Plan Review Details - Permit 07070387
Plan Review Stops For Permit 07070387
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2007-09-04 Cont ID  
Sent By dpalmer Date 2007-09-04 Time 09:24 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2007-09-04 09:25:16UNIT ADDED TO SYSTEM FOR 1201 EAST AS STATED ON PLANS.
 ADDED TO PERMIT APPLICATION ALSO.
2007-09-04 09:15:07NEEDS SUITE/UNIT

Review Stop AD ADDRESSING
Rev No 1 Status N Date 2007-07-31 Cont ID  
Sent By jleech Date 2007-07-31 Time 10:21 Rev Time 0.00
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-09-26 Cont ID  
Sent By mjacobs Date 2007-09-26 Time 16:40 Rev Time 0.00
Received By mjacobs Date 2007-09-26 Time 15:49 Sent To PC
Notes
2007-09-26 16:41:31PROCESS PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-09-05 Cont ID  
Sent By mjacobs Date 2007-09-05 Time 17:43 Rev Time 0.00
Received By mjacobs Date 2007-09-05 Time 17:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-27 Cont ID  
Sent By mjacobs Date 2007-07-27 Time 15:20 Rev Time 0.00
Received By mjacobs Date 2007-07-25 Time 10:06 Sent To  
Notes
2007-07-25 12:13:04BUILDING PLAN REVIEW
 PERMIT: 07070387
 ADD: 777 S. FLAGLER DR 12FL
 CONT: BUTLER CONST
 TEL: (561)586-5353
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)OK
  
 2)OK
  
 3)OK
  
 4)OK
  
 5)OK
  
 6)OK
  
 7)OK
  
 8)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-01-04 Cont ID  
Sent By dpalmer Date 2008-01-04 Time 08:54 Rev Time 0.00
Received By dpalmer Date 2008-01-04 Time 08:54 Sent To PC
Notes
2008-01-04 08:56:04REDLINED GROUND ATTACHMENT FOR TRANSFORMER AS THIS ONLY
 SHOWS COLD WATER.
 PLEASE SEE 250.50, 250.58 AS THIS IS REQUIRED TO OTHER
 THAN COLD WATER.
 FREQENTLY THE COLD WATER LINE IN A HIGH RISE HAS CPVC
 OR OTHER DEVICE INSTALLED IN LINE WHICH AFFECTS AN
 EFFECTIVE PATH AS REQUIRED.
 MUST HIT A GROUND ELECTRODE RISER OR STRUCTURAL STEEL.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-09-20 Cont ID  
Sent By dpalmer Date 2007-09-20 Time 11:32 Rev Time 0.00
Received By dpalmer Date 2007-09-20 Time 10:49 Sent To  
Notes
2007-09-20 11:33:51***NOTES REDLINED **
  
 1) THE LOW VOLTAGE IS REQUIRED TO BE UNDER SEPARATE
 PERMIT. MAY USE PLANS TO REFERENCE FOR LV>
 2) ATTACHMENT FOR TRANSFORMER NOTED, PER 250.58
  
 PLANS STAMPED, OK.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-09-04 Cont ID  
Sent By dpalmer Date 2007-09-04 Time 12:26 Rev Time 0.00
Received By dpalmer Date 2007-08-31 Time 16:09 Sent To  
Notes
2007-09-04 12:26:432007-09-04 12:26:43
  
 ** DENIED2ND REVIEW**
  
  
 ** PLEASE SEE THERE ARE COMMENTS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING.
 ** PLEASE SEE THERE ARE ALSO NEW COMMENTS AS THERE WERE
 SEVERAL CHANGES MADE TO PANEL SCHEDULES/RISER WHICH
 HAVE CREATED NEW COMMENTS. AS THESE ITEMS WERE NOT ON
 PREVIOUS PLANS THIS WAY, THESE NEW COMMENTS COULD NOT
 HAVE BEEN MADE ON THE PREVIOUS REVIEW.
  
 1) NOTE: PLEASE SEE PREVIOUS NOTE #1 WITH RESPECT TO
 CODES REQUIRED. PLEASE SEE ARCHITECTURAL COVER SHEET
 WHICH NOTES A 2005 NFPA-72. PLEASE KNOW THIS CODE
 SHOULD BE THE 2002 NFPA-72.
 PLEASE ADJUST.
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH
 MAY REQUIRE CERTAIN CODES.
  
 2) NOTE: PLEASE SEE NOTE #6 FROM PREVIOUS REVIEW WITH
 RESPECT TO INFORMATION BEING NEEDED FOR MAXIMUM
 LIGHTING POWER DENSITIES. PLEASE SEE 13-415.2, AND
 13-415.2.ABC.1.2 WITH RESPECT TO TRACK LIGHTING. THE
 RESPONSE FROM THE DESIGNER MENTIONS LOADS FOR TRACK
 LIGHTING BASED ON THE NEC MINIMUM LOADS FOR BRANCH
 CIRCUITS AND SERVICE FEEDER LOADS. THIS SECTION OF THE
 FBC AND CHAPTER 13 HAS TO DO WITH THE MAXIMUM ALLOWED
 LIGHTING LEVELS AND WATTS PER SQ FT BASED ON USE OF THE
 SPACE ETC.
 PLEASE SEE THERE IS A MAXIMUM TIME OF 30 MINUTES FOR
 OCCUPANCY TYPE DEVICES PER THE FBC AND SOME OC TYPE
 DEVICES AS NOTED ON LEGEND MENTIONS 2HRS.
 PLEASE SEE THAT THE COORDINATION OF LIGHTING, FIXTURES
 AND LEVELS CAN NOT FULLY BE DONE AT THIS TIME. PLEASE
 SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #8 WITH
 RESPECT TO MINIMUM LEVELS FOR ADA COMPLIANCE. THE
 RESPONSE LETTER MENTIONS LEVELS AT 70DB, HOWEVER NO
 INFORMATION OR LEVELS FOR CANDELA LEVELS COULD BE
 LOCATED.
 PLEASE SEE THE NOTE BELOW FROM PREVIOUS REVIEW*PLEASE
 SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND STATE THE
 MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA REQUIRED
 AREAS. DEVICES ARE BEING SHOWN ON PLANS/LEGEND. PLEASE
 CORRELATE WITH PLANS, AND FA SHEETS SUBMITTED.
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM
 SETS.
 FBC 106.3.5.1.2
  
 4) NOTE:PLEASE SEE PREVIOUS NOTE #10. RESPONSE
 MENTIONS LOAD WAS ADJUSTED HOWEVER PLANS SHOW THE SAME
 INFORMATION AS ON PREVIOUS CALCULATIONS. PLEASE SEE THE
 NEC HANDBOOK AS WATER HEATERS ARE NOW CONSIDERED
 *CONTINUOUS LOADS* WHICH REQUIRES THE 125% FOR LOAD.
 THIS WAS A CHANGE FROM THE PREVIOUS CODE WHICH ONLY
 REQUIRED THE BRANCH CIRCUIT CONDUCTORS AND OVER CURRENT
 PROTECTION TO BE DONE AT 125%.
 PLEASE ALSO INCLUDE THE WATER HEATER LOAD AT 125% FOR
 CONTINUOUS LOAD. PLEASE SEE 422.13 OF THE 2005 NEC.
  
 5) NOTE: PLEASE SEE THE PREVIOUS NOTE #11 REQUESTED
 COORDINATION AND CHANGES FOR CODE COMPLIANCE FOR
 FEEDERS ON RISER AND PANEL SCHEDULES. PLEASE SEE SOME
 OF THESE ITEMS WERE CHANGED AND CORRECT HOWEVER PLEASE
 SEE SOME ITEMS WERE NOT CHANGED.
 PLEASE SEE THE FEEDERS NOTED ON PANEL *H* ARE STILL
 SHOWN AS 3/0 WHEN THE RISER AND NOTES TO RISER INDICATE
 1/0.
 PLEASE SEE COMMENTS BELOW FOR OTHER ITEMS FOR
 COORDINATION.
  
 6) NOTE: PLEASE SEE THE PREVIOUS NOTE #12 WHICH
 REQUESTED FOR THE OVER CURRENT PROTECTION OF THE
 TRANSFORMER AS LISTED ON THE PANEL *H* TO MEET 450.3.
 THE RESPONSE LETTER MENTIONS THIS IS TO BE CHANGED TO
 70AMP HOWEVER PLEASE SEE PANEL *H* AS THIS NOW SHOW A
 3-POLE 20AMP BREAKER WITH #3 CONDUCTORS.
 PLEASE SEE THE RISER SHOWS OTHER CONDUCTOR SIZES.
 PLEASE KNOW THE #3 CONDUCTORS WILL NOT FIT INTO THIS
 SIZE BREAKER.
 PLEASE SEE THIS 20AMP OVER CURRENT PROTECTION DOES NOT
 MEET THE MINIMUM LOADS ON THE TRANSFORMER FROM PANEL
 *L1*.
 240.4, 310.16, 110.3,ETC. THERE ARE SEVERAL CODE
 SECTIONS, TOO MANY TO LIST.
 PLEASE COORDINATE.
  
 7) NOTE: PLEASE SEE THE LOAD FOR THE TRANSFORMER HAS
 NOW BEEN REVISED AND INDICATES A LOAD OF .5 KVA. THIS
 IS NOT POSSIBLE WHEN THE LOAD ON PANEL *L1* IS 42KVA AT
 120/208 VOLTS. THIS LOAD WAS CHANGED FROM PREVIOUS
 PLANS.
 PLEASE SEE THE TOTAL LOAD ON PANEL *H* HAS NOW GONE
 DOWN WITH OUT THIS LOAD OF THE PANEL *L1*.
 PLEASE COORDINATE AND ADJUST ALL OF THESE ITEMS.
 240,220, 408.4, 310.16, 215, ETC.
  
 8) NOTE: PLEASE SEE PREVIOUS NOTE #14. PLEASE CLARIFY
 RATING OF THE PANELS *H* AND *L1*ON RISER AND ON
 SCHEDULE.
 PANEL *L1* IS SHOWN AS A 225AMP RATED PANEL WITH A
 150AMP MCB, YET RISER SHOWS THIS AS 200AMPS? PLEASE SEE
 PANEL *H* IS SHOWN ON SCHEDULE AS 225AMP RATED, WITH
 200AMP RATED MCB. THIS IS OK, HOWEVER THIS IS SHOWN AS
 200AMP ON RISER WITH A 150AMP FEED FROM THE BUS-TAP AND
 DISCONNECT.
 THE ABOVE NEEDS SOME COORDINATION.
 FBC 106.1.2, 106.1.1, 106.3.5.1.2
 FAC 61G15-23.004
  
 9) NOTE: PLEASE SEE PREVIOUS NOTE #16 AS THIS REQUESTED
 COORDINATION OF THE PANEL NUMBER OF POLES LISTED ON
 PANEL AND SHOWN ON CIRCUITS.
 PLEASE SEE PANEL *L1* WAS CORRECTED, HOWEVER PLEASE SEE
 PANEL *H* IS STILL SHOWN AS 30 AND 42 CIRCUIT PANELS.
 (225AMP RATED PANELS ARE MOST LIKELY NOT AVAILABLE AS
 30POLES)
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE PREVIOUS NOTE #17 FOR TRANSFORMER
 GROUNDING. A CONDUCTOR SIZE WAS ADDED HOWEVER NO
 ATTACHMENT LOCATIONS WERE SHOWN OR NOTED.
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE TRANSFORMER GROUNDING ELECTRODE
 SYSTEM PER 250.20, 250.30, 250.66 ETC. PLEASE SHOW
 ATTACHMENT WITH THE SIZE OF THE CONDUCTOR. FBC 106.1.2,
 106.3.5.1.2, FAC 61G15-33.004
  
 11) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
 PLEASE BE SURE TO CALL TO GO OVER COMMENTS.
  
 AS PREVIOUSLY STATED:
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-04 08:28:172007-09-04 08:28:17
 REVIEW IN PROGRESS
2007-08-31 16:09:26IN ELEC,

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-19 Cont ID  
Sent By dpalmer Date 2007-07-19 Time 16:54 Rev Time 0.00
Received By dpalmer Date 2007-07-19 Time 07:07 Sent To  
Notes
2007-07-19 16:54:35 
  
 ****** UNSAT *****
  
  
  
 1) NOTE: PLEASE SEE THAT PLANS HAVE BEEN SUBMITTED FOR
 PERMIT AFTER DECEMBER 8TH, 2006 WHICH PLACES PROJECT
 UNDER THE NEW CODES.
 PLEASE SEE THE FOLLOWING SHALL BE STATED ON THE
 ARCHITECTURAL CS COVER SHEET. PLEASE ALSO BE SURE THE
 TRADES REFLECT THE CODES RELEVANT TO THEIR DESIGNS ON
 RESPECTIVE SHEETS.
 2004 FBC W/ 2006 REVISIONS (ALL TRADES).
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 2003 NFPA-20
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH
 MAY REQUIRE CERTAIN CODES.
  
 2) NOTE: PLEASE SEE MISSING THE REQUIRED INFORMATION ON
 TITLE BLOCKS FOR ARCHITECTURAL FIRM. PLEASE SEE A
 CERTIFICATE OF AUTHORIZATION NUMBER WHICH IS SHOWN ON
 TITLE BLOCKS IS ONLY APPLIED FOR AND IS AN APPLICATION
 IN PROGRESS AS LISTED ON THE STATES WEBSITE AS OF THIS
 REVIEW. PLEASE REVISE TITLE BLOCKS FOR COMPLIANCE WITH
 THE FS 481.0219, FAC 61G1-16.004 OR OBTAIN THE CA # BY
 THE TIME THE NEXT RE-SUBMITTAL OF PLANS IS DONE. **
 THIS COMMENT STANDS FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 3) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULE(S) SUBMITTED. PLEASE
 SEE SOME ARE MISSING CIRCUIT DESIGNATIONS.
 FBC 106.3.5.1.2, 106.1.2, NEC 408.4
  
 4) NOTE: PLEASE SEE NEC 408.4 AS THE CIRCUITS ARE
 REQUIRED TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH
 THEY FEED. PLEASE SEE THE DESIGNATIONS MAY BE NUMERICAL
 TO ROOMS/AREAS.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS EXTRACTED FROM
 THE NEC.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.5.1.2
  
 5) NOTE: PLEASE SEE THE PLANS WILL REQUIRE AN
 ADDRESSING REVIEW. PLEASE SEE THE PERMIT APPLICATION
 DOES NOT INCLUDE ANY SUITE/UNIT NUMBER. ONCE THE
 SUITE/UNIT NUMBER IS DESIGNATED PLEASE REVISE TITLE
 BLOCKS TO INCLUDE THE SUITE/UNIT NUMBER.
 FBC 106.1.2
 FAC 61G1-16.004/61G15-23.002
  
 6) NOTE:
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. P PLEASE
 ALSO SEE 13-415.2
 PLEASE SEE THAT THE TIMES FOR SCHEDULING NEEDS TO BE
 STATED ON PLANS FOR LIGHTING CONTROL PANEL(S). PLEASE
 KNOW EVEN THOUGH THE TIME IS DERIVED FROM THE TENANT
 AND WILL MOST LIKELY CHANGE THE PLANS ARE STILL
 REQUIRED TO CONTAIN A MINIMUM TIMED SCHEDULE. PLEASE
 STATE ALL MAXIMUM TIMES FOR THE DEVICES AS SHOWN ON
 PLANS. PLEASE COORDINATE THE INFORMATION ON THE SYMBOL
 LEGEND. (SOME MAXIMUM TIMES ARE SHOWN BUT NOT FOR ALL
 DEVICES AS SPECIFIED).
 PLEASE SEE AREA(S) WHICH DO NOT CONTAIN DEVICES FOR
 COVERAGE. PLEASE CLARIFY THE PRIVATE BATH/STALL AREA
 WHICH CONTAINS SEPARATION WALL. IS THE DEVICE AS SHOWN
 A COMBINATION DEVICE WHICH PICKS UP ON
 MOTION/SOUND/HEAT?
 PLEASE COMPLETE FIXTURE LEGEND FOR THE TYPES OF
 LUMINARIES, THE NUMBER OF LUMINARIES, ETC. PLEASE SEE
 SOME AREAS OF THE FIXTURE LEGEND WHICH DID NOT PRINT
 CORRECTLY AND SEEMS TO HAVE COMPACTED SOME LINES AND
 DELETED INFORMATION.
 PLEASE SEE THE NUMBER OF LUMINARIES ON PLANS DO NOT
 CORRELATE WITH THE NUMBER OF LUMINARIES ON LEGEND.
 (EXAMPLE PLEASE SEE FIXTURE R1) THE PLANS INDICATE A
 MUCH HIGHER NUMBER OF THESE LUMINARIES THAN THAT
 INDICATED ON LEGEND).
 PLEASE CLARIFY THE LOADS FIGURED FOR THE TRACK LIGHTING
 PER 13-415.2.ABC.1.2
 PLEASE KNOW THAT THERE IS INFORMATION NEEDED FOR SOME
 OF THE ABOVE WHICH AT THIS TIME CAN NOT CONFIRMED FOR
 COMPLIANCE.
  
 7) NOTE: PLEASE CLARIFY WHAT IS BEING SHOWN AS
 *COMPUTER ROOM*. IS THIS AN *IT* ROOM? THIS CAN BE
 CLARIFIED WITH NOTE(S) ON PLANS.
 IF THIS ROOM WILL FALL UNDER THE DEFINITIONS OF AN IT
 ROOM, PLEASE ADJUST PLANS FOR CODE COMPLIACE FOR NEC
 645 AND NFPA-75.
  
 8) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON
 PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA
 SHEETS SUBMITTED.
 ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A
 SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM
 SETS.
 FBC 106.3.5.1.2
  
 9) NOTE: PLEASE SEE 210.63 AND 210.8B FOR MISSING CU
 GFI. IS THIS EXISTING OR NEW?
  
 10) NOTE: PLEASE ALSO INCLUDE THE WATER HEATER LOAD AT
 125% FOR CONTINUOUS LOAD. PLEASE SEE 422.13 OF THE 2005
 NEC.
  
 11) NOTE: PLEASE SEE THE FEEDERS TO TRANSFORMER FROM
 PANEL *H* DO NOT CORRELATE FROM RISER DIAGRAM TO PANEL
 *H* SCHEDULE.
 PLEASE SEE THAT THE FEEDERS ON PANEL H ARE OK, HOWEVER
 THE RISER DO NOT MEET 310.16. PLEASE SEE THE FOLLOWING
 COMMENT #12 AS THE OCP ON THE PANEL WILL BE REQUIRED TO
 CHANGE WHICH WILL AFFECT THE CONDUCTOR SIZES. PLEASE BE
 SURE TO COORDINATE RISER, PANEL AND CONDUCTOR SCHEDULE
 ON THE UPPER RIGHT HAND CORNER.
  
 12) NOTE: PLEASE SEE 450.3 AS THE MAXIMUM OVER CURRENT
 PROTECTION OF THE 45K TRANSFORMER IS TOO HIGH. PLEASE
 SEE THIS IS 125% MAXIMUM UNLESS MEETING THE EXCEPTIONS
 OF THE TABLES AS NOTED.
 PLEASE ADJUST FEEDERS.
  
 13) NOTE: PLEASE SEE THE FEEDERS ON THE SECONDARY SIDE
 OF THE TRANSFORMER DO NOT MEET 240.21, 310.16 AND
 240.4.
 PLEASE SEE THE CONDUCTORS MUST TERMINATE IN OCP WHICH
 LIMITS THE LOAD ON THESE TAPPED CONDUCTORS.
 PLEASE SEE THE 200AMP OCP IN PANEL L1 IS TOO HIGH FOR
 THE #1 CONDUCTORS SHOWN ON RISER.
  
 14) NOTE: PLEASE CORRELATE RISER FOR PANEL H WITH THAT
 OF THE CONDUCTORS SHOWN ON PANEL H SCHEDULE.
 THIS PANEL IS LISTED AS 225A, 200A MCB AND 3/0
 CONDUCTORS WHERE PANEL IS LISTED AS MLO?
 PLEASE SEE THE COMMENTS ABOVE WITH RESPECT TO
 COORDINATION OF CONDUCTORS ETC.
 FBC 106.1.2., FAC 61G15-33.004
 NEC 310.16,240.4
  
 15) NOTE: PLEASE CORRELATE PANEL L1 WITH RISER. PLEASE
 SEE THIS PANEL SCHEDULE AND INFORMATION INDICATES THIS
 AS A 225A PANEL/200AMP MCB. THIS IS ALSO SHOWN AS
 CONTAINING MLO WITH 3/0 CONDUCTORS, YET RISER SHOWS #1
 AWG?
 PLEASE COORDINATE ALL.
 FBC 106.1.2, FAC 61G15-33.004
 NEC 310.16, 240.4
  
 16) NOTE: PLEASE SEE BOTH PANELS H AND L1 INDICATE
 30POLES ON SCHEDULE HOWEVER THEY ARE CIRCUITED TO 42
 POLES?
 PLEASE COORDINATE.
 FBC 106.1.2.
  
 17) NOTE: PLEASE INDICATE THE TRANSFORMER GROUNDING
 ELECTRODE SYSTEM PER 250.20, 250.30, 250.66 ETC. PLEASE
 SHOW ATTACHMENT WITH THE SIZE OF THE CONDUCTOR. FBC
 106.1.2, 106.3.5.1.2, FAC 61G15-33.004
  
 18) NOTE: PLEASE CLARIFY THE AIC RATINGS FOR BREAKERS
 IN PANELS. THESE ARE BEING NOTED AS 22K FOR ALL
 BREAKERS IN PANELS INCLUDING BRANCH CIRCUITS. THIS IS
 OK AND CODE COMPLIANT, HOWEVER THE NOTE ON PANEL ALSO
 STATES SERIES RATING.
 PLEASE CLARIFY
 FBC 106.1.2.
  
 19) NOTE: PLEASE PROVIDE INFORMATION FOR THE ACCESS
 CONTROL LOCKS. PLEASE SEE 7.2.1.5.1, 7.2.1.6.2 OF THE
 2003 LIFE SAFETY CODE AS THESE DEVICES SHALL NOT
 INTERFERE OR IMPEDE EGRESS.
 PLEASE PROVIDE FAIL SAFE INFORMATION.
 PLEASE SEE FIRE REVIEW COMMENTS AS THIS COMMENT MAY BE
 EXPANDED UPON. PLEASE VERIFY ANY ADDITIONAL INFORMATION
 ONCE THE FIRE MARSHAL HAS REVIEWED SAID PLANS.
  
 ** PLEASE SEE AS THERE ARE SEVERAL CHANGES WHICH NEED
 TO BE MADE TO PLANS/RISER, THERE MAY VERY WELL BE
 COMMENTS BASED ON CHANGES.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-19 07:07:52IN ELEC FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-09-25 Cont ID  
Sent By mawillia Date 2007-09-25 Time 12:55 Rev Time 0.00
Received By mawillia Date 2007-09-25 Time 12:32 Sent To  
Notes
2007-09-25 12:55:02*****APPROVED*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS A13.1, E2.0, AAND FP-1
 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-09-06 Cont ID  
Sent By mwennerg Date 2007-09-06 Time 14:14 Rev Time 0.00
Received By mwennerg Date 2007-09-06 Time 14:13 Sent To  
Notes
2007-09-06 14:19:39***DENIED***
  
 1) IT APPEARS THAT ALL COMMENTS FROM FIRST REVIEW HAVE
 BEEN ADDRESSED. PLEASE SEE OTHER REVIEW COMMENTS
 REGARDING FAC 61G15-23.002 REQUIREMENTS. ALL SHEETS
 SIGNED BY PROFESSIONAL ENGINEERS INCLUDING FIRE
 PROTECTION TO CONTAIN RAISED SEAL.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-30 Cont ID  
Sent By mwennerg Date 2007-07-30 Time 10:10 Rev Time 0.00
Received By mwennerg Date 2007-07-30 Time 10:10 Sent To  
Notes
2007-07-30 10:25:41***DENIED***
  
 1) DOOR SCHEDULE INDICATES A "C" RATING FOR
 ELECTRICAL/MECHANICAL DOOR. PLEASE PROVIDE RATING IN
 TERMS OF MINUTES.
  
 2) PLEASE INDICATE UL LISTED CLOSER FOR APPROPRIATE
 DOOR.
  
 3) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
 5) PLEASE INDICATE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS IN TERMS OF CLASS
 A,B ORC.
  
 6) WORK SHALL NOT INTERFERE WITH EXISTING BUILDING FIRE
 PROTECTION EQUIPMENT AND REQUIRED MEANS OF EGRESS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-01-03 Cont ID  
Sent By adarroug Date 2008-01-03 Time 15:58 Rev Time 0.00
Received By adarroug Date 2008-01-03 Time 15:58 Sent To E
Notes
2008-01-03 15:59:03TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-12-14 Cont ID  
Sent By adarroug Date 2007-12-14 Time 09:32 Rev Time 0.00
Received By tgordon Date 2007-12-14 Time 09:32 Sent To B
Notes
2007-12-14 09:33:16TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-15 Cont ID  
Sent By adarroug Date 2007-11-15 Time 09:19 Rev Time 0.00
Received By adarroug Date 2007-11-15 Time 09:19 Sent To M
Notes
2007-11-15 09:19:27TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-14 Cont ID  
Sent By adarroug Date 2007-09-14 Time 13:26 Rev Time 0.00
Received By adarroug Date 2007-09-14 Time 13:26 Sent To  
Notes
2007-09-20 09:01:45TO "BOB"#8
2007-09-14 13:26:49WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-16 Cont ID  
Sent By adarroug Date 2007-08-16 Time 09:36 Rev Time 0.00
Received By adarroug Date 2007-08-16 Time 09:36 Sent To  
Notes
2007-08-31 10:46:01TO "BOB"#1
2007-08-16 09:36:20WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-31 Cont ID  
Sent By jleech Date 2007-07-31 Time 10:22 Rev Time 0.00
Received By jleech Date 2007-07-17 Time 14:32 Sent To  
Notes
2007-07-17 14:32:23TO "BOB"#13

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-12-20 Cont ID  
Sent By tgordon Date 2007-12-20 Time 09:56 Rev Time 0.30
Received By tgordon Date 2007-12-20 Time 09:56 Sent To  
Notes
2007-12-20 09:58:22REVISION TO MECH. PLANS PAGES M-1, M-2.1, M-2.2, AND
 M-3.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-11-16 Cont ID  
Sent By tgordon Date 2007-11-16 Time 11:24 Rev Time 0.45
Received By tgordon Date 2007-11-16 Time 11:24 Sent To  
Notes
2007-11-16 12:13:04PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
 1) PLANS ON FILE PAGE A-7.2 SHOWS THE WALLS TO THE
 TEL/SERVER ROOM ARE ONE HOUR FIRE RATED. THE TWO 14"
 FLEX DUCTS MAY NOT PENETRATE A RATED WALL, SHOW
 COMPLIANCE WITH 2004 FBC/M 607.5. ALSO FOR THE 8'
 EXHAUST DUCT (ON PAGE M-2.1).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-09-21 Cont ID  
Sent By tgordon Date 2007-09-21 Time 08:15 Rev Time 0.30
Received By tgordon Date 2007-09-21 Time 08:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-09-06 Cont ID  
Sent By tgordon Date 2007-09-06 Time 11:08 Rev Time 0.30
Received By tgordon Date 2007-09-06 Time 11:08 Sent To  
Notes
2007-09-06 11:13:50PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) MECHANICAL PLANS ARE MISSING THE ENGINEER'S RAISED
 SEAL, SEE FAC 61G15-23.002.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-20 Cont ID  
Sent By tgordon Date 2007-07-20 Time 10:41 Rev Time 0.45
Received By tgordon Date 2007-07-20 Time 10:40 Sent To  
Notes
2007-07-20 11:36:53*** DENIED ***
 1) PLEASE ADJUST NOTE ON MECHANICAL PLANS "CEILING
 CAVITY IS A RETURN AIR PLENUM NO P.V.C. ALLOWED" TO
 INCLUDE NO COMBUSTIBLES TO COMPLY WITH 2004 FCC/M
 602.2.1.
  
 2) PLAN M-2 SHOWS A BATHROOM EXHAUST DUCT IN THE RETURN
 AIR PLENUM, PER 2004 FBC/M 601.3 EXHAUST DUCTS UNDER
 POSITIVE PRESSURE SHELL NOT PASS THROUGH PLENUMS.
 PLEASE CORRECT.
  
 3) IF AN EXHAUST DUCT NOT UNDER PRESSURE IS TO BE USED
 SHOW HOW THE OPENING WILL BE PROTECTED AT THE RATED
 WALL, SEE 2004 FBC/M 607.
  
 4) BATHROOM EXHAUST FAN EF-1 IS RATED AT 50 CFM'S. SEE
 2004 FBC/M TABLE 403.3 SHOWS TOILET ROOMS AT 50 CFM'S
 AND SHOWER AT 50 CFM'S. PLEASE ADJUST.
  
 5) PLAN M-3 SHOWS A DETAIL FOR A CONDENSER UNIT WALL
 BRACKET. PLEASE SUBMIT ENGINEERING FOR BRACKET AND SHOW
 THAT IT WILL WITHSTAND 140 MPH WINDS TO COMPLY WITH
 2004 FBC 1609. IF PRE-ENGINEERED PLEASE SUBMIT PRODUCT
 APPROVAL, PER FAC RULE 9B-72.
  
 6) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK ON
 MECHANICAL PLANS, PER 2004 FBC CITY WPB AMEND.
 106.1.3.
  
 7) SEE ELECTRICAL REVIEW NOTES #1 AND #2, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-09-25 Cont ID  
Sent By jleech Date 2007-09-25 Time 13:31 Rev Time 0.00
Received By jleech Date 2007-09-25 Time 13:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-09-10 Cont ID  
Sent By jleech Date 2007-09-10 Time 09:26 Rev Time 0.00
Received By jleech Date 2007-09-10 Time 09:26 Sent To  
Notes
2007-09-10 09:28:22DENIED;
  
 PLUMBING PLANS ARE NOT SEALED BY ENGINEER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-31 Cont ID  
Sent By jleech Date 2007-07-31 Time 09:56 Rev Time 0.00
Received By jleech Date 2007-07-31 Time 09:18 Sent To  
Notes
2007-07-31 10:20:37DENIED;
 1. SEE ELECTRICAL PLAN REVIEW'S NOTE # 2.
 2. GENERAL PLUMBING NOTE # 16, SHOW UL LISTING FOR FIRE
 ASSEMBY TO BE USED AND THE MANUFACTURE OF PRODUCT.
 3. SANITARY RISER AND FLAT DRAWING NOT TO CODE;
 A) BREAK SINK NOT PERMITED TO GO THRU A
 BATHROOM GROUP. SECTION 909.1
 B) SHOWER IS NOT VENTED.
 4. SHOW TYPE OF THERMAL EXPANSION TO BE USED FOR THE
 HOT WATER. SECTION 607.3.
 5. THE PRIVATE BATHROOM DOES NOT COMPLY WITH, FBC-2004
 BUILDING CHAPTER 11 SECTION 11-4.1.3(11) I.E. " A
 PRIVATE TOILET ROOM FOR THEOCCUPENT OF A PRIVATE
 OFFICE". THIS BATHROOM SHALL BE ADAPTABLE WITH ALL
 BACKING REQUIRED AND TOILET AT 18" OFF SIDE WALL.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-07-20 Cont ID  
Sent By choops Date 2007-07-20 Time 16:24 Rev Time 0.00
Received By choops Date 2007-07-20 Time 16:24 Sent To  
Notes
2007-07-20 16:25:04*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.