Plan Review Details - Permit 07070573
Plan Review Stops For Permit 07070573
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-09-11 Cont ID  
Sent By jgomez Date 2007-09-11 Time 14:07 Rev Time 0.00
Received By jgomez Date 2007-09-11 Time 14:07 Sent To PC
Notes
2007-09-11 14:08:41BABY FENCE AND SCREEN ENCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-10 Cont ID  
Sent By jgomez Date 2007-09-10 Time 13:25 Rev Time 0.00
Received By jgomez Date 2007-09-10 Time 13:25 Sent To P
Notes
2007-09-10 13:32:51RESIDENTIAL POOL BUILDING REVIEW SECOND CHECKLIST.
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE.
  
 1- REPEAT COMMENT FROM PREVIOUS CHECKLIST:
 CLEARLY SHOW ON DRAWINGS HOW COMPLYING WITH THE
 SWIMMING BARRIER REQUIREMENTS OF SEC. R4104.17 OF 2004
 FLORIDA RESIDENTIAL CODE TO IMPEDE ACCESS FROM THE
 OUTSIDE AREA TO THE POOLAND FROM THE HOUSE TO THE
 POOL.. DRAWINGS SUBMITTED WERE NOT REVISED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-13 Cont ID  
Sent By jgomez Date 2007-08-13 Time 12:53 Rev Time 0.00
Received By jgomez Date 2007-08-13 Time 12:33 Sent To PC
Notes
2007-08-13 12:57:55POOL FIRST BUILDING REVIEW CHECKLIST.
 REVIEW UNDER CHAPTER 41 OF 2004 FLORIDA RESIDENTIAL
 CODE AND 2006 REVISIONS.
  
 1- CLEARLY SHOW ON DRAWINGS HOW COMPLYING WITH THE
 SWIMMING BARRIER REQUIREMENTS OF SEC. R4101.17 OF 2004
 FLORIDA RESIDENTIAL CODE TO IMPEDE ACCESS FROM THE
 HOUSETO THE POOL OR FROM OUTSIDEAREA TO THE POOL.
 THERE IS A NOTE ON POOL PLAN THAT SAYS "APPROX.
 LOCATION OF BABY FENCE".IT'S THE FENCE GOING TO BE
 INSTALLED AROUND THE POOL?.IS THERE A FENCE AT THE
 PERIMETER OF THE PROPERTY?.PLANS DON'T IDENTIFY THESE
 ITEMS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-08-29 Cont ID  
Sent By btrobaug Date 2007-08-29 Time 17:13 Rev Time 0.00
Received By btrobaug Date 2007-08-29 Time 16:43 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By btrobaug Date 2007-07-26 Time 10:26 Rev Time 0.00
Received By btrobaug Date 2007-07-26 Time 07:42 Sent To P
Notes
2007-07-26 10:23:41 
  
 DENIED/INCORRECT INFORMATION
  
 THE BONDING GRID NOTE ON THE LAST (UNTITLED) SHEET OF
 THE PLAN INCORRECTLY STATES THAT THE" #8 BONDING WIRE
 IS TO BE PLACED AROUND THE PERIMETER 36" FROM THE POOL
 WATERS EDGE-----".THE TEXT OF SB 2836 READS "18 INCHES
 TO 24" FROM INSIDE THE WALL OF A SWIMMING POOL OR SPA"
 PLEASE CORRECT THAT NOTE TO INSURE THE INTENT IS MET
 AND AVOID CONFUSION IN THE FIELD.
  
 NOTE: I HAVE ATTACHED A COPY OF SENATE BILL 2836, AS IT
 PERTAINS TO ARTICLE 680, FOR THE POOL CONTRACTOR AND
 FOR THE ENGINEER, FOR YOUR RECORDS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-08-06 Cont ID  
Sent By mperson Date 2007-08-06 Time 10:03 Rev Time 0.00
Received By mperson Date 2007-08-06 Time 10:02 Sent To B
Notes
2007-08-06 10:04:12NOTE: POOL HEATER IS AN ELECTRIC HEAT PUMP.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-24 Cont ID  
Sent By adarroug Date 2007-08-24 Time 11:26 Rev Time 0.00
Received By adarroug Date 2007-08-24 Time 11:26 Sent To Z
Notes
2007-08-24 11:27:23TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-13 Cont ID  
Sent By jgomez Date 2007-08-13 Time 13:18 Rev Time 0.00
Received By jgomez Date 2007-07-20 Time 09:01 Sent To  
Notes
2007-07-20 09:01:40TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-09-11 Cont ID  
Sent By mperson Date 2007-09-11 Time 13:40 Rev Time 0.00
Received By mperson Date 2007-09-11 Time 13:40 Sent To B
Notes
2007-09-11 13:43:13 

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-08-06 Cont ID  
Sent By mperson Date 2007-08-06 Time 09:49 Rev Time 0.33
Received By mperson Date 2007-08-06 Time 09:49 Sent To G
Notes
2007-08-06 10:02:46DENIED
 REFERENCE:
 ** FBC-2004 SECTION 424.2 OR R4101 SWIMMING POOLS.
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE CORRELATE THE SPA SPECIFICATIONS WITH THE
 SPA PLANS ON THE RESUBMITTAL. SPA SPECIFICATIONS ARE
 INDICATING 7 THERAPY JETS AND THE SPA PLANIS
 INDICATING 6 THERAPY JETS.
  
 2. FBC-2004 SEC. 424.2.6.6.5, OR
 FBCR-2004 SEC. R4101.6.6.5 WHERE
 PROVIDED, THE VACUUM OR PRESSURE CLEANER
 FITTING SHALL BE LOCATED AT LEAST 6" AND
 NOT GREATER THAN 12" BELOW THE MINIMUM
 OPERATING WATER LEVEL OR AS AN
 ATTACHMENT TO THE SKIMMER.
 NOTE: DETAIL REQUIRED WITH MAKE AND MODEL NUMBER OF THE
 FITTING.
  
 3. FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC.
 R4101.9 WATER SUPPLY, LOCAL ORD.
 #2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE.(PLEASE ADD TO NOTES ON THE RESUBMITTAL)
  
 4. FBC-2004 SEC. 424.2.12.1, OR
 FBCR-2004 SEC. R4101.12.1 PRESSURE
 TESTS. PER MANUFACTURE RECOMMENDATIONS,
 NO AIR TEST SHALL BE APPROVED FOR PVC
 PIPE AND FITTINGS. (PLEASE ADD TO NOTES ON THE
 RESUBMITTAL)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2007-08-28 Cont ID  
Sent By choops Date 2007-08-28 Time 15:30 Rev Time 0.00
Received By choops Date 2007-08-28 Time 15:30 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-23 Cont ID  
Sent By choops Date 2007-07-23 Time 12:59 Rev Time 0.00
Received By choops Date 2007-07-23 Time 12:59 Sent To E
Notes
2007-07-23 13:01:55***FAILED***
  
  
 1)AS THE SURVEY DOES NOT SHOW AN EXISTING FENCE
 SURROUNDING THE POOL (BABY BARRIER IS NOT SUFFICIENT),
 A FENCE PERMIT SHALL BE SUBMITTED CONCURRENTLY AND
 SHALL CONFORM TO THE MINIMUM STANDARDS PROVIDED BELOW.
  
 AS PER THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS, SECTION, 94-304(D)(2)(B)+(C):
  
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
 2) PLEASE PROVIDE POOL DECK DETAIL.
  
 3)INDICATE POOL EQUIPMENT SETBACK DIMENSIONS FROM
 PROPERTY LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720