Plan Review Details - Permit 07070425
Plan Review Stops For Permit 07070425
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-07-21 Cont ID  
Sent By mjacobs Date 2008-07-21 Time 08:45 Rev Time 0.00
Received By mjacobs Date 2008-07-21 Time 07:55 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-07-01 Cont ID  
Sent By mjacobs Date 2008-07-01 Time 09:39 Rev Time 0.00
Received By mjacobs Date 2008-07-01 Time 07:41 Sent To E
Notes
2008-07-01 09:39:01PERMIT: 07070425
 ADD: 201 NARCISSUS AVE # 1104-1105
 CONT: ROYAL DIAMOND HOMES
 TEL: (561)582-3818
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 7-1-08
 REVIEW: #2 REV.
 ACTION: DENIED
  
 1)NOW THE REVISED AREA IS IDENTIFIED, ADDITIONAL
 INFORMATION IS REQUIRED FOR THE SOFFITS WHICH WERE NOT
 ON THE ORIGINAL DRAWINGS. PROVIDE DETAIL DRAWINGS OF
 THE SOFFIT INDICATING ALL MATERIALS; ALSO SHOW HOW THE
 SOFFIT WILL BE ATTACHED TO THE STRUCTURE ABOVE, AND
 STATE WHAT TYPE OF FASTENERS WILL BE USED TO HOLD THE
 FRAMING MEMBERS IN PLACE. ELEVATION DRAWINGS SHALL BE
 INCLUDED ON THE PLANS TO SHOW THE BOTTOM HEIGHT OF THE
 SOFFIT. THE BUILDING OFFICIAL MAY REQUIRE DETAILS AND
 OTHER DATA NECESSARY TO DESCRIBE THE CONSTRUCTION
 INSTALLATION. 106.1.2*
  
 2)THERE IS NO A-1.5 SHEET IN OUR FILE SET, SO WHICH
 SHEET IS THIS NEW SHEET REVISING? THE REVISION NUMBER
 SHALL BE ALSO SHOWN ON THE DRAWINGS WITH THE DATE OF
 THE REVISION. THIS NEW SHEET MAKES REFERENCE TO DETAILS
 A-B-C ON SHEET A-3.0 HOWEVER, THERE IS NO SHEET A-3.0
 SUBMITTED OR IN OUR FILES. SUBMIT THIS SHEET TO SHOW
 THE NECESSARY DETAILS PER SHEET A-1.5.CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THE
 CODE. 106.1.1
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-06-23 Cont ID  
Sent By mjacobs Date 2008-06-23 Time 07:49 Rev Time 0.00
Received By mjacobs Date 2008-06-20 Time 16:46 Sent To PC
Notes
2008-06-20 17:00:02 
  
 BUILDING PLAN REVIEW
 PERMIT: 07070425
 ADD: 201 NARCISSUS AVE. #1104 &1105
 CONT: ROYAL DIAMOND HOMES
 TEL: (561)582-3818
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: REVISION
 ACTION: DENIED
  
 1)THE REVISED SHEET NEEDS TO CLEARLY SHOW THE NEW
 REVISED AREA BY CLOUDING THE AREA.THE SHEET SHALL BE
 SIGNED, DATED AND SEALED BY THE ARCHITECT OF RECORD.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-24 Cont ID  
Sent By mjacobs Date 2007-10-24 Time 14:02 Rev Time 0.00
Received By mjacobs Date 2007-10-24 Time 11:07 Sent To  
Notes
2007-10-24 14:02:50BUILDING PLAN REVIEW
 PERMIT: 07070425
 ADD: 201 NARCISSUS AVE 1104 & 1105
 CONT: ROYAL DIAMONS HOMES
 TEL: (561)582-3818
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD 10/24/07
 ACTION:
  
 1)OK
 2)OK
 3)OK
  
 4)ITEM REMOVED.
 5)OK
 6)OK
 **NEW**
 BEFORE A PERMIT IS ISSUED, PROVIDE A UNITY OF TITLE FOR
 BOTH UNITS. THE ADDRESS WILL BE ALTERED WHEN THESE TWO
 UNITS BECOME ONE. SUBMITTED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-14 Cont ID  
Sent By mjacobs Date 2007-09-14 Time 06:29 Rev Time 0.00
Received By mjacobs Date 2007-09-13 Time 06:29 Sent To  
Notes
2007-09-14 06:29:09 
  
 BUILDING PLAN REVIEW
 PERMIT: 007070425
 ADD: 201 NARCISSUS AVE 1104 & 1105
 CONT: ROYAL DIAMONS HOMES
 TEL: (561)582-3818
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION. OK
  
 2) 2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 **NOTED**
  
 3)ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004FLORIDA BUILDING
 CODE/WITH 2006 REVISIONS.
 **NOTED**
  
 4)PROVIDE THE STRUCTURAL FLOOR LOAD CALCULATIONS FOR
 THE FISH TANK AS INDICATED ON SHEET A-1.2 NOTE #7.
 **NOTED**
  
 **NOTED**
 5)WHEN THE EXISTING FLOOR IS REMOVED, WHAT TYPE OF
 MATERIAL WILL BE USED TO REPLACE IT?PROVIDE
 INFORMATION ON THE SOUND INSULATION. FBC 1207.3 THE
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS SHALL
 HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF NOT
 LESS THAN 50. SEE FBC 1207 FOR MORE INFORMATION.
  
 6)PROVIDE A FINISH SCHEDULE INDICATING THE FINISHES
 ON THE FLOOR/CEILINGS AND WALLS. SEE FBC 803/804 AND
 805.
 **NOTED**
  
 **NEW**
 BEFORE A PERMIT IS ISSUED, PROVIDE A UNITY OF TITLE FOR
 BOTH UNITS. THE ADDRESS WILL BE ALTERED WHEN THESE TWO
 UNITS BECOME ONE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-08 Cont ID  
Sent By mjacobs Date 2007-08-08 Time 10:14 Rev Time 0.00
Received By mjacobs Date 2007-08-08 Time 06:03 Sent To PC
Notes
2007-08-08 10:14:41BUILDING PLAN REVIEW
 PERMIT: 007070425
 ADD: 201 NARCISSUS AVE
 CONT: ROYAL DIAMONS HOMES
 TEL: (561)582-3818
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) 2004 FBC EXISTING
 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE/WITH 2006 REVISIONS.
  
 4)PROVIDE THE STRUCTURAL FLOOR LOAD CALCULATIONS FOR
 THE FISH TANK AS INDICATEDON SHEET A-1.2 NOTE #7.
  
 5)WHEN THE EXISTING FLOOR IS REMOVED, WHAT TYPE OF
 MATERIAL WILL BE USED TO REPLACE IT?PROVIDE
 INFORMATIONON THE SOUND INSULATION. FBC 1207.3 THE
 FLOOR/CEILINGASSEMBLIES BETWEEN DWELLING UNITS SHALL
 HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF NOT
 LESS THAN 50. SEE FBC 1207 FOR MORE INFORMATION.
  
 6)PROVIDE A FINISH SCHEDULE INDICATING THE FINISHES
 ON THE FLOOR/CEILINGS AND WALLS. SEE FBC 803/804 AND
 805.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-07-01 Cont ID  
Sent By btrobaug Date 2008-07-01 Time 14:22 Rev Time 0.00
Received By btrobaug Date 2008-07-01 Time 13:18 Sent To PC
Notes
2008-07-01 14:22:20 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THERE WAS NOT A SHEET "A-1.5" IN THE PERMITTED SET
 OF PLANS, THEREFORE THE PLAN SUBMITTED CANNOT BE A
 REVISION. PLEASE SUBMIT THE CORRECT SHEET INTENDED TO
 BE REVISED.
  
 2} 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL (SEE ALSO SECTION 106.3.5).*
 THERE APPEARS TO BE SOME REVISIONS TO THE THE LIGHTS IN
 THE DINING AND BAR AREA. IF THIS IS INTENDED AS PART OF
 THE REVISION TO SHEETA-1.4, INDICATE THAT CHANGE ON THE
 REVISION FORM.HAND DRAWN CHANGES TO THE PLAN ARE NOT
 ACCEPTABLE FOR RECORD RETENTION OR CLARITY IN THE
 FIELD. 106.1.3 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-25 Cont ID  
Sent By btrobaug Date 2007-10-25 Time 14:21 Rev Time 0.00
Received By btrobaug Date 2007-10-25 Time 13:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-09-17 Cont ID  
Sent By btrobaug Date 2007-09-17 Time 07:19 Rev Time 0.00
Received By btrobaug Date 2007-09-17 Time 06:48 Sent To  
Notes
2007-09-17 07:18:58 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 PLANS INDICATING THE SCOPE OF WORK MUST BE SUBMITTED
 WITH THE APPLICATION. NO ELECTRICAL PLANS WERE
 SUBMITTED AND AN ELECTRICAL PERMIT WAS APPLIED FOR. TWO
 SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR REVIEW PER
 106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-06 Cont ID  
Sent By btrobaug Date 2007-08-01 Time 12:33 Rev Time 0.00
Received By btrobaug Date 2007-08-01 Time 12:17 Sent To I
Notes
2007-08-06 07:41:02DEMO PERMIT ONLY
2007-08-01 12:33:29 
  
 DENIED/INCOMPLETE INFORMATION
  
 R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. INDICATE
 HOW THESE UNITS WILL INTERCONNECT.SEE 210.12 FOR AFCI
 CIRCUITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-10-24 Cont ID  
Sent By mwennerg Date 2007-10-24 Time 14:43 Rev Time 0.00
Received By mwennerg Date 2007-10-24 Time 14:43 Sent To  
Notes
2007-10-24 14:46:06CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY WITH
 NFPA 241.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-09-19 Cont ID  
Sent By mwennerg Date 2007-09-19 Time 14:28 Rev Time 0.00
Received By mwennerg Date 2007-09-19 Time 14:28 Sent To  
Notes
2007-09-19 14:31:36***DENIED***
  
 PLEASE NOTE THAT COMMENTS WERE TAKEN FROM LAST FIRE
 REVIEW. PLEASE ADDRESS COMMENTS:
  
 1) PLEASE SEE ELECTRICAL PLAN REVIEW COMMENT REGARDING
 SMOKE ALARMS. PLEASE INDICATE LOLOCATIONS AND SEE
 INTER-CONNECTING REQUIREMENTS.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) SEPARATE SHOP DRAWINGS AND PERMIT MAY BE REQUIRED
 FOR FIRE SPRINKLER REMODEL DEPENDING ON SCOPE OF WORK.-
 (OK SHT A1.0)
  
 4) PLEASE PROVIDE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING IN TERMS OF CLASS
 A,B OR C. PLEASE BE SPECIFIC REGARDING THIS PROJECT.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-08-06 Cont ID  
Sent By mwennerg Date 2007-08-06 Time 13:17 Rev Time 0.00
Received By mwennerg Date 2007-08-06 Time 13:17 Sent To  
Notes
2007-08-06 13:24:38***DENIED***
  
 1) PLEASE SEE ELECTRICAL PLAN REVIEW COMMENT REGARDING
 SMOKE ALARMS. PLEASE INDICATE LOLOCATIONS AND SEE
 INTER-CONNECTING REQUIREMENTS.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) SEPARATE SHOP DRAWINGS AND PERMIT MAY BE REQUIRED
 FOR FIRE SPRINKLER REMODEL DEPENDING ON SCOPE OF WORK.
  
 4) PLEASE PROVIDE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING IN TERMS OF CLASS
 A,B OR C. PLEASE BE SPECIFIC REGARDING THIS PROJECT.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-07-18 Cont ID  
Sent By adarroug Date 2008-07-18 Time 16:51 Rev Time 0.00
Received By adarroug Date 2008-07-18 Time 16:51 Sent To B
Notes
2008-07-18 16:52:04TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-06-26 Cont ID  
Sent By shill Date 2008-06-26 Time 16:47 Rev Time 0.00
Received By shill Date 2008-06-26 Time 16:47 Sent To B
Notes
2008-06-26 16:47:34TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-10 Cont ID  
Sent By adarroug Date 2008-06-10 Time 14:33 Rev Time 0.00
Received By adarroug Date 2008-06-10 Time 14:33 Sent To B
Notes
2008-06-10 14:33:42TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-11 Cont ID  
Sent By adarroug Date 2007-10-11 Time 08:46 Rev Time 0.00
Received By adarroug Date 2007-10-11 Time 08:46 Sent To  
Notes
2007-10-15 17:01:14TO 'BOB"#15
2007-10-11 08:46:25WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-23 Cont ID  
Sent By adarroug Date 2007-08-23 Time 08:32 Rev Time 0.00
Received By adarroug Date 2007-08-23 Time 08:32 Sent To  
Notes
2007-08-31 10:43:14TO "BOB"#4
2007-08-23 08:32:52WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-10-27 Cont ID  
Sent By jleech Date 2007-08-06 Time 07:41 Rev Time 0.00
Received By jleech Date 2007-07-16 Time 15:53 Sent To  
Notes
2007-07-19 13:49:54TO "BOB"#2
2007-07-16 15:54:17WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-07-20 Cont ID  
Sent By tgordon Date 2007-07-20 Time 12:23 Rev Time 0.20
Received By tgordon Date 2007-07-20 Time 12:23 Sent To  
Notes
2007-07-20 12:23:40NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-10-27 Cont ID  
Sent By jleech Date 2007-10-27 Time 06:32 Rev Time 0.00
Received By jleech Date 2007-10-27 Time 06:32 Sent To  
Notes
2007-10-27 06:37:20PLUMBING DEMO ONLY SEE NOTE 2 PLUMBING PERMIT REQUIRED
 INSPECTION REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-09-15 Cont ID  
Sent By jleech Date 2007-09-15 Time 06:29 Rev Time 0.00
Received By jleech Date 2007-09-15 Time 06:29 Sent To  
Notes
2007-09-15 06:53:35PAGE A-1.2 NOTE 9, SHOW WHERE AND HOW PLUMBING WILL BE
 INSTALLED. ARE EXISTINGFIXTURES TO STAY AS IS OR WILL
 THEY BE REPLACED PLEASE STATE ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-08-06 Cont ID  
Sent By jleech Date 2007-08-06 Time 07:42 Rev Time 0.00
Received By jleech Date 2007-09-15 Time 06:26 Sent To  
Notes
2007-08-06 07:43:27DEMO PLUMBING PERMIT ONLY NO FIXTURE CHANGE

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-26 Cont ID  
Sent By mflis Date 2007-10-26 Time 08:38 Rev Time 0.00
Received By mflis Date 2007-10-26 Time 08:38 Sent To  
Notes
2007-10-26 08:39:15ZONING REVIEW: PASSED
  
 * UNITY OF TITLE PROVIDED
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 2 Status F Date 2007-09-13 Cont ID  
Sent By mflis Date 2007-09-13 Time 08:30 Rev Time 0.00
Received By mflis Date 2007-09-13 Time 08:30 Sent To  
Notes
2007-09-13 08:31:39ZONING REVIEW: FAILED
  
 * REPEAT COMMENT FROM PREVIOUS REVIEW *
  
 * MUST SUBMIT EVIDENCE OF UNITY OF TITLE TO COMBINE
 THESE TWO UNITS; PLEASE PROVIDE A COPY OF UNITY OF
 TITLE WITH NEXT RESUBMISSION
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-31 Cont ID  
Sent By mflis Date 2007-07-31 Time 14:11 Rev Time 0.00
Received By mflis Date 2007-07-31 Time 14:11 Sent To E
Notes
2007-07-31 14:12:48ZONING REVIEW: FAILED
  
 * EVIDENCE OF UNITY OF TITLE SHALL BE REQUIRED TO
 COMBINE UNITS.
 * PLEASE PICK UP A COPY OF THE UNITY OF TITLE FORM AT
 THE PLANNING DEPARTMENT AND REVIEW WITH AN AVAILABLE
 PLANNER
  
 MATT FLIS - 822-1445