DESIGN PRESSURE NOT LESS THAN -89 PSF |
| GENERAL LIMITATION #9PROHIBITS |
| RATIONAL ANALYSIS OR EXTRAPOLATION TO |
| ENHANCE THE UPLIFT PRESSURE AT PERIMETER |
| AND CORNER AREAS BY REDUCING THE |
| FASTENER SPACING IN THESE AREAS.EITHER |
| SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT |
| APPROVAL) THAT DOES NOT CITE GENERAL |
| LIMITATION #9.ALTERNATIVELY IF THE |
| SELECTED SYSTEM DOES CITE GENERAL |
| LIMITATION #9, IT MUST HAVE A MAXIMUM |
| DESIGN PRESSURE THAT EXCEEDS THE |
| PRESSURE IN ROOF ZONE 3 (TYPICALLY -89 |
| PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR |
| LESS). |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| 805-6726 |
| |
| |
| |
| |
| |