Plan Review Stops For Permit 07070832 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
7 |
Status |
P |
Date |
2008-06-18 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-06-18 |
Time |
14:10 |
Rev Time |
0.33 |
Received By |
jwitmer |
Date |
2008-06-18 |
Time |
14:10 |
Sent To |
|
|
Notes |
2008-06-18 14:10:41 | REVISION # 5 ELECTRICAL CLOSET |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
6 |
Status |
F |
Date |
2008-04-11 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-04-11 |
Time |
15:22 |
Rev Time |
0.55 |
Received By |
jwitmer |
Date |
2008-04-11 |
Time |
15:21 |
Sent To |
FIRE |
|
Notes |
2008-04-11 15:39:34 | BUILDING PLAN REVIEW | | PERMIT: 07070832 | | ADD: 4455 MEDICAL CENTER WAY | | CONT: GSD CONTRACTING LLC | | TEL: (954)646-3538 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVISIONREVIEW | | ACTION: DENIED | | | | 1) THE CREATING A NEW ELECTRICAL CLOSET BY ADDING NEW | | WALLS AND DOORS TO ENCLOSE AN ELECTRICAL PANEL HAS | | CREATED AN ELECTRICAL VIOLATION.THE NEW ELECTRICAL | | ROOM 103B IS NOT DEEP ENOUGH TO HAVE THE CLEAR AREA IN | | FRONT OF THE PANEL, THIS WILL BE COVERED IN THE | | ELECTRICAL REVIEWERS COMMENTS WHEN PLANS ARE SUBMITTED | | UNDER THE "E" SHEETS. CURRENTLY THE ONLY CODE SECTION | | THAT COVERS THIS UNDER THE BUILDING PORTION IS 2701.1. | | SCOPE. | | THIS CHAPTER GOVERNS THE ELECTRICAL COMPONENTS, | | EQUIPMENT AND SYSTEMS USED IN BUILDINGS AND STRUCTURES | | COVERED BY THIS CODE. ELECTRICAL COMPONENTS, EQUIPMENT | | AND SYSTEMS SHALL BE DESIGNED AND CONSTRUCTED IN | | ACCORDANCE WITH THE PROVISIONS OF THE NFPA 70, NATIONAL | | ELECTRICAL CODE , EXCEPT ARTICLE 80. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)805-6731 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2008-03-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-03-12 |
Time |
11:01 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-03-12 |
Time |
11:01 |
Sent To |
PC |
|
Notes |
2008-03-12 11:02:22 | SHOP DRAWINGS YKK | | X-RAY SHIELDING |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2008-02-27 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-02-27 |
Time |
12:44 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2008-02-27 |
Time |
12:44 |
Sent To |
PC |
|
Notes |
2008-02-27 12:45:59 | REVISION: TRENCH, SLAB ON GRADE OK -PROVISO: 1816.1 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2008-01-04 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2008-01-04 |
Time |
12:39 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2008-01-04 |
Time |
12:39 |
Sent To |
|
|
Notes |
2008-01-04 12:48:26 | 07070832 | | 4455 MEDICAL CENTER WAY | | BUILDING PROVISO: | | UPON COMPLETION OF THE PHYSICIST'S REPORT FOR THE | | AMOUNT OF LEAD SHIELDING REQUIRED, | | THE CONTRACTOR IS TO SUBMIT THE REPORT ALONG WITH THE | | MANUFACTURERS SPECIFICATIONS TO | | THE CITY OF WEST PALM BEACH FOR REVIEW BEFORE THE | | FRAMING INSPECTION CAN TAKE | | PLACE. | | | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | LAW. WRITTEN COMMUNICATIONS | | TO OR FROM LOCAL OFFICIALS REGARDING CITY BUSINESS ARE | | PUBLIC RECORD, AVAILABLE TO THE | | PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-11-07 |
|
|
Cont ID |
|
Sent By |
jjohnsto |
Date |
2007-11-07 |
Time |
14:20 |
Rev Time |
3.00 |
Received By |
jjohnsto |
Date |
2007-11-07 |
Time |
14:10 |
Sent To |
|
|
Notes |
2007-11-07 14:13:44 | CONSTRUCTION SERVICES DEPARTMENT | | 200 SECOND STREET, 3RD FLOOR, | | WEST PALM BEACH, FLORIDA33401 | | TEL:561-805-6713FAX:561-805-6731 | | | | JAMES JOHNSTON, | | BUILDING PLAN EXAMINER II | | E-MAIL:JJOHNSTON @WPB.ORG | | | | | | PERMIT NO07070832 | | PROJECT CONCENTRA MEDICAL CLINIC | | ADDRESS4455 MEDICAL CENTER WAY | | DATE NOVEMBER7,2007 | | | | | | BUILDINGPLANREVIEW | | | | FLORIDA BUILDING CODES 2004 W REVISIONS | | | | 1 COMPLIED | | | | 2 COMPLIED | | | | 3 COMPLIED | | | | 4 COMPLIED | | | | 4-B NOT IN COMPLIANCE | | | | FLORIDA BUILDING CODE BUILDING 104.3 EXAMINATION OF | | DOCUMENTS | | 104.3.1 PLAN REVIEW. THE BUILDING OFFICIAL SHALL | | EXAMINE OR | | CAUSE TO BE EXAMINED EACH APPLICATION FOR A PERMIT AND | | THE | | ACCOMPANYING DOCUMENTS | | | | PROJECT INFORMATION | | FBC2004 EXISTING BUILDING | | LEVEL OF ALTERATIONIII | | NUMBER OF STORIES | | | | COMMENTPLEASE COMPLETE THE INFORMATION REQUESTED | | | | | | | | 4-C COMPLIED | | | | | | 4-D COMPLIED | | | | 5 COMPLIED | | | | 6 COMPLIED | | | | | | 7 | | COMPLIED AS NOTED | | ALL DATA FOR THE X-RAY EQUIPMENT SHALL BE SUBMITTED | | FOR | | | | REVIEW PRIOR TO FRAMING INSPECTION | | | | | | 8 COMPLIED | | | | | | | | 9 | | FLORIDA STATUE471.023CERTIFICATION OF | | BUSINESS ORGANIZATIONS.? | | (2)FOR THE PURPOSES OF THIS SECTION, A CERTIFICATE OF | | AUTHORIZATION SHALL BE REQUIRED FOR ANY BUSINESS | | ORGANIZATION?.. | | | | COMMENT HENZ ENGINEERING INC. MUST HAVE THEIR CA | | NUMBER PRINTED IN THEIR TITLE BLOCK |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-09-01 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-09-01 |
Time |
10:56 |
Rev Time |
3.55 |
Received By |
jwitmer |
Date |
2007-09-01 |
Time |
08:10 |
Sent To |
|
|
Notes |
2007-09-01 10:57:16 | BUILDING PLAN REVIEW | | PERMIT: 07070832 | | ADD: 4455 MEDICAL CENTER WAY | | CONT: GSD CONTRACTING LLC | | TEL: (954)961-4222 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | 1STREVIEW | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR | | ANTICIPATED COOPERATION. | | | | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | 3) PAGE SOUTHERN PAGE- ARCHITECTURE INTERIORS | | CONSULTING ENGINEERING | | 471.023 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE | | BLOCK FOR ANY | | SHEET BEARING THE NAME OF AN ENGINEER PRACTICING UNDER | | A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP, | | OFFERING ENGINEERING SERVICES, SHALL | | INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. | | | | 4) SHEET A-000 | | | | 4A) PLEASE CORRECT THE CODE ANALYSIS, PLANS INDICATE | | THE 2003 IBC. | | FLORIDA USES THE 2004 FBC-BUILDING WITH THE 2006 | | REVISIONS. | | | | 4B) PLEASE ALSO INCLUDE IN THE CODE ANALYSIS, THE 2004 | | FLORIDA EXISTING BUILDING CODE | | WITH 2006 REVISIONS. PLEASE IDENTIFY TO WHAT LEVEL OF | | ALTERATIONS THIS PERMIT WILL COVER UNDER THE SCOPE OF | | WORK. | | | | 4C) (2) PLEASE PROVIDE ADDITIONAL INFORMATION SEE TABLE | | 503 AS FAR AS IS THE TYPE II BUILDING A TYPE **A OR | | B**. | | | | 4D) (5) EGRESS WIDTH PLANS INDICATE 36?, PLEASE SEE | | 1016.2 CORRIDOR WIDTH NOT LESS THAN 44 INCHES, | | EXCEPTION 2 STATES THIRTY-SIX INCHES WITH A REQUIRED | | OCCUPANT CAPACITY OF 50 OR LESS. | | OCCUPANT LOAD. THE NUMBER OF PERSONS FOR WHICH THE | | MEANS OF EGRESS OF A BUILDING OR PORTION THEREOF IS | | DESIGNED. | | | | 5) SHEET A202 BREAK ROOM SECTION5EISN?T CLEAR AS TO | | CABINET HEIGHT, PLUS THE PLANS INDICATE THE USE OF A | | GARBAGE DISPOSAL, GARBAGE DISPOSAL TO BE ADA APPROVED. | | PLEASE CORRECT, SEE TEXT BELOW IN REGARDS TO BREAK ROOM | | SINK: SINKS:11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE | | MOUNTED WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE | | FINISH FLOOR. | | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH | | 30" WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH | | SINKS. | | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT | | LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) | | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN | | FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR | | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL | | EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE | | SINK. | | | | 6) SHEET A102 RESTROOMS 148,150& 153 ARE ALL NEW | | RESTROOMS REQUIRING THE LAV TO BE IN THE RESTROOM. | | 11-4.16.2 CLEAR FLOOR SPACE. | | CLEAR FLOOR SPACE FOR WATER CLOSETS NOT IN STALLS SHALL | | COMPLY WITH FIGURE 28. CLEAR FLOOR SPACE MAY BE | | ARRANGED TO ALLOW EITHER A LEFT-HANDED OR RIGHT-HANDED | | APPROACH. NOTE LAVATORIES ARE TO BE PART OF THE TOILET | | ROOM. | | | | 7) SHEET A-105 INDICATES ROOM # 137 TO BE USED FOR | | X-RAYS, PLEASE PROVIDE THE FOLLOWING INFORMATION. | | 435.5.1 SHIELDING. | | EACH X-RAY FACILITY SHALL HAVE PRIMARY AND SECONDARY | | PROTECTIVE BARRIERS AS NEEDED TO ASSURE THAT AN | | INDIVIDUAL WILL NOT RECEIVE A RADIATION DOSE IN EXCESS | | OF THE LIMITS SPECIFIED IN PART III OF CHAPTER 64 E-5, | | FLORIDA ADMINISTRATIVE CODE . | | | | 435.5.1.1 | | STRUCTURAL SHIELDING IN WALLS AND OTHER VERTICAL | | BARRIERS REQUIRED FOR PERSONNEL PROTECTION SHALL EXTEND | | WITHOUT BREACH FROM THE FLOOR TO A HEIGHT OF AT LEAST 7 | | FEET (2.1 M). | | | | 435.5.1.2 | | DOORS, DOOR FRAMES, WINDOWS AND WINDOW FRAMES SHALL | | HAVE THE SAME LEAD EQUIVALENT SHIELDING AS THAT | | REQUIRED IN THE WALL OR OTHER BARRIER IN WHICH THEY ARE | | INSTALLED. | | | | 435.5.1.3 | | PRIOR TO CONSTRUCTION, THE FLOOR PLANS AND EQUIPMENT | | ARRANGEMENT OF ALL NEW INSTALLATIONS, OR MODIFICATIONS | | OF EXISTING INSTALLATIONS, UTILIZING X-RAY ENERGIES OF | | 200 KEV AND ABOVE FOR DIAGNOSTIC OR THERAPEUTIC | | PURPOSES SHALL BE SUBMITTED TO THE DEPARTMENT OF HEALTH | | FOR REVIEW AND APPROVAL. IN COMPUTATION OF PROTECTIVE | | BARRIER REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD, | | USE FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR | | RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN | | INTO CONSIDERATION. | | | | 435.5.1.3.1 | | THE PLANS SHALL SHOW, AS A MINIMUM, THE FOLLOWING: | | 435.5.1.3.1.1 THE NORMAL LOCATION OF THE X-RAY SYSTEM?S | | RADIATION PORT; THE PORT?S TRAVEL AND TRAVERSE LIMITS; | | GENERAL DIRECTION OF THE USEFUL BEAM; LOCATIONS OF ANY | | WINDOWS AND DOORS; THE LOCATION OF THE OPERATOR?S | | BOOTH; AND THE LOCATION OF THE X-RAY CONTROL PANEL. | | 435.5.1.3.1.2 THE STRUCTURAL COMPOSITION AND THICKNESS | | OR LEAD EQUIVALENT OF ALL WALLS, DOORS, PARTITIONS, | | FLOOR AND CEILING OF THE ROOM CONCERNED. | | 435.5.1.3.1.3 THE DIMENSIONS OF THE ROOM CONCERNED. | | 435.5.1.3.1.4 THE TYPE OF OCCUPANCY OF ALL ADJACENT | | AREAS INCLUSIVE OF SPACE ABOVE AND BELOW THE ROOM | | CONCERNED. IF THERE IS AN EXTERIOR WALL, THE DISTANCE | | TO THE CLOSEST AREA WHERE IT IS LIKELY THAT INDIVIDUALS | | MAY BE PRESENT. | | 435.5.1.3.1.5 THE MAKE AND MODEL OF THE X-RAY EQUIPMENT | | AND THE MAXIMUM TECHNIQUE FACTORS. | | 435.5.1.3.1.6 THE TYPE OF EXAMINATIONS OR TREATMENTS | | WHICH WILL BE PERFORMED WITH THE EQUIPMENT. | | | | 8) SHEET E-2 THE PLANS SHOW 2 EXIT DIRECTIONAL LIGHTS | | INDICATING THE EGRESS PATH TRAVELING INTO | | ROOM# 100 WHICH IS A WAITING ROOM WITHOUT A MEANS | | PLEASE CORRECT. | | | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | REQUIREMENT, THE SPECIFIC | | REQUIREMENT SHALL BE APPLICABLE. | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | BUILDING PLAN REVIEW II | | | | | | | | | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
8 |
Status |
P |
Date |
2008-06-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-06-13 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-06-13 |
Time |
14:59 |
Sent To |
|
|
Notes |
2008-06-13 15:03:09 | REV FOR THE ADDITION OF DOORS FOR CREATING ELEC CLOSET. | | ALL SHALL MEET 110.26. MIN CLEARANCES ARE SHOWN ON | | PLANS. DESIGNATION IS ELECTRICAL ROOM AND SIGNAGE WILL | | BE REQUIRED TO SHOW " ELECTRICAL ROOM" " NO STORAGE | | PERMITTED". |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
7 |
Status |
P |
Date |
2008-04-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-04-14 |
Time |
17:45 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-04-14 |
Time |
17:45 |
Sent To |
|
|
Notes |
2008-04-14 17:45:57 | REV | | E-1, REV #3 | | E-3, REV #4 AND #5 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
6 |
Status |
F |
Date |
2008-04-08 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-04-08 |
Time |
12:30 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-04-08 |
Time |
12:30 |
Sent To |
|
|
Notes |
2008-04-08 12:30:30 | ** DENIED/ NOT PART OF REVIEW** | | | | ELECTRICAL PLANS ON ARCHITECTURAL PLANS. | | | | 1) NOTE: PLEASE SEE THE SHEET A-104 WHICH CONTAINS | | ELECTRICAL SCOPE OF WORK IS NOT TO BE REVIEWED AS THIS | | SCOPE SHOULD BE ON ELECTRICAL PLANS DONE BY THE | | ELECTRICAL ENGINEER OF RECORD. | | | | ** INDICATION OF ELECTRICAL REVISION SUBMITTED ON 3/21 | | WAS ONLY INDICATED FOR ELECTRICAL REVIEW ON 4/7. | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2008-03-04 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-03-04 |
Time |
14:06 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-03-04 |
Time |
14:06 |
Sent To |
PC |
|
Notes |
2008-03-04 14:06:27 | REV ADDING A/C UNITS. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2008-02-01 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2008-01-18 |
Time |
17:56 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2008-01-18 |
Time |
17:56 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2007-12-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-12-21 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-12-21 |
Time |
14:51 |
Sent To |
|
|
Notes |
2007-12-21 14:53:05 | ** DENIED 3RD REVIEW ** | | | | 1) NOTE:PLEASE SEE PLANS AND PACKAGE NOW INCLUDE NEW | | REVISED METHOD *B* CALCULATIONS IN REVIEW FOR THE FIRST | | TIME. | | PLEASE SEE THE PREVIOUS NOTES SPECIFICALLY STATED TO BE | | PLEASE BE SURE ALL LIGHTING NEW BEING INSTALLED AS | | SHOWN ON PLANS ARE PLACED INTO THE LIGHTING | | PERFORMANCE/ENERGY CALCULATIONS TO BE SUBMITTED. | | PLEASE EXPLAIN HOW SOME OF THESE ARE NOT INCLUDED ON | | THE INPUT DATA REPORT: FOR EXAMPLE, WHERE ARE FIXTURES | | E-1, E-2 AND E-3? WHERE IS FIXTURE *D* WHEN THE WATTAGE | | ON FIXTURE LEGEND SHOWS 110W AND IDR SHOWS 64W. | | PLEASE SEE OTHERS AS THE WATTAGE ON FIXTURE LEGEND DOES | | NOT CORRELATE WITH THE IDR. *C* FIXTURE?: | | PLEASE GO THROUGH AND SEE THE NUMBERS OF FIXTURES FOR | | 2X4 LAY-INS ON THE IDR AND PLANS. | | PLEASE SEE 13-415.2. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-10-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-10-25 |
Time |
12:53 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-10-25 |
Time |
08:38 |
Sent To |
|
|
Notes |
2007-10-25 12:53:24 | | | | | | | | | *** DENIED2ND REVIEW *** | | | | PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW STILL NEED | | TO BE ADDRESSED. | | | | | | 1) NOTE: PLEASE SEE PREVIOUS NOTE #1 WHICH MENTIONED | | THE FOLLOWING CODES WERE BEING REQUESTED ON ELECTRICAL | | PLANS. | | PLEASE SEE ONLY ONE CODE WAS INDICATED. | | PLEASE SEE MISSING NFPA-101 2003 | | | | 2) NOTE:THIS IS THE SAME COMMENT AS PREVIOUS REVIEW | | NOTE #2. | | PLEASE SEE THE TITLE BLOCKS ARE MISSING THE REQUIRED | | LICENSE INFORMATION FOR THE ARCHITECTURAL/ENGINEERING | | FIRM PAGE, SOUTHERLAND, PAGE. | | PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 | | AND 61G15-23.002 WHICH REQUIRES THE INFORMATION ON | | TITLE BLOCKS. PLEASE SEE FLORIDA STATUTES 471.023 AND | | 481.219 WHICH REQUIRES ANY FIRM OFFERING ARCHITECTURAL | | AND ENGINEERING SERVICES TO CONTAIN CERTIFICATE OF | | AUTHORIZATION LICENSE NUMBER FOR SAID FIRM PRACTICING | | UNDER EACH DISCIPLINE. | | PLEASE KNOW THIS COMMENT IS NOT FOR HENZ ENGINEERING AS | | THEIR CA # IS STATE ON TITLE BLOCKS AS REQUIRED. | | | | 3) NOTE: PLEASE SEE THE SAME EXACT ENERGY CALCULATIONS | | WERE SUBMITTED BACK. | | PLEASE SEE THAT METHOD *A* MAY NOT BE USED. THIS IS NOT | | A WHOLE BUILDING AS THE METHOD *A* IS FOR. | | THIS IS ALSO A RENOVATION IN AN EXISTING BUILDING WHICH | | MEETS 13-101.1.3, 13-101.2.3. | | PLEASE SEE 13-415.1.B, 13-415.1.C. AND 13-415.2 | | PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS/ENERGY | | CALCULATIONS AND PLEASE BE SURE THESE COORDINATE WITH | | PLANS. | | | | ** PLEASE CLARIFY NOTE #21 ON ELECTRICAL NOTES ON E-3. | | PLEASE SEE FBC CHAPTER 13 | | | | | | ** PLEASE KNOW AS SOME INFORMATION HAS NOT YET BEEN | | SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW | | COMMENTS ON THE NEXT REVIEW. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | DELAYS. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-08-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-08-25 |
Time |
11:45 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-08-23 |
Time |
21:18 |
Sent To |
|
|
Notes |
2007-08-25 11:46:03 | 2007-08-25 11:46:03 | | | | *** DENIED*** | | | | | | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS | | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES | | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. THE | | ARCHITECTURAL COVE SHEET DOES CONTAIN SOME OF THE CODES | | HOWEVER THE BELOW ARE BEING GIVEN SO THESE MAY BE | | PLACED ON PLANS INCLUSIVE OF A COVER SHEET AND | | E-SHEETS. | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | AFFECT DESIGNS FOR ALL TRADES. | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | REVIEWER AT A MINIMUM. | | 2004 FBC W/ 2006 REVISIONS | | 2005 NFPA-70 | | 2002 NFPA-72 | | 2003 NFPA-101 | | | | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED | | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS | | NOT MADE BY OTHER TRADE(S). | | | | 2) NOTE: PLEASE SEE THE TITLE BLOCKS ARE MISSING THE | | REQUIRED LICENSE INFORMATION FOR THE | | ARCHITECTURAL/ENGINEERING FIRM PAGE, SOUTHERLAND, | | PAGE. | | PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 | | AND 61G15-23.002 WHICH REQUIRES THE INFORMATION ON | | TITLE BLOCKS. PLEASE SEE FLORIDA STATUTES 471.023 AND | | 481.219 WHICH REQUIRES ANY FIRM OFFERING ARCHITECTURAL | | AND ENGINEERING SERVICES TO CONTAIN CERTIFICATE OF | | AUTHORIZATION LICENSE NUMBER FOR SAID FIRM PRACTICING | | UNDER EACH DISCIPLINE. | | PLEASE KNOW THIS COMMENT IS NOT FOR HENZ ENGINEERING AS | | THEIR CA # IS STATE ON TITLE BLOCKS AS REQUIRED. | | | | 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS | | SUBMITTED ARE REQUIRED TO COORDINATE WITH THE | | ELECTRICAL PLANS AND LIGHTING AS SHOWN ON PLANS. PLEASE | | SEE THE INPUT DATA REPORT STARTING ON PAGE #2 OF THE | | IDR. | | PLEASE SEE THE TYPE OF FIXTURES, THE NUMBER OF | | FIXTURES, THE WATTAGE AND THE CONTROL METHOD NEEDS TO | | BE COORDINATED WITH PLANS. | | PLEASE SEE THE AMOUNT OF LUMINARIES LISTED ON THE IDR | | INDICATES ONLY ONE FIXTURE FOR EACH TYPE. HOW IS THIS | | POSSIBLE WHEN THERE ARE SEVERAL FIXTURES FOR EACH | | TYPE. | | PLEASE SEE THE METHOD OF CONTROLS ARE SHOWN AS *MANUAL | | ON/OFF* WHEN THE CONTROLS ON PLANS ARE AUTOMATED/TIMERS | | ETC PLEASE CORRELATE. | | PLEASE SEE THE WATTAGE OF THE FIXTURES IS SHOWN 1600, | | 1000 WATTS ETC WHEN THE PLANS DO NOT CONTAIN ANY | | FIXTURES OF THIS WATTAGE. | | PLEASE SUBMIT THE TIME OF SCHEDULING FOR SYSTEMS. | | PLEASE INDICATE ALL MAXIMUM TIMES FOR ALL OVER RIDE | | DEVICES, OCCUPANCY TYPE DEVICES ETC. | | PLEASE SEE SOME AREAS OF PLANS SEEM TO BE MISSING | | CONTROLS ARE REQUIRED. (PHYSICAL THERAPY AREA, BUSINESS | | OFFICE AREA) | | 13-415.1.ABC.1.1, .1.2, .1.3. | | 13-415.1.A, 13-415.2 | | PLEASE GO OVER ALL OF THESE ITEMS PER FBC CHAPTER 13 | | | | 4) NOTE: PLEASE INDICATE NOTES FOR GROUNDING PER 517.13 | | (A) AND (B). | | THIS JURISDICTION HAS HAD SEVERAL INSTANCES WHERE | | CORRECT GROUNDING METHODS ARE NOT BEING DONE IN THE | | FIELD. WE ARE REQUIRING ADDITIONAL NOTES ON PLANS TO | | HELP ALLEVIATE POSSIBLE DELAYS IN PROJECTS. MANY TIMES | | THESE LOCATIONS HAVE TO BE COMPLETELY RE-WIRED DUE TO | | IMPROPER GROUNDING WHICH ONLY DELAYS AND HOLDS UP ALL | | INVOLVED. | | **MANY CONTRACTORS ARE AWARE OF CORRECT INSTALLATIONS | | IN MEDICAL OFFICES/PATIENT CARE AREAS, AND MANY ARE | | NOT. | | | | 5) NOTE: PLEASE KNOW THE SCOPE OF WORK FOR PHASED | | CONSTRUCTION WILL BE GONE OVER WITH THE INSPECTION | | SERVICES AS MANY AREAS WILL NEED TO BE SAFE AND FULL | | PROTECTION OF ALL SYSTEMS INCLUDING ANY FIRE ALARMS, | | FIRE SPRINKLERS WILL BE REQUIRED TO REMAIN OPERABLE. ** | | ONLY BEING NOTED FOR INFORMATION. | | | | 6) NOTE:PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) | | AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR | | ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON | | PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA | | SHEETS SUBMITTED. | | ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A | | SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS | | REQUIRED ON BASE PLANS AS SHOWN. | | FBC 106.3.5.1.2 | | ** WHERE BUILDINGS CONTAIN A FA SYSTEM** | | | | 7) NOTE: PLEASE KNOW ANY LOW VOLTAGE SYSTEMS WIRING | | WILL BE REQUIRED TO BE UNDER SEPARATE PERMITS. | | | | 8) NOTE: PLEASE SEE THE RISER IS SHOWING AN ADDITIONAL | | METER/MAIN FOR ONE OF THE PANELS IN THIS ONE TENANT | | SPACE. THE SINGLE TENANT IS ONLY BEING PERMITTED TO | | CONTAIN ONE METER AND THIS IS A SINGLE OCCUPANCY. THE | | NEW PANEL WHICH IS BEING RELOCATED SHOULD BE FROM THE | | TENANT METER WHICH FEEDS SPACE. | | THIS INFORMATION WILL BE FORWARDED TO ZONING AND | | BUILDING. | | PLEASE SEE LOAD CALCULATIONS FOR SERVICE DOES NOT | | INCLUDE ALL EQUIPMENT MAINS AS SHOWN ON RISER. PLEASE | | SEE MISSING MAIN #3. | | PLEASE COMPLETE AND ADJUST RISER. 90.4 220, 215.3, | | ETC. | | FBC 106.3.5.1.2 | | | | 9) NOTE: PLEASE SEE LS 101 7.8 AND 7.9. | | PLEASE PROVIDE THE MINIMUM LEVELS ARE NEEDED ON THE | | EGRESS PATHS. | | PLEASE SEE FAC 61G15-33.004. | | FBC 106.1.2 | | | | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | 2007-08-25 09:58:45 | 2007-08-25 09:58:45 | | | | REVIEW IN PROGRESS | 2007-08-23 21:18:24 | 2007-08-23 21:18:24 | | | | IN ELEC FOR REVIEW. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
6 |
Status |
P |
Date |
2008-06-19 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-06-19 |
Time |
16:25 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-06-19 |
Time |
16:14 |
Sent To |
|
|
Notes |
2008-06-19 16:25:34 | *****REVISION APPROVED***** | | | | REVIEWED REVISED SHEETS A-102, A-104, AND E1;HOWEVER | | NO FIRE-STAMPING NEEDED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
5 |
Status |
F |
Date |
2008-06-19 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-04-22 |
Time |
12:13 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-04-22 |
Time |
11:33 |
Sent To |
|
|
Notes |
2008-04-22 11:47:46 | ****UNSAT***** | | | | WHEN THE CONCERNS OF THE BUILDING AND ELECTRICAL PLAN | | REVIEWERS HAVE BEEN ADDRESSED, HOW WILL ACCESS TO THE | | ENCLOSED ELECTRICAL CLOSET BE ATTAINED IF NEEDED BY | | FIRE RESCUE PERSONNEL. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PALN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2008-02-13 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-02-13 |
Time |
16:04 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-02-13 |
Time |
15:39 |
Sent To |
|
|
Notes |
2008-02-13 15:51:01 | *****APPROVED***** | | | | PLAN SHEETS A-101, A-103, A-106, AND E-2 WERE STAMPED, | | INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2008-02-13 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2008-01-03 |
Time |
15:39 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2008-01-03 |
Time |
10:55 |
Sent To |
|
|
Notes |
2008-01-03 11:06:12 | *****PROVISO***** | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEETS TO | | BE FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE BEEN | | SATISFIED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2007-11-06 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-11-06 |
Time |
15:49 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-11-06 |
Time |
13:47 |
Sent To |
|
|
Notes |
2007-11-06 15:49:39 | *****DENIED***** | | | | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 06.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS | | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT | | OR MORE FREQUENLTLY AS NECESSARY FOR SAFE OPERATIONS. | | | | 08.PLEASE AMEND OR CLARIFY DISCREPANCIES SHOWN IN THE | | ESCAPE PLAN (SHEET A-000) AS COMPARED TO OTHER PLAN | | SHEETS' EXIT DOORS (I.E. SHEET A-102, E-2). B.DOOR | | 145A (A-102) IS SHOWN AS A MEANS OF EGRESS (A-000) BUT | | NOT MARKED AS AN EXIT (E-2). D. DOOR 130B (A-102) IS | | SHOWN AS A MEANS OF EGRESS (A-000) BUT NOT MARKED AS AN | | EXIT (E-2) | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-09-18 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-09-18 |
Time |
15:11 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-09-18 |
Time |
12:38 |
Sent To |
|
|
Notes |
2007-09-18 14:36:10 | *****DENIED***** | | | | | | 01.NFPA 101 - 2003 EDITION AND THE FLORIDA FIRE | | PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED. | | | | 02.INDEX TO DRAWINGS SHOWN ON SHEET A-000 SHOW NO | | REFERENCE TO ELECTRICAL, PLUMBING, OR MECHANICAL | | SHEETS. | | | | 03.THE SUITE NUMBER SHALL BE INCLUDED WITH THE | | NUMERICAL ADDRESS LOCATED IN THE TITLE BLOCK OF EACH | | SUBMITTED PLAN SHEET. | | | | 04.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 05.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | ACCESS TO OR EGRESS FROM THE PROPERTY OR VICINITY | | THEREOF (INCLUDING FIRE LANES). | | | | 06.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS | | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT | | OR MORE FREQUENLTLY AS NECESSARY FOR SAFE OPERATIONS. | | | | 07.SPECIFY THE INTERIOR FINISH MATERIAL | | CLASSIFICATION FOR THE EXITS, EXIT AISLE CORRIDORS, AND | | ALL OTHER SPACES IN TERMS OF CLASS A, CLASS B, OR CLASS | | C. | | | | 08.PLEASE AMEND OR CLARIFY DISCREPANCIES SHOWN IN THE | | ESCAPE PLAN (SHEET A-000) AS COMPARED TO OTHER PLAN | | SHEETS' EXIT DOORS (I.E. SHEET A-102, E-2). | | A. EXIT DOOR 108A (A-102) NOT SHOWN AS AN EXIT ON | | ESCAPE PLAN (A-000) B.DOOR 145A (A-102) IS SHOWN | | AS A MEANS OF EGRESS (A-100) BUT NOT MARKED AS AN EXIT | | (E-2). C.A MEANS OF EGRESS THROUGH THE WAITING | | AREA #100 (A-000) BUT NO EXIT DOOR IS SHOWN (E-102). D. | | DOOR 130B (A-102) IS SHOWN AS A MEANS OF EGRESS (A-100) | | BUT NOT MARKED AS AN EXIT (E-2) | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
11 |
Status |
N |
Date |
2008-06-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-06-19 |
Time |
13:27 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-06-19 |
Time |
13:27 |
Sent To |
FIRE |
|
Notes |
2008-06-19 13:28:13 | TO "F" BOX--PLANS TAKE FROM "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
10 |
Status |
N |
Date |
2008-05-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-05-22 |
Time |
16:07 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-05-22 |
Time |
16:07 |
Sent To |
|
|
Notes |
2008-05-27 16:07:24 | TO "COMM" BD#28 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
9 |
Status |
N |
Date |
2008-04-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-04-09 |
Time |
10:18 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-04-09 |
Time |
10:18 |
Sent To |
|
|
Notes |
2008-04-09 10:21:33 | TO "COMM" BD#33 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
8 |
Status |
N |
Date |
2008-03-21 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-21 |
Time |
16:43 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-21 |
Time |
16:43 |
Sent To |
|
|
Notes |
2008-03-21 16:44:06 | TO "COMM" BD#19 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
7 |
Status |
N |
Date |
2008-03-05 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-03-05 |
Time |
15:13 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-03-05 |
Time |
15:13 |
Sent To |
B |
|
Notes |
2008-03-05 15:15:46 | TO "JWITMER" DESK/2 SUBMITTALS |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2008-02-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-02-22 |
Time |
10:40 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-02-22 |
Time |
10:40 |
Sent To |
B |
|
Notes |
2008-02-22 10:41:13 | TO "JWITMER" DESK/SUBMITTAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2008-02-21 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-02-21 |
Time |
15:59 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-02-21 |
Time |
15:59 |
Sent To |
E |
|
Notes |
2008-02-21 16:00:08 | TO "E" BOX/REV |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2008-01-16 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2008-01-16 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2008-01-16 |
Time |
14:11 |
Sent To |
|
|
Notes |
2008-01-16 14:14:13 | TO "COMM" BD#49 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-12-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-12-12 |
Time |
09:47 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-12-12 |
Time |
09:43 |
Sent To |
|
|
Notes |
2007-12-12 09:48:05 | TO "COMM" BD#8 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-10-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-10-02 |
Time |
10:21 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-10-02 |
Time |
10:21 |
Sent To |
|
|
Notes |
2007-10-23 09:34:39 | TO "COMM" BD#14 | 2007-10-02 10:21:29 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-09-18 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-09-18 |
Time |
11:05 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-07-27 |
Time |
13:02 |
Sent To |
|
|
Notes |
2007-08-07 20:21:18 | TO COMM BOARD #49 | 2007-07-27 13:02:48 | WAITING FOR "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
5 |
Status |
P |
Date |
2008-07-11 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2008-07-11 |
Time |
11:51 |
Rev Time |
1.30 |
Received By |
tgordon |
Date |
2008-07-11 |
Time |
11:51 |
Sent To |
|
|
Notes |
2008-07-11 11:54:06 | REVISION: RECEIVED DETAIL M-1 AND M-2 AHU CLOSET. | | | | *** PROVISO *** | | 1) PLENUM TO COMPLY WITH 2004 FBC/M 602 AND 602.2.1 | | MATERIALS EXPOSED WITHIN PLENUMS. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-04-29 |
Time |
10:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2008-01-07 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2008-01-07 |
Time |
09:54 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2008-01-07 |
Time |
09:44 |
Sent To |
PC |
|
Notes |
2008-01-07 09:54:25 | PAGES M-1 AND M-2 REVISEDTO SHOW ARCHITECTURAL FIRM'S | | COA NUMBER. RESTAMPED. REVIEW PASSED PENDING ACCEPTANCE | | OF ENERGY CALCULATIONS BY ELECTRICAL REVIEWER. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2007-11-17 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-11-17 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-11-16 |
Time |
17:40 |
Sent To |
|
|
Notes |
2007-11-17 10:24:59 | REVIEW #: 2NE | | ACTION: PASS/PENDING | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | COMMENTS 1 THROUGH 15 HAVE BEEN ADEQUATELY ADDRESSED | | AND ARE IN COMPLIANCE. | | | | COMMENT 16: THE SAME ENERGY CALCULATIONS FROM PREVIOUS | | SUBMITTAL HAVE BEEN RESUBMITTED. THE ELECTRICAL | | DESIGNER IS NOT LISTED ON THE COMPLIANCE FORM. ALSO, | | THE ROOF TYPE IS NOT CONSISTENT WITH THIS TYPE OF | | CONSTRUCTION. | | NOTE: THIS IS A RENOVATION (AS DEFINED IN FBC 13-202) | | OF PART OF AN EXISTING BUILDING. METHOD A "WHOLE | | BUILDING COMPLIANCE" IS NOT AVAILABLE AS THIS IS NOT A | | WHOLE BUILDING CONSTRUCTION PROJECT. METHOD B OR C | | SHALL BE USED TO SHOW COMPLIANCE IN ACCORDANCE WITH FBC | | 13-400.0.C.4. | | METHOD A COMPLIANCE IS ONLY ALLOWED IN EXISTING | | BUILDINGS IF THE BUILDING CAN NOT BE BROUGHT INTO | | COMPLIANCE WITH METHOD B OR C PRESCRIPTIVE REQUIREMENTS | | AND THE ENTIRE BUILDING IS BROUGHT INTO COMPLIANCE WITH | | METHOD A IN ACCORDANCE WITH FBC 13-101.4.2. | | PROVIDE CORRECTED ENERGY CALCULATIONS AND RESUBMIT. | | | | NOTE: MECHANICAL PLANS HAVE BEEN STAMPED, BUT REVIEW | | WILL BE IN "FAILED" STATUS PENDING ACCEPTANCE OF ENERGY | | CALCULATIONS BY ALL INTERESTED TRADES. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-08-16 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-08-16 |
Time |
11:24 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-08-14 |
Time |
19:55 |
Sent To |
|
|
Notes |
2007-08-16 11:24:12 | REVIEW #: 1ST | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC | | CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. PROVIDE CFMS FOR EXISTING EXHAUST DROPS IN AHU 1 | | AREA. | | | | 2. CHECK AIR BALANCE ON ALL AHU SYSTEMS. AHU 1 AND AHU | | 2 WERE CHECKED DURING THIS REVIEW AND WERE FOUND NOT IN | | BALANCE. EXAMPLE: AHU 1 ON SCHEDULE SHOWS 4000 CFM | | SUPPLY (WHICH SEEMS HIGH FOR AN 8 TON SYSTEM) WITH 400 | | CFM OF O.A. THE FLOOR PLAN SHOWS 3400 CFM OF SUPPLY | | WITH 2600 CFM OF RETURN. THIS DOES NOT CORRESPOND WITH | | EQUIPMENT SCHEDULE OR BALANCE, EVEN WITH THE 400 CFM OF | | O.A. INCLUDED. EXHAUST COULD NOT BE TAKEN INTO ACCOUNT | | SINCE THE INFORMATION WAS NOT PROVIDED. WHEN ADJUSTING | | BALANCE OF THIS AND ALL SYSTEMS, KEEP IN MIND THAT | | MECHANICAL SYSTEMS SHALL BE DESIGNED TO ASSURE THAT THE | | BUILDING IS PRESSURIZED WITH RESPECT TO THE OUTDOORS | | PER FBC 13-409.1.ABC.2. PROVIDE AN OVERALL AIR BALANCE | | SCHEDULE TO SHOW COMPLIANCE. | | | | 3. AHU 2: RETURN AND SUPPLY DROPS IN OFFICE 105 ARE | | REVERSED. PLEASE CORRECT. | | | | 4. EXHAUST FANS IN TOILET ROOMS SHALLL EITHER RUN | | CONTINUOUS OR BE INTERLOCKED WITH THE AHU'S TO ASSURE | | THAT AIR SUPPLIED TO THESE SPACES IS EXHAUSTED AND NOT | | RECIRCULATED PER FBC,M 403.2.1(3). PROVISIONS SHALL | | ALSO BE MADE TO ASSURE THAT VENTILATION IS PROVIDED | | DURING PERIODS THAT THE ROOMS OR SPACES ARE OCCUPIED | | PER FBC,M 401.3. | | | | 5. AHU 6 SHOWS 1" CONDENSATE FROM UNIT BUT THERE IS A | | NOTE WHICH SAYS THE NEW CONDENSATE IS TO BE 3/4". | | PLEASE CLARIFY. | | | | 6. PHYSICAL THERAPY AREA ROOM 145 HAS AN OCCUPANT LOAD | | OF 36 PEOPLE PER TABLE 403.3. AT 15 CFM PER PERSON THE | | TOTAL OUTDOOR AIR REQUIRED IN THIS AREA IS 720 CFM. | | ALSO, NOTE THAT AHU 6, WHICH SERVES THIS AREA, IS NOT | | LISTED ON THE OUTDOOR AIR SCHEDULE. PLEASE CORRECT. | | | | 7. ROOM 143 LAUNDRY, DRYER EXHAUST IS REQUIRED AND | | SHALL COMPLY WITH FBC,M SEC. 504. SHOW MEANS, LOCATION | | AND TERMINATION OF THE DRYER EXHAUST DUCT SYSTEM, | | INCLUDING MANUFACTURER'S INSTALLATION INSTRUCTIONS PER | | FBC,M 504.1. | | | | 8. VERTICAL AHU DETAIL: SHOW MEANS OF SECONDARY OR | | AUXILIARY DRAIN PROTECTION AS REQUIRED BY FBC,M | | 307.2.3. | | | | 9. AREA SERVED BY AHU 1 CONTAINS A CONFERENCE ROOM | | WHICH HAS A HIGHER OCCUPANT LOAD THAN THE OFFICE AREA. | | THE OUTDOOR AIR REQUIREMENTS FOR THIS AREA SHALL BE | | BASED ON THE SPACE HAVING THE LARGEST OUTDOOR AIR | | REQUIREMENT PER FBC,M 403.3.2. PROVIDE OUTDOOR AIR | | CALCULATIONS TO SHOW COMPLIANCE. | | | | 10. THE WAITING/RECEPTION AREA SERVED BY AHU 2 ALSO HAS | | A HIGHER OCCUPANT LOAD THAN THE OFFICE AREAS AND IS | | SUBJECT TO FBC,M 403.3.2. RE-CALCULATE OUTDOOR AIR | | REQUIREMENTS AND SHOW COMPLIANCE WITH THIS SECTION. | | PLEASE ALSO DOUBLE-CHECK REMAINING SYSTEMS FOR | | COMPLIANCE PRIOR TO RESUBMITTAL. | | | | 11. AHU-5: FLOOR PLAN ONLY SHOWS 675 CFM OF RETURN. | | PLEASE SHOW HOW BALANCED RETURN IS TO BE ACHIEVED. | | FBC,M 601.4 | | | | 12. WHIRLPOOL SPA AREA REQUIRES MECHANICAL EXHAUST PER | | FBC,M 402.3.1. THIS AREA MAY NEED TO BE SEPARATED FROM | | OTHER PARTS OF THE PHYSICAL THERAPY AREA AS | | RECIRCULATION OF AIR FROM THE WHIRLPOOL SPA AREA IS | | PROHIBITED PER FBC,M 403.2.1(3). | | | | 13. EXHAUST FROM LABS 150 AND 153 HAS A NOTE FOR A | | "WALL CAP" BUT THE DUCT IS NOT SHOWN AS ROUTED TO AN | | EXTERIOR WALL. ALSO, THERE IS NO DETAIL ON M-2 FOR A | | WALL CAP. PLEASE CLARIFY. | | | | 14. BOTH OUTDOOR AIR SUPPLY AND EXHAUST SYSTEMS SHALL | | BE EQUIPPED WITH DAMPERS THAT WILL AUTOMATICALLY SHUT | | WHEN THE SYSTEMS OR SPACES SERVED ARE NOT IN USE. | | VENTILATION OUTSIDE AIR DAMPERS SHALL BE CAPABLE OF | | AUTOMATICALLY SHUTTING OFF DURING PREOCCUPANCY BUILDING | | WARMUP, COOLDOWN, AND SETBACK, EXCEPT WHEN VENTILATION | | REDUCES ENERGY COSTS (E.G., NIGHT PURGE) OR WHEN | | VENTILATION MUST BE SUPPLIED TO MEET CODE REQUIREMENTS. | | GRAVITY (NONMOTORIZED) DAMPERS ARE ACCEPTABLE IN | | BUILDING EXHAUST AIR SYSTEMS. GRAVITY (NONMOTORIZED) | | DAMPERS ARE ACCEPTABLE IN SYSTEMS WITH A DESIGN OUTSIDE | | AIR INTAKE OR EXHAUST CAPACITY OF 300 CFM OR LESS. FBC | | 13-409.1.ABC.3.3 | | | | 15. CONDENSER TIE-DOWN DETAIL: THIS DETAIL INDICATES | | CABLES AND STRAPS. WHICH IS TO BE USED? PLEASE CLARIFY. | | IF CABLES OR STRAPS ARE TO BE USED, THEY SHALL NOT | | IMPEDE EQUIPMENT SERVICE ACCESS PER FBC,M 306.1. | | | | 16. ENERGY CALCULATIONS: | | A) THE INPUT DATA REPORT SHOWS A METAL BUILDING ROOF W/ | | R-19 BATTS. IS THAT AN ACCURATE DESCRIPTION OF THE | | ROOFING SYSTEM USED ON THIS BUILDING? | | B) PLEASE INCLUDE THE PERMIT # ON THE PROJECT SUMMARY | | PAGE. | | C) INCLUDE THE NAME AND REGISTRATION NUMBER OF THE | | ELECTRICAL DESIGNER ON THE CERTIFICATIONS PAGE PER FBC | | 13-409.1.ABC.2. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2008-02-13 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2008-02-13 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2008-02-13 |
Time |
10:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2007-12-20 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-12-20 |
Time |
06:36 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-12-19 |
Time |
18:59 |
Sent To |
|
|
Notes |
2007-12-20 06:42:52 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | MUNICIPAL CODES | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | ****FROM PREVIOUS REVIEW: | | ******FROM PREVIOUS REVIEWS | | | | 1. OK | | 2. OK | | | | 3. ST A-104 EQUIPMENT SCHEDULE #36, X-RAY FILM | | PROCESSOR. AN INTERCEPTOR AND/OR A NEUTRALIZER TANK MAY | | BE REQUIRED. PLEASE CONTACT RODNEY COMPO, (561) | | 822-2272, E-MAIL [email protected], OR CALVIN WILLIAMS, | | (561) 822-2284, E-MAIL [email protected]. THEIR FAX | | NUMBER IS (561) 822-2287. PLEASE SUBMIT A DETERMINATION | | FROM ENVIRONMENTAL COMPLIANCE INDICATING REQUIREMENTS, | | IF ANY, FOR FOR AN INTERCEPTOR OR A NEUTRALIZER TANK, | | OR A WAIVER. MUNICIPAL CODE ARTICLE III SECTION | | 90-125(B)(1)(2). | | ****NO RESPONSE, NOT ADDRESSED. | | ******RESPONSE NOTED, BUT CONTACT FROM ENVIRONMENTAL | | COMPLIANCE NOT SUBMITTED. PLEASE CONTACT MR. COMPO OR | | MR. WILLIAMS FOR A DETERMINATION AS TO THE REQUIREMENT | | OF AN INTERCEPTOR OR NEUTRALIZER OR NOT. | | | | 4. OK | | | | 5. SHT A-202 DETAIL 5E. THE GARBAGE DISPOSAL SHALL BE | | ADA APPROVED. PLEASE SUBMIT THE MANUF. SPECIFICATION | | SHEETS. GARBAGE DISPOSAL SHALL NOT INTRUDE INTO THE | | CLEAR FLOOR SPACE REQUIRED FOR THE SINK. | | ****NO RESPONSE, NOT ADDRESSED. | | ******RESPONSE NOTED, BUT NO ADA APPROVAL INDICATED ON | | GARBAGE DISPOSAL SPECIFICATIONS SHEETS SUBMITTED. | | | | 6. OK | | | | 7. OK | | | | **********NEW COMMENT********** | | | | 1B. SEE ATTACHED SHEET CONCERNING THE DESIGN | | PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN ONLY AS | | A NOTICE AT THIS TIME. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE | | SET OF THEM LOOSELY ON TOP OF THE COLLATED | | PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | ****NO RESPONSE, NOT ADDRESSED BY THE ARCHITECT. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2007-12-01 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-12-01 |
Time |
04:50 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-12-01 |
Time |
04:45 |
Sent To |
|
|
Notes |
2007-12-01 05:11:28 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | MUNICIPAL CODES | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | ****FROM PREVIOUS REVIEW: | | | | 1. ALL ARCHITECTURAL SHEETS SHALL INCLUDE THE FIRM | | LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), IN THE | | TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(2) & FS | | 481.219, 481.2055. | | ****NO RESPONSE, BUT ONLY THE SHEETS CHANGED OUT HAVE | | THE FIRM LICENSE NUMBER IN THE TITLE BLOCK. ALL SHEETS | | SHALL SHOW THE FIRM LICENSE NUMBER IN THE TITLE BLOCK. | | | | | | 2. SHT A-102 TOILET ROOM 116 INDICATES TWO TOILET | | STALLS, BUT ONLY ONE W/C IS SHOWN. PLEASE CLARIFY. | | SECTION 106.1.1. | | ****NO RESPONSE, NOT ADDRESSED. | | | | 3. ST A-104 EQUIPMENT SCHEDULE #36, X-RAY FILM | | PROCESSOR. AN INTERCEPTOR AND/OR A NEUTRALIZER TANK MAY | | BE REQUIRED. PLEASE CONTACT RODNEY COMPO, (561) | | 822-2272, E-MAIL [email protected], OR CALVIN WILLIAMS, | | (561) 822-2284, E-MAIL [email protected]. THEIR FAX | | NUMBER IS (561) 822-2287. PLEASE SUBMIT A DETERMINATION | | FROM ENVIRONMENTAL COMPLIANCE INDICATING REQUIREMENTS, | | IF ANY, FOR FOR AN INTERCEPTOR OR A NEUTRALIZER TANK, | | OR A WAIVER. MUNICIPAL CODE ARTICLE III SECTION | | 90-125(B)(1)(2). | | ****NO RESPONSE, NOT ADDRESSED. | | | | 4. SHT A-105 FINISH LEGEND. CLARIFICATION REQUIRED. | | WILL ALL TOILET ROOMS HAVE A F3 SURFACE ON THE FLOORS? | | --ARE ALL WALLS IN THE NEW TOILET ROOMS TO BE | | GLASSBOARD? IF SO THE WALLS WITHIN 2' OF THE W/C'S | | SHALL HAVE A "SMOOTH, HARD, NONABSORBENT SURFACE". | | PLEASE SUBMIT MANUF. SPECIFICATIONS FOR THE GLASSBOARD. | | SHOW COMPLIANCE WITH SECTION 1210.2. | | ****NO RESPONSE, NOT ADDRESSED | | | | 5. SHT A-202 DETAIL 5E. THE GARBAGE DISPOSAL SHALL BE | | ADA APPROVED. PLEASE SUBMIT THE MANUF. SPECIFICATION | | SHEETS. GARBAGE DISPOSAL SHALL NOT INTRUDE INTO THE | | CLEAR FLOOR SPACE REQUIRED FOR THE SINK. | | ****NO RESPONSE, NOT ADDRESSED | | | | 6. OK | | | | 7. OK | | | | **********NEW COMMENT********** | | | | 1B. SEE ATTACHED SHEET CONCERNING THE DESIGN | | PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN ONLY AS | | A NOTICE AT THIS TIME. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE ONE | | SET OF THEM LOOSELY ON TOP OF THE COLLATED | | PLANS TO BE REVIEWED. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | ****NO RESPONSE, NOT ADDRESSED BY THE ARCHITECT. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-09-08 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-09-08 |
Time |
14:19 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-09-08 |
Time |
14:19 |
Sent To |
|
|
Notes |
2007-09-08 15:28:01 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 BUILDING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | MUNICIPAL CODES | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1. ALL ARCHITECTURAL SHEETS SHALL INCLUDE THE FIRM | | LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), IN THE | | TITLE BLOCK OF EACH SHEET. FAC 61G1-16.004(2) & FS | | 481.219, 481.2055. | | | | 2. SHT A-102 TOILET ROOM 116 INDICATES TWO TOILET | | STALLS, BUT ONLY ONE W/C IS SHOWN. PLEASE CLARIFY. | | SECTION 106.1.1. | | | | 3. ST A-104 EQUIPMENT SCHEDULE #36, X-RAY FILM | | PROCESSOR. AN INTERCEPTOR AND/OR A NEUTRALIZER TANK MAY | | BE REQUIRED. PLEASE CONTACT RODNEY COMPO, (561) | | 822-2272, E-MAIL [email protected], OR CALVIN WILLIAMS, | | (561) 822-2284, E-MAIL [email protected]. THEIR FAX | | NUMBER IS (561) 822-2287. PLEASE SUBMIT A DETERMINATION | | FROM ENVIRONMENTAL COMPLIANCE INDICATING REQUIREMENTS, | | IF ANY, FOR FOR AN INTERCEPTOR OR A NEUTRALIZER TANK, | | OR A WAIVER. MUNICIPAL CODE ARTICLE III SECTION | | 90-125(B)(1)(2). | | | | 4. SHT A-105 FINISH LEGEND. CLARIFICATION REQUIRED. | | WILL ALL TOILET ROOMS HAVE A F3 SURFACE ON THE FLOORS? | | --ARE ALL WALLS IN THE NEW TOILET ROOMS TO BE | | GLASSBOARD? IF SO THE WALLS WITHIN 2' OF THE W/C'S | | SHALL HAVE A "SMOOTH, HARD, NONABSORBENT SURFACE". | | PLEASE SUBMIT MANUF. SPECIFICATIONS FOR THE GLASSBOARD. | | SHOW COMPLIANCE WITH SECTION 1210.2. | | | | 5. SHT A-202 DETAIL 5E. THE GARBAGE DISPOSAL SHALL BE | | ADA APPROVED. PLEASE SUBMIT THE MANUF. SPECIFICATION | | SHEETS. GARBAGE DISPOSAL SHALL NOT INTRUDE INTO THE | | CLEAR FLOOR SPACE REQUIRED FOR THE SINK. | | | | 6. ALL ELECT. PLMG & MECH SHEETS. THE ENGINEER SHALL | | LEGIBLY INDICATE THEIR ADDRESS AS WELL AS THE ADDRESS | | OF THE ENGINEERING BUSINESS IN THE TITLE BLOCK. ONLY | | THE ADDRESS OF THE ENGINEERING BUSINESS IS INDICATED. | | FAC 61G15-23.002(2) & FS 471.025. PLEASE INDICATE THE | | ENGINEERS ADDRESS. | | | | 7. THERMAL EXPANSION CONTROL IS REQUIRED. PLEASE | | INDICATE METHOD. SECTION 607.3.2. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
N |
Date |
2007-09-07 |
|
|
Cont ID |
|
Sent By |
kdfreema |
Date |
2007-09-07 |
Time |
08:51 |
Rev Time |
0.00 |
Received By |
kdfreema |
Date |
2007-09-07 |
Time |
08:51 |
Sent To |
|
|
Notes |
|
|