Plan Review Details - Permit 07070852
Plan Review Stops For Permit 07070852
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-08-20 Cont ID  
Sent By mperson Date 2007-08-20 Time 09:50 Rev Time 0.33
Received By mperson Date 2007-08-20 Time 09:50 Sent To PC
Notes
2007-08-20 09:54:47****************PROVISO****************
 IF DRYER ROOM IS A CONFINED SPACE, OPENINGS REQUIRED
 PER SECTION 304.5 OR SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 2250 CUBIC FEET REQUIRED.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-08-10 Cont ID  
Sent By mperson Date 2007-08-10 Time 09:38 Rev Time 0.33
Received By mperson Date 2007-08-10 Time 09:38 Sent To PC
Notes
2007-08-10 09:52:45DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-16 Cont ID  
Sent By adarroug Date 2007-08-16 Time 08:47 Rev Time 0.00
Received By adarroug Date 2007-08-16 Time 08:47 Sent To G
Notes
2007-08-16 08:47:25TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-10 Cont ID  
Sent By mperson Date 2007-08-10 Time 09:52 Rev Time 0.00
Received By mperson Date 2007-07-27 Time 11:18 Sent To  
Notes
2007-07-27 11:18:40TO "G" BOX