Plan Review Stops For Permit 07070573 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-09-11 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-09-11 |
Time |
14:07 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2007-09-11 |
Time |
14:07 |
Sent To |
PC |
|
Notes |
2007-09-11 14:08:41 | BABY FENCE AND SCREEN ENCLOSURE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-09-10 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-09-10 |
Time |
13:25 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2007-09-10 |
Time |
13:25 |
Sent To |
P |
|
Notes |
2007-09-10 13:32:51 | RESIDENTIAL POOL BUILDING REVIEW SECOND CHECKLIST. | | REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE. | | | | 1- REPEAT COMMENT FROM PREVIOUS CHECKLIST: | | CLEARLY SHOW ON DRAWINGS HOW COMPLYING WITH THE | | SWIMMING BARRIER REQUIREMENTS OF SEC. R4104.17 OF 2004 | | FLORIDA RESIDENTIAL CODE TO IMPEDE ACCESS FROM THE | | OUTSIDE AREA TO THE POOLAND FROM THE HOUSE TO THE | | POOL.. DRAWINGS SUBMITTED WERE NOT REVISED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-08-13 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-08-13 |
Time |
12:53 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2007-08-13 |
Time |
12:33 |
Sent To |
PC |
|
Notes |
2007-08-13 12:57:55 | POOL FIRST BUILDING REVIEW CHECKLIST. | | REVIEW UNDER CHAPTER 41 OF 2004 FLORIDA RESIDENTIAL | | CODE AND 2006 REVISIONS. | | | | 1- CLEARLY SHOW ON DRAWINGS HOW COMPLYING WITH THE | | SWIMMING BARRIER REQUIREMENTS OF SEC. R4101.17 OF 2004 | | FLORIDA RESIDENTIAL CODE TO IMPEDE ACCESS FROM THE | | HOUSETO THE POOL OR FROM OUTSIDEAREA TO THE POOL. | | THERE IS A NOTE ON POOL PLAN THAT SAYS "APPROX. | | LOCATION OF BABY FENCE".IT'S THE FENCE GOING TO BE | | INSTALLED AROUND THE POOL?.IS THERE A FENCE AT THE | | PERIMETER OF THE PROPERTY?.PLANS DON'T IDENTIFY THESE | | ITEMS. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2007-08-29 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-08-29 |
Time |
17:13 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-08-29 |
Time |
16:43 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-07-26 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-07-26 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-07-26 |
Time |
07:42 |
Sent To |
P |
|
Notes |
2007-07-26 10:23:41 | | | | | DENIED/INCORRECT INFORMATION | | | | THE BONDING GRID NOTE ON THE LAST (UNTITLED) SHEET OF | | THE PLAN INCORRECTLY STATES THAT THE" #8 BONDING WIRE | | IS TO BE PLACED AROUND THE PERIMETER 36" FROM THE POOL | | WATERS EDGE-----".THE TEXT OF SB 2836 READS "18 INCHES | | TO 24" FROM INSIDE THE WALL OF A SWIMMING POOL OR SPA" | | PLEASE CORRECT THAT NOTE TO INSURE THE INTENT IS MET | | AND AVOID CONFUSION IN THE FIELD. | | | | NOTE: I HAVE ATTACHED A COPY OF SENATE BILL 2836, AS IT | | PERTAINS TO ARTICLE 680, FOR THE POOL CONTRACTOR AND | | FOR THE ENGINEER, FOR YOUR RECORDS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2007-08-06 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-08-06 |
Time |
10:03 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-08-06 |
Time |
10:02 |
Sent To |
B |
|
Notes |
2007-08-06 10:04:12 | NOTE: POOL HEATER IS AN ELECTRIC HEAT PUMP. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-08-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-24 |
Time |
11:26 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-24 |
Time |
11:26 |
Sent To |
Z |
|
Notes |
2007-08-24 11:27:23 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-08-13 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2007-08-13 |
Time |
13:18 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2007-07-20 |
Time |
09:01 |
Sent To |
|
|
Notes |
2007-07-20 09:01:40 | TO "Z" BOX |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2007-09-11 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-09-11 |
Time |
13:40 |
Rev Time |
0.00 |
Received By |
mperson |
Date |
2007-09-11 |
Time |
13:40 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-08-06 |
|
|
Cont ID |
|
Sent By |
mperson |
Date |
2007-08-06 |
Time |
09:49 |
Rev Time |
0.33 |
Received By |
mperson |
Date |
2007-08-06 |
Time |
09:49 |
Sent To |
G |
|
Notes |
2007-08-06 10:02:46 | DENIED | | REFERENCE: | | ** FBC-2004 SECTION 424.2 OR R4101 SWIMMING POOLS. | | ** FBC-2004 PLUMBING. | | ** FBC-2004 CHAPTER 1, THE CITY OF | | WEST PALM BEACH AMENDMENTS. | | ** FLORIDA ADMINISTRATIVE CODE. | | ** FLORIDA STATUTES. | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | 1. PLEASE CORRELATE THE SPA SPECIFICATIONS WITH THE | | SPA PLANS ON THE RESUBMITTAL. SPA SPECIFICATIONS ARE | | INDICATING 7 THERAPY JETS AND THE SPA PLANIS | | INDICATING 6 THERAPY JETS. | | | | 2. FBC-2004 SEC. 424.2.6.6.5, OR | | FBCR-2004 SEC. R4101.6.6.5 WHERE | | PROVIDED, THE VACUUM OR PRESSURE CLEANER | | FITTING SHALL BE LOCATED AT LEAST 6" AND | | NOT GREATER THAN 12" BELOW THE MINIMUM | | OPERATING WATER LEVEL OR AS AN | | ATTACHMENT TO THE SKIMMER. | | NOTE: DETAIL REQUIRED WITH MAKE AND MODEL NUMBER OF THE | | FITTING. | | | | 3. FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC. | | R4101.9 WATER SUPPLY, LOCAL ORD. | | #2853-95, BACKFLOW REQUIRED ON WATER | | SERVICE.(PLEASE ADD TO NOTES ON THE RESUBMITTAL) | | | | 4. FBC-2004 SEC. 424.2.12.1, OR | | FBCR-2004 SEC. R4101.12.1 PRESSURE | | TESTS. PER MANUFACTURE RECOMMENDATIONS, | | NO AIR TEST SHALL BE APPROVED FOR PVC | | PIPE AND FITTINGS. (PLEASE ADD TO NOTES ON THE | | RESUBMITTAL) | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL= [email protected] | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2007-08-28 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-08-28 |
Time |
15:30 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-08-28 |
Time |
15:30 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2007-07-23 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-07-23 |
Time |
12:59 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-07-23 |
Time |
12:59 |
Sent To |
E |
|
Notes |
2007-07-23 13:01:55 | ***FAILED*** | | | | | | 1)AS THE SURVEY DOES NOT SHOW AN EXISTING FENCE | | SURROUNDING THE POOL (BABY BARRIER IS NOT SUFFICIENT), | | A FENCE PERMIT SHALL BE SUBMITTED CONCURRENTLY AND | | SHALL CONFORM TO THE MINIMUM STANDARDS PROVIDED BELOW. | | | | AS PER THE CITY OF WEST PALM BEACH ZONING AND LAND | | DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)+(C): | | | | B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE | | OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT | | ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF | | THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED. | | BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN | | HEIGHT ABOVE GRADE. | | C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE | | THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND | | SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR | | WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF | | GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL | | SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH | | WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT | | SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A | | 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE, | | AT THE PROPERTY LINE, TO ENSURE PRIVACY. | | | | 2) PLEASE PROVIDE POOL DECK DETAIL. | | | | 3)INDICATE POOL EQUIPMENT SETBACK DIMENSIONS FROM | | PROPERTY LINES. | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | TECHNICIAN | | (561)805-6720 |
|
|