2007-07-30 10:26:32 | |
| *** UNSAT *** |
| |
| *** PLANS NOW SUBMITTED UNDER A NEW PERMIT APPLICATION |
| FOR VOID PERMIT 06010504 |
| |
| 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE SPECIFIC CHANGES IN THE 2005 NEC |
| WHICH REQUIRES ITEMS ON PLANS TO BE REVISED ALONG WITH |
| OTHER CODE REQUIRED CHANGES. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| 2) NOTE: PLEASE SEE THE BUILDING IS STILL BEING |
| SUBMITTED UNDER ONE PERMIT. AS STATED ON PERVIOUS |
| REVIEW, IF THESE ARE FEE SIMPLE *TOWN HOMES* BY |
| DEFINITION OF THE FBC, THEN SEE BUILDING REVIEW |
| COMMENTS AS THESE ARE EACH UNDER A SEPARATE PCN AS |
| STATED ON LETTER FROM PBC AND WILL REQUIRE PERMIT |
| APPLICATIONS AND PLANS FOR EACH AS THESE ARE EACH A |
| SEPARATE LEGAL PROPERTY ETC. |
| PLEASE ALSO SEE THE PLANS STILL CALL FOR THIS AS A |
| *MULTI-FAMILY* BUILDING WHICH DOES NOT COORDINATE WITH |
| PLANS, STATEMENTS, PERMIT APPLICATION ETC. |
| PLEASE ALSO SEE THAT IF THESE ARE SEPARATE |
| *BUILDINGS*/TOWN HOUSES,* PLEASE SEE DEFINITIONS OF |
| BUILDING IN THE FBC AND REQUIREMENTS FOR TYPE OF WALL |
| CONSTRUCTION AND SEPARATION. THIS IS TO BE CONFIRMED |
| WITH THE BUILDING REVIEWER AS THE REQUIRED *FIRE WALL* |
| DOES NOT SEEM TO BE SHOWN ON PLANS. THE FIRE WALL |
| REQUIRES COLLAPSE OF THE STRUCTURE ON EITHER SIDE |
| WITHOUT AFFECTING THE STRUCTURAL INTEGRITY OF THE |
| OTHER. |
| BASED ON PLANS SUBMITTED AND SINGLE PERMIT APPLICATION, |
| THIS IS A *MULTI-FAMILY* BUILDING AND ONLY ONE |
| ELECTRICAL SERVICE WILL BE GRANTED PER 230.2. PLEASE BE |
| SURE TO GROUP ALL MAINS PER 230.72 INTO ONE SERVICE. |
| 230.70, 230.71, 250.66, 240.4, 310.16 ETC. PLEASE |
| REVISE RISER WITH ALL NEW REQUIREMENTS FOR CONDUCTORS, |
| GROUNDING ETC. |
| PLEASE KNOW THAT A COMPLETE REVIEW OF THIS RISER CAN |
| NOT BE DONE AT THIS TIME AS PLANS SHOW THIS A SINGLE |
| SERVICE FOR EACH. |
| |
| 3) NOTE: PLEASE SEE PLANS SHOW *SD* FOR SMOKE |
| DETECTORS, YET THESE ARE SHOWN AS 120V W/ BATTERY BACK |
| UP. IF THESE ARE INDEED SMOKE DETECTORS, PLEASE SEE |
| THAT THESE WOULD NOT BE AS SHOWN. PLEASE INCLUDE |
| SOUNDING DEVICES ON PLANS. PLEASE SEE NFPA-72 |
| DEFINITIONS AS THESE MOST LIKELY ARE *SA* SMOKE ALARMS. |
| BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| SHOWN) AND WOULD DETECT AND SOUND AN ALARM. |
| PLEASE SEE THAT THE PLANS ALSO INDICATE UP TO FOUR |
| CIRCUITS FOR THESE DEVICES. AS THEY ARE REQUIRED TO BE |
| WIRED *IN-LINE* THIS WOULD NOT BE POSSIBLE WITH |
| MULTIPLE CIRCUITS AS SHOWN. |
| PLEASE ADJUST CIRCUITING. |
| PLEASE SEE SOME ARE MISSING CIRCUITS. |
| PLEASE COMPLETE AND COORDINATE. |
| ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE*. |
| PLEASE SEE NFPA-72 11.5.1.1, 11.8.3 |
| |
| |
| 4) NOTE: PLEASE SUBMIT A REVISED PANEL SCHEDULE TO |
| SPECIFICALLY INDICATE ALL CIRCUITS ON PANEL SCHEDULE |
| WHICH CORRELATES WITH PLANS/ROOMS/AREA LAYOUTS. PLEASE |
| SEE 408.4 AND THE FOLLOWING TEXT BELOW WHICH IS FROM |
| THE NEC. |
| |
| *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| SECTION.* |
| 408.4, 310.16, 240.4 ETC |
| FBC 106.3.5.4 |
| |
| 5) NOTE: PLEASE SEE 210.4B AS THE DISHWASHER AND |
| DISPOSAL IS SHOWN TO THE SAME DEVICE YET ARE SHOWN ON |
| SINGLE POLE BREAKERS. |
| PLEASE REVISE AS THESE ARE REQUIRED TO BE FROM ONE |
| 2-POLE BREAKER. |
| |
| 6) NOTE: PLEASE SEE 422.13 AS THE LOAD FOR THE WATER |
| HEATER NEEDS TO BE SHOWN AT 125%. THIS IS NEW UNDER THE |
| 2005 NEC. PREVIOUS CODE REQUIRED 125% FOR BRANCH |
| CIRCUIT, CODE NOW REQUIRES LOAD AT 125% ALSO AS A |
| CONTINUOUS LOAD. |
| |
| 7) NOTE: PLEASE SEE THE VALUE AS APPLIED SEEMS LOW AND |
| WILL BE REVIEWED PER THE TABLES ADOPTED INTO THE FBC |
| 108.3. |
| |
| ** PLEASE KNOW AS THERE ARE ITEMS WHICH HAVE NOT YET |
| BEEN SUBMITTED FOR REVIEW, NEW COMMENTS MAY BE FOUND ON |
| THE NEXT REVIEW. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2007-07-27 16:49:54 | IN ELEC FOR REVIEW. |