Plan Review Details - Permit 07070810
Plan Review Stops For Permit 07070810
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-09-15 Cont ID  
Sent By shill Date 2007-09-15 Time 11:41 Rev Time 0.00
Received By shill Date 2007-09-15 Time 11:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-11 Cont ID  
Sent By shill Date 2007-09-11 Time 16:39 Rev Time 0.00
Received By shill Date 2007-09-11 Time 16:39 Sent To  
Notes
2007-09-11 16:43:05****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)ANCHOR SPACING IS FOR A CONCRETE SUBSTRATE, YOU
 STATE THAT THE SUBSTRATE FOR EACH OPENING IS "CONCRETE
 BLK".
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-30 Cont ID  
Sent By shill Date 2007-08-30 Time 17:50 Rev Time 0.00
Received By shill Date 2007-08-30 Time 17:50 Sent To  
Notes
2007-08-30 17:52:05****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
  
 1.0SHUTTER CONNECTION MOUNTING TYPE SHOULD BE
 SPECIFIC, SEE SHEET 7 OF THE PANEL PRODUCT APPROVAL.
 YOU'VE CIRCLED 4 BOTTOM, 5 TOP.INCLUDE INFORMATION ON
 YOUR INSTALLATION SCHEDULE.
  
 2.)CONCRETE BLOCK SUBSTRATE FOR THE CONNECTION TYPES
 YOU'VE CIRCLED REQUIRES 3" SPACING.SEE PRODUCT
 APPROVAL, REVISE INSTALLATION SCHEDULE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-21 Cont ID  
Sent By shill Date 2007-08-21 Time 10:50 Rev Time 0.00
Received By shill Date 2007-08-21 Time 10:50 Sent To  
Notes
2007-08-21 11:08:16****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 1.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR
 PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT, FBC*106.THE INSTALLATION SCHEDULE
 SUBMITTED LACKS REQUIRED INFORMATION SUCH AS THE
 SPECIFIC CONNECTION TYPE (SHOULD CORRELATE WITH THE
 ANCHOR SCHEDULE, WILL BE 1 THROUGH 9, TOP OR BOTTOM).
  
 2.AN EDGE DISTANCE OF 2" REQUIRES A .5 FACTOR, SEE
 SHEET 7 (PANELS).
  
 3.)AN EDGE DISTANCE OF 3" REQURES A .86 FACTOR, SEE
 SHEET 11 (ACCORDIONS).
  
 4.)OPENING 3, SPAN OF 38" IS MUCH LESS THAN THE
 OPENING HEIGHT OF 86".FOR A WALL MOUNT, SPAN SHOULD
 BE LARGER THAN OPENING HEIGHT (BLADE LENGTH FOR
 ACCORDIONS).
  
 5.)OPENING 6, YOU STATE THAT HIS IS WORST CASE.YOU
 SPECIFY A SPAN OF 75" FOR A 55" OPENING HEIGHT.
 OPENING 8 HAS AN 84" OPENING HEIGHT, SO HOW IS OPENING
 6 "WORST CASE"?OPENING 4 IS THE SMALLEST OPENING, SO
 THIS OPENING WILL HAVE THE GREATEST DESIGN PRESSURE
 UNLESS THERE ARE OPENINGS IN ZONE 5.
  
 6.)OPENINGS 1 AND 9, PROVIDE THE DIMENSION FOR THE
 DISTANCE TO THE CORNER.ARE ANY OF THESE OPENINGS IN
 ZONE 5?
  
 7.)IT IS ACCEPTABLE TO DESIGN TO "WORST CASE", BUT
 ALL INFORMATION TO DETERMINE CODE COMPLIANCE IS
 REQUIRED.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-12 Cont ID  
Sent By adarroug Date 2007-09-12 Time 15:39 Rev Time 0.00
Received By adarroug Date 2007-09-12 Time 15:39 Sent To B
Notes
2007-09-12 15:40:14TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-07 Cont ID  
Sent By adarroug Date 2007-09-07 Time 14:09 Rev Time 0.00
Received By adarroug Date 2007-09-07 Time 14:09 Sent To B
Notes
2007-09-07 14:10:07TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-28 Cont ID  
Sent By adarroug Date 2007-08-28 Time 13:15 Rev Time 0.00
Received By adarroug Date 2007-08-28 Time 13:15 Sent To B
Notes
2007-08-28 13:15:33TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-21 Cont ID  
Sent By shill Date 2007-08-21 Time 11:08 Rev Time 0.00
Received By shill Date 2007-07-27 Time 13:52 Sent To  
Notes
2007-07-27 13:52:50TO "MISC" BOX#1


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved