Plan Review Details - Permit 07070665
Plan Review Stops For Permit 07070665
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-02-11 Cont ID  
Sent By jgomez Date 2008-02-11 Time 16:43 Rev Time 0.00
Received By jgomez Date 2008-02-11 Time 16:43 Sent To Z
Notes
2008-02-11 16:44:28BUILDING REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-01-29 Cont ID  
Sent By jgomez Date 2008-01-29 Time 16:32 Rev Time 0.00
Received By jgomez Date 2008-01-29 Time 16:32 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-02 Cont ID  
Sent By jgomez Date 2007-11-02 Time 12:37 Rev Time 0.00
Received By jgomez Date 2007-11-02 Time 10:54 Sent To P
Notes
2007-11-02 12:58:41RESIDENTIAL REPAIRS BUILDING REVIEWPROVISO:
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:ALL SIMPSON CONNECTORS SPECIFIED ON
 DRAWINGS BY THE ENGINEER OF RECORD.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 PRODUCT APPROVAL REQUESTED ON ITEM 1 ABOVE AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 3- ENGINEER TO SPECIFY BUILDING CONSTRUCTION TYPE AS
 REQUIRED BY 602.1 FBC 2004.NEED TO IDENTIFY IF
 CONSTRUCTION TYPE A OR B. SEE SEC. 602.1 FBC 2004.
  
 4- TYPICAL WALL SECTION:
 A) WHERE WAS CONNECTOR MSTM16 TAKEN FROM? LOOKED IN
 2007 SIMPSON CATALOG AND WAS UNABLE TO FIND IT TO
 VERIFY COMPLIANCE WITH PROPOSED APPLICATION. NEED A
 WOOD TO MASONRY CONNECTOR.***NOTE: KEEP IN MIND THAT
 WHEN TYPE AND NUMBER OF FASTENERS ARE DIFFERENT FROM
 THOSE TESTED AND PUBLISHED BY THE MANUFACTURER, THEN
 COMPLETE ENGINEERING ANALYSIS WILL BE REQUIRED TO SHOW
 HOW THE LOADSARE ACHIEVED. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 B) ENGINEER OF RECORD NEEDS TO REVIEW PRODUCT
 APPROVALFOR HARDIPANEL SIDING AND REVISE WALL
 SHEATHING SIZE TO MATCH SIZE REQUIRED ON THE PRODUCT
 APPROVAL.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-03 Cont ID  
Sent By jgomez Date 2007-10-03 Time 17:43 Rev Time 0.00
Received By jgomez Date 2007-10-03 Time 17:09 Sent To PC
Notes
2007-10-03 18:04:14RESIDENTIAL REPAIRS BUILDING REVIEW SECOND CHECKLIST.
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND
 2004 FBC EXISTING BUILDINGWITH 2007 REVISIONS.
  
 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) NEW SINGLE HUNG WINDOWS. INFORMATION SUBMITTED IS
 NOT AN APPROVED PRODUCT APPROVAL. VISIT
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD APPROVED FLORIDA
 PRODUCT APPROVALS.OR PROVIDE DADE COUNTY NOA.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS AND DETAILS.REPEAT COMMENT, NOT ADDRESSED.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 3- SPECIFY CONSTRUCTION TYPE AS REQUIRED BY SEC. 602.1
 FBC 2004 AND SEC. 106.1.2CITY AMENDMENTS TO FBC 2004.
 REPEATED COMMENT, NOT ADDRESSED.
  
 4- TYPICAL WALL SECTION;
 A) PROVIDE COMPLETE TYPICAL WALL SECTION SHOWING
 CONNECTORS ON TOP AND BOTTOM OF WOOD STUDS. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004. SECTION/DETAIL
 SHOWN IS INCOMPLETE. REPEAT COMMENT, NOT ADDRESSED.
  
 B) NEED TO REVISE SIMPSON TS18 CONNECTOR. THIS IS A
 WOOD TO WOOD CONNECTOR. NEED TO SPECIFY WOOD TO MASONRY
 CONNECTOR. SEE CATALOG AND REVISE AS REQUIRED. REPEAT
 COMMENT, NOT PROPERLY ADDRESSED.
  
 5- NOTICE OF COMMENCEMENT WAS RECORDED ON 5/16/2007. IT
 EXPIRES AFTER 90 DAYS OF RECORDING IF WORK IS NOT
 STARTED. SEC. 713.13 FLORIDA STATUTE.NEED TO PROVIDE
 RE-RECORDED NOTICE OF COMMENCEMENT.
  
 6- PLEASE DON'T STAPLE PRODUCT APPROVALS TO DRAWINGS.
 THIS WILL HELP EXPEDITE THE REVIEW PROCESS.
  
 7- DRAWING 2 OF 2 IS NOT LEGIBLE. IS THIS DRAWING
 REALLY REQUIRED.COORDINATE INFORMATION IN THIS
 DRAWING WITHHARDIPLANK PRODUCT APPROVALTO AVOID
 CONFLICTS AND DELAYS IN THE REVIEW PROCESS.
  
 8- SEE ZONING COMMENTS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-07 Cont ID  
Sent By jgomez Date 2007-08-07 Time 16:47 Rev Time 0.00
Received By jgomez Date 2007-08-07 Time 16:47 Sent To P
Notes
2007-08-07 16:58:19BUILDING REVIEW FOR STRUCTURAL REPAIRS.
 FIRST REVIEW CHECKLIST.
 REVIEW DONE UNDER FBC 2004BUILDING WITH 2006
 REVISIONS AND 2004 FLORIDA RESIDENTIAL CODE:
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BYDCA RULE
 9B-72 FOR:
 A) NEW EXTERIOR WINDOWS AND DOORS.
  
 B) STORM SHUTTERS, UNLESS WINDOWS AND DOORS HAVE
 HURRICANE MISSILE IMPACT GLAZINGAS REQUIRED BY SEC.
 R301.2.1.2 OF 2004 FLORIDA RESIDENTIAL CODE. ***NOTE:
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE ATTACHED
 SAMPLE.AND,CLEARLY CIRCLEON SHUTTERS DRAWINGS
 SPECIFIC MOUNTING CONDITIONS AND SPECIFIC ANCHOR TYPE
 AND SPACING TO BE USED. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS AND DETAILS.
  
 2- SPECIFY CONSTRUCTION TYPE AS REQUIRED BY SEC. 602.1
 FBC 2004 AND SEC. 106.3.5.4 CITY AMENDMENTS TO FBC
 2004.
  
 3- TYPICAL WALL SECTION ON SHEET 1 OF 1:
 A)PROVIDE COMPLETE TYPICAL WALL SECTION SHOWING
 CONNECTORS ON TOP AND BOTTOM OF WOOD STUDS. SEC.
 106.1.2 CITY AMENDMENTS TO FB 2004. SECTION SHOWNIS
 INCOMPLETE.
  
 B)NEED TO REVISE SIMPSON ST18 STRAP SPECIFIED ON
 TYPICAL WALL SECTION SECTION.THIS IS A WOOD TO WOOD
 CONNECTOR.NEED TO SPECIFY A WOOD TO MASONRY
 CONNECTOR.SEE CURRENT SIMPSON CATALOG AND REVISE AS
 REQUIRED.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 C) PROVIDE COMPLETE SPECIFICATIONS FOR NEW STUCCO
 FINISH. PROVIDE COMPLETE WALL SHEATHING SPECS AND
 FASTENING, AND STUCCO FINISH AS REQUIRED BY ASTM C926
 AND ASTM C1063.
  
 D) HOW CAN YOU RECONSTRUCT 2X4 STUD?.SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 4- PROVIDEENERGY CALCULATIONSAS REQUIRED BY SEC.
 13-600.1.C.2 FBC 2004.
  
 5- SPECIFY SIZE AND TYPE OF WINDOW TO BE REPLACED AT
 BEDROOM WINDOW TO VERIFY COMPLIANCE WITH EGRESS
 REQUIREMENTS.SEC. 405 FBC 2004 EXISTING BUILDING.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-02-08 Cont ID  
Sent By btrobaug Date 2008-02-08 Time 11:18 Rev Time 0.00
Received By btrobaug Date 2008-02-08 Time 10:57 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-01-24 Cont ID  
Sent By btrobaug Date 2008-01-24 Time 17:04 Rev Time 0.00
Received By btrobaug Date 2008-01-24 Time 16:41 Sent To P
Notes
2008-01-24 17:04:04 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE REVISIONSUBMITTED NOW HAS A TANKLESS ELECTRIC
 WATER HEATER WITH OCP IN A CLOTHES CLOSET IN VIOLATION
 OF 240.24(D). REMOVE FROM CLOSET.
  
 2} THE LOAD CALCULATIONWAS NOT REVISED TO INDICATE THE
 NEW LOAD, REVISE SAME PER ARTICLE 220.
  
 3} SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS, THAT INCLUDE THE ELECTRICAL
 SPECIFICATIONS, FOR THE WATER HEATER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-23 Cont ID  
Sent By btrobaug Date 2007-10-23 Time 13:20 Rev Time 0.00
Received By btrobaug Date 2007-10-23 Time 13:08 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-24 Cont ID  
Sent By btrobaug Date 2007-09-24 Time 17:12 Rev Time 0.00
Received By btrobaug Date 2007-09-24 Time 17:01 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-08-06 Cont ID  
Sent By btrobaug Date 2007-08-06 Time 10:34 Rev Time 0.00
Received By btrobaug Date 2007-07-26 Time 13:34 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-02-05 Cont ID  
Sent By adarroug Date 2008-02-05 Time 13:09 Rev Time 0.00
Received By adarroug Date 2008-02-05 Time 13:08 Sent To E
Notes
2008-02-05 13:09:19TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-22 Cont ID  
Sent By adarroug Date 2008-01-22 Time 10:17 Rev Time 0.00
Received By adarroug Date 2008-01-22 Time 10:17 Sent To E
Notes
2008-01-22 10:18:11TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-17 Cont ID  
Sent By adarroug Date 2007-10-17 Time 16:22 Rev Time 0.00
Received By adarroug Date 2007-10-17 Time 16:22 Sent To Z
Notes
2007-10-17 16:22:36TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-18 Cont ID  
Sent By adarroug Date 2007-09-18 Time 11:31 Rev Time 0.00
Received By adarroug Date 2007-09-18 Time 11:31 Sent To Z
Notes
2007-09-18 11:32:11TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-07 Cont ID  
Sent By jgomez Date 2007-08-07 Time 16:58 Rev Time 0.00
Received By jgomez Date 2007-07-23 Time 15:38 Sent To  
Notes
2007-07-23 15:42:14TO "E" BOX

Review Stop P PLUMBING
Rev No 6 Status P Date 2008-02-11 Cont ID  
Sent By mperson Date 2008-02-11 Time 13:59 Rev Time 0.00
Received By mperson Date 2008-02-11 Time 13:59 Sent To B
Notes
2008-02-11 14:00:48REVISION SHEET 1: "OK"

Review Stop P PLUMBING
Rev No 5 Status F Date 2008-01-29 Cont ID  
Sent By mperson Date 2008-01-29 Time 13:42 Rev Time 0.00
Received By mperson Date 2008-01-29 Time 13:42 Sent To B
Notes
2008-01-29 13:54:44PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2006 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 REVISION DENIED:
  
 1. SHEET 1, SANITARY PLUMBING RISER DIAGRAM: THE
 BATHROOM GROUP IS NOT VENTED. PER FBC PLUMBING SECTION
 *909.1 WET VENT PERMITTED.
  
 2. SHEET 1, SANITARY PLUMBING RISER DIAGRAM: THE
 SHOWER NEEDS A WATER-SEAL TRAP. PER FBC PLUMBING
 SECTION *1002.1 FIXTURE TRAPS.
  
 3.ALL CHANGES TO THE PLAN ARE TO BE CLOUDED WITH
 REVISION NUMBERS/DATES PER FBC-2004 CHAPTER 1, SECTION
 106.1.3 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM.
 NOTE: A TRANSMITTAL LETTER IS HELPFUL.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-11-05 Cont ID  
Sent By mperson Date 2007-11-05 Time 08:01 Rev Time 0.00
Received By mperson Date 2007-11-05 Time 08:01 Sent To PC
Notes
2007-11-05 08:11:22****************PROVISO****************
 DUE TO THE SITUATION OF THE OWNERS BEING DISPLACED FROM
 THE RESIDENCE BECAUSE OF DAMAGE DUE TO VEHICLE
 COLLISION AN AS BUILT CODE COMPLIANT SANITARY ISOMETRIC
 RISER DIAGRAM WILL BE REQUIRED BEFORE A FINAL
 INSPECTION. PER FBC-2004, PLUMBING, SECTION 909.1 WET
 VENT PERMITTED: ONLY THE FIXTURES WITHIN THE BATHROOM
 GROUPS SHALL CONNECT TO THE WET-VENTED HORIZONTAL
 BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-10-30 Cont ID  
Sent By mperson Date 2007-10-30 Time 11:31 Rev Time 0.00
Received By mperson Date 2007-10-30 Time 11:31 Sent To B
Notes
2007-10-30 11:38:22DENIED
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE ON THE
 RESUBMITTED PLANS:
  
 1. SHEET 1, SANITARY RISER DIAGRAM IS INDICATING THE
 WASHING MACHINE WRONG PER FBC-2004, PLUMBING, SECTION
 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-10-03 Cont ID  
Sent By mperson Date 2007-10-03 Time 09:15 Rev Time 0.00
Received By mperson Date 2007-10-03 Time 09:15 Sent To B
Notes
2007-10-03 09:45:50DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 05 &O6 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 1. NOTE: PER ZONING COMMENTS ON ORIGINAL RECORDS SHOWS
 ORIGINAL CONSTRUCTION OF A RESIDENCE AND A COTTAGE (TWO
 SEPERATE BUILDINGS) CONNECTED WITH AN OPEN PORCH.
 SURVEY SUBMITTED SHOWS AS A DUPLEX WITHIN ONE
 STRUCTURE. PLEASE PROVIDE PROOF (PERMIT RECORD) OF A
 LEGAL CONVERSION.
  
 2. PER FBC-2004 W/05 & 06 REV., PLUMBING TABLE 403.1
 (R-3) ONE- AND TWO-FAMILY DWELLINGS THE MINIMUM FIXTURE
 REQUIREMENTS FOR THE DUPLEX ARE PER THE FOLLOWING.
  
 A} WATER CLOSET= 1 PER DWELLING UNIT.
 B} LAVATORIES= 1 PER DWELLING UNIT.
 C} BATHTUBS/SHOWERS= 1 PER DWELLING UNIT.
 D} KITCHEN SINK= 1 PER DWELLING UNIT.
 E} AUTOMATIC CLOTHES WASHER CONNECTOR= 1 PER DWELLING
 UNIT.
  
 NOTE: THE INDICATED UNIT ON THE PLANS DOES NOT HAVE A
 LAVATORY OR AN AUTOMATIC CLOTHES WASHER CONNECTOR
 INDICATED ON THE PLANS. PLEASE PROVIDE PROOF (PERMIT
 RECORD) OF A LEGAL CONVERSION.
  
 **END OF COMMENTS**
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-08-08 Cont ID  
Sent By mperson Date 2007-08-08 Time 10:37 Rev Time 0.00
Received By mperson Date 2007-08-08 Time 10:37 Sent To PC
Notes
2007-08-08 11:08:55DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 1. MORE INFORMATION IS REQUIRED DUE TO THE FACT THAT A
 PLUMBING PERMIT IS BEING APPLIED FOR.
  
 A} IF PLUMBING LAYOUT IS THE SAME
 WITH NO CHANGES, PLEASE INDICATE THIS ON
 THE RESUBMITTED DRAWING.
  
 B} IF PLUMBING LAYOUT IS THE
 SAME AND THE PLUMBING FIXTURES ARE TO BE
 CHANGED, PLEASE INDICATE ON THE RESUBMITTED DRAWING.
 "EXACT FIXTURE CHANGE OUT ONLY."
  
 C} IF THE NEW PROPOSED PLUMBING LAYOUT IS DIFFERENT
 FROM THE EXISTING PLEASE INDICATE ON A SEPERATE FLOOR
 PLAN DRAWINGS THE EXISTING FLOOR PLAN LAYOUT AND THE
 NEW PROPOSED BATHROOM PLUMBING LAYOUT AND FOLLOW WHAT
 IS REQUIRED IN COMMENT #2.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-22 Cont ID  
Sent By choops Date 2007-10-22 Time 14:08 Rev Time 0.00
Received By choops Date 2007-10-22 Time 14:05 Sent To E
Notes
2007-10-22 14:08:45***APPROVED - RESUB #2***
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 2 Status F Date 2007-09-20 Cont ID  
Sent By choops Date 2007-09-20 Time 13:46 Rev Time 0.00
Received By choops Date 2007-09-20 Time 13:46 Sent To E
Notes
2007-09-20 13:49:34***FAILED - RESUB #1***
  
  
 1)ORIGINAL RECORDS SHOW ORIGINAL CONSTRUCTION OF A
 RESIDENCE AND A COTTAGE (TWO SEPARATE BUILDINGS)
 CONNECTED WITH A OPEN PORCH.SURVEY SUBMITTED SHOWS AS
 A DUPLEX WITHIN ONE STRUCTURE.PLEASE PROVIDE PROOF
 (PERMIT RECORD) OF THE LEGAL CONVERSION.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-27 Cont ID  
Sent By choops Date 2007-07-27 Time 17:29 Rev Time 0.00
Received By choops Date 2007-07-27 Time 17:29 Sent To E
Notes
2007-07-27 17:30:48***FAILED***
  
  
 1)PLEASE PROVIDE A CURRENT SURVEY SHOWING THE SCOPE
 OF WORK WITH SETBACK DIMENSIONS TO THE PROPERTY LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720