Plan Review Details - Permit 07070568
Plan Review Stops For Permit 07070568
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-09-11 Cont ID  
Sent By mjacobs Date 2007-09-11 Time 08:49 Rev Time 0.00
Received By mjacobs Date 2007-09-11 Time 08:30 Sent To PC
Notes
2007-09-11 08:48:40PROCESS PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-09-06 Cont ID  
Sent By mjacobs Date 2007-09-06 Time 10:55 Rev Time 0.00
Received By mjacobs Date 2007-09-06 Time 10:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-08 Cont ID  
Sent By mjacobs Date 2007-08-08 Time 15:58 Rev Time 0.00
Received By mjacobs Date 2007-08-08 Time 14:35 Sent To PC
Notes
2007-08-08 15:58:43BUILDING PLAN REVIEW
 PERMIT: 07070568
 ADD: 1617 N. FLAGLER DR. #502
 CONT: KENNETH M. SALUACCI INC.
 TEL: (561)684-7459
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1) -- VERYIMPORTANT STATEMENT--
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)2004 FBC EXISTING
 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)ALL PLANS SUBMITTED AFTER OCTOBER, 1ST 2004 SHALL
 BE DESIGNED TO THE 2004 FBC / WITH 2006 REVISIONS.
 INDICATE THIS INFORMATION ON THE DRAWINGS.
  
 4)SUBMIT AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR
 PLAN CLEARLY INDICATING WHERE ALL THE CHANGES ARE
 MADE.
  
 5)SUBMIT A FINISH SCHEDULE MEETING THE REQUIREMENTS
 OF FBC 803 / 804 AND 805. INDICATE THE FLAME SPREAD AND
 SMODE-DEVELOPED INDEX OF THE ROOMS ECT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-06 Cont ID  
Sent By btrobaug Date 2007-09-06 Time 07:37 Rev Time 0.00
Received By btrobaug Date 2007-09-06 Time 06:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-03 Cont ID  
Sent By btrobaug Date 2007-08-03 Time 15:34 Rev Time 0.00
Received By btrobaug Date 2007-08-03 Time 07:48 Sent To  
Notes
2007-08-03 14:24:49 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT.
  
 1} PROVIDE A PANEL SCHEDULE SO THAT OVERCURRENT
 PROTECTION AND WIRE SIZES PER 310.16 CAN BE REVIEW, AND
 REQUIRED CIRCUITS PER 210.11 CAN BE VERIFIED AS
 COMPLIANT
  
 2} THE ISLAND RECEPTACLE(S) MUST COMPLY WITH
 210.52(C)(2). THE RECEPTACLE 16" FROM THE FLOOR WILL
 NOT MEET THE REQUIREMENT, ALSO GFCI IS REQUIRED PER
 210.8(A)(6).
  
 3} A SMOKE ALARM NEEDS TO BE ADDED OUTSIDE THE MASTER
 BEDROOM TO MEET THE INTENT OF R313.1.1" OUTSIDE EACH
 SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
 BEDROOMS"
  
 PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE PUT A ON
 THE PLAN FOR CLARITY IN THE FIELD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-09-10 Cont ID  
Sent By mawillia Date 2007-09-10 Time 13:34 Rev Time 0.00
Received By mawillia Date 2007-09-10 Time 13:18 Sent To B1
Notes
2007-09-10 13:35:43*****APPROVED*****
  
  
 ALL PREVIOUS FIRE PLAN REVIEW COMMENTS HAVE BEEN
 ADDRESSED;PLAN SHEET STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-08-07 Cont ID  
Sent By mawillia Date 2007-08-07 Time 15:22 Rev Time 0.00
Received By mawillia Date 2007-08-07 Time 13:30 Sent To  
Notes
2007-08-07 14:06:06*****DENIED*****
  
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.THE REMOVAL AND/OR THE REPLACEMENT OF BUILDING
 MATERIALS & SUPPLIES SHALL NOT INTERFERE OR HINDER
 ACCESS TO OR EGRESS FROM THE 5TH FLOOR CORRIDOR OR ANY
 OTHER FLOOR IN THE BUILDING.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE
 PROPOSED WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS
 C.
  
 6.DOORS SHALL BE NOT LESS THAN 78 INCHES IN NOMINAL
 HEIGHT.PLEASE EXPLAIN/CLARIFY DIMENSION OF THE
 PROPOSED CLOSET DOORS.
  
 7.PLEASE INDICATE IF THE UNIT SPACE'S SMOKE DETECTION
 DEVICES ARE ACTUALLY SMOKE DETECTORS OR SMOKE ALARMS.
 PLEASE BE ADVISED THAT SMOKE DETECTORS (SD) ARE TIED
 INTO THE BUILDING'S FIRE ALARM SYSTEM WHEREAS SMOKE
 ALARMS (SA) ALERT THE OCCUPANT(S) OF THE UNIT SPACE
 ONLY.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLANS EACH ITEM WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-21 Cont ID  
Sent By adarroug Date 2007-08-21 Time 16:25 Rev Time 0.00
Received By adarroug Date 2007-08-21 Time 16:25 Sent To  
Notes
2007-08-31 10:50:32TO "BOB"#12
2007-08-21 16:25:37WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-08-08 Time   Rev Time 0.00
Received By adarroug Date 2007-07-19 Time 14:21 Sent To  
Notes
2007-07-30 09:08:59TO "BOB"#16
2007-07-19 14:21:46WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-07-30 Cont ID  
Sent By tgordon Date 2007-07-30 Time 13:45 Rev Time 0.20
Received By tgordon Date 2007-07-30 Time 13:45 Sent To  
Notes
2007-07-30 13:45:51NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop Z ZONING
Rev No 1 Status N Date 2007-08-02 Cont ID  
Sent By choops Date 2007-08-02 Time 08:31 Rev Time 0.00
Received By choops Date 2007-08-02 Time 08:31 Sent To  
Notes
2007-08-02 08:31:22*VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.