Plan Review Stops For Permit 07070304 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2007-07-11 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2007-07-11 |
Time |
12:25 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2007-07-11 |
Time |
12:25 |
Sent To |
M |
|
Notes |
2007-07-11 13:20:14 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.)SHOW LOCATION OF THE EXHAUST AND STATE WHICH ZONE | | IT IS LOCATED IN SO THAT DESIGN PRESSURES CAN BE | | DETERMINED, FBC TABLE 1609.6.2.2. | | | | 2.)PROVIDE THE FIRST SHEETS OF THE NOA WHICH LIST THE | | ASSEMBLY COMPONENTS.ONLY APPROVED ASSEMBLIES WHICH | | YOU ARE NOT USING SHOULD BE REMOVED FROM THE NOA. | | | | 3.)PROVIDE LEGIBLE DOCUMENTS. | | | | 4.)PROVIDE INFORMATION IN REGARDS TO THE OCCUPANCY | | FBC CHAPTER 3 AND VENTILATION REQUIREMENTS. | | |
|
|
|