Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-09-07 Cont ID  
Sent By jgomez Date 2007-09-07 Time 11:05 Rev Time 0.00
Received By jgomez Date 2007-09-07 Time 10:55 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-10 Cont ID  
Sent By jgomez Date 2007-08-10 Time 16:09 Rev Time 0.00
Received By jgomez Date 2007-08-10 Time 16:09 Sent To PC
Notes
2007-08-10 16:25:34SIGN BUILDING REVIEW FIRSTCHECKLIST.
 REVIEW UNDER FBC 2004.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 2- ENGINEERINGDRAWINGSTO PROVIDE COMPLETE
 SPECIFICATIONS FOR WELDING ON TYPICAL INSTALLATION
 SADDLE DETAIL.SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004 AND SEC. 2002.1 FBC 2004.
  
 3- ENGINEERING DRAWINGS TO PROVIDE COMPLETE
 SPECIFICATIONS AND DETAILS FOR"WELDED ALUMINUM
 FABRICATION" SPECIFIED ON SIGN SECTION. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004 AND SEC. 2002.1 FBC 2004.
  
 4- UPDATE ALL REFERENCE STANDARDS AND YEAR AS ADOPTED
 BY FBC 2004.SEE CHAPTER 35 OF FBC 2004 AND REVISE
 ALL SPECIFIED STANDARDS AND EDITIONSSPECIFIED ON
 SHEET 2 OF 2.
 AND, CLARIFY WHERE IS SHEET 1 OF 2?.
  
 5- NOTE #8 OF STRUCTURAL STEEL REQUIREMENTS SPECIFIES
 ASCE 7-05. CORRECT REFERENCE IS ASCE 7-02 WHICH IS THE
 ONE ADOPTED BY FBC 2004. REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-06 Cont ID  
Sent By btrobaug Date 2007-09-06 Time 12:58 Rev Time 0.00
Received By btrobaug Date 2007-09-06 Time 12:58 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-07-27 Cont ID  
Sent By btrobaug Date 2007-07-27 Time 11:44 Rev Time 0.00
Received By btrobaug Date 2007-07-27 Time 11:41 Sent To B
Notes
2007-07-27 11:45:07 
  
 B MISC #3./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-04 Cont ID  
Sent By adarroug Date 2007-09-04 Time 10:17 Rev Time 0.00
Received By adarroug Date 2007-09-04 Time 10:17 Sent To Z
Notes
2007-09-04 10:18:02TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-10 Cont ID  
Sent By jgomez Date 2007-08-10 Time 16:25 Rev Time 0.00
Received By jgomez Date 2007-07-23 Time 08:47 Sent To  
Notes
2007-07-23 08:47:46TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2007-09-05 Cont ID  
Sent By choops Date 2007-09-05 Time 10:04 Rev Time 0.00
Received By choops Date 2007-09-05 Time 10:03 Sent To E
Notes
2007-09-05 10:04:20PROVISO: ALL ILLUMINATED SIGNS MUST CONFORM TO THE CITY
 OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS, SECTIONS 94-402(B) , 94-406 , AND ANY
 OTHER RESTRICTIONS DESIGNATED BY THE ZONING DISTRICT IN
 WHICH IT IS LOCATED.
  
 PROVISO:REQUIRED 5' SETBACK FROM RIGHT OF WAY SHALL
 BE MEASURED FROM OUTER MOST POINT OF THE SIGN (NO PART
 OF THE SIGN SHALL OVERHANG WITHIN THE 5' SETBACK)

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-24 Cont ID  
Sent By choops Date 2007-07-24 Time 09:09 Rev Time 0.00
Received By choops Date 2007-07-24 Time 09:09 Sent To E
Notes
2007-07-24 09:16:07***FAILED***
  
  
 1)EXCEEDS MAXIMUM SQUARE FOOTAGE ALLOWABLE.
 PERMITTED 1/2 SQ.FT. FOR EVERY ONE (1) LINEAR FOOT OF
 FRONTAGE ALONG DIXIE HWY.AS THERE IS 147.94' FRONTAGE
 ON DIXIE HWY. THE PERMITTED SQUARE FEET FOR A HIGH
 FREE-STANDING SIGN IS 73.97 SQ.FT..PROPOSED SIGN IS
 90 SQ.FT. (45' ON TWO (2) SIDES).
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720