Plan Review Details - Permit 07070235
Plan Review Stops For Permit 07070235
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-29 Cont ID  
Sent By amorse Date 2007-11-29 Time 16:51 Rev Time 0.00
Received By amorse Date 2007-11-29 Time 16:51 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-13 Cont ID  
Sent By amorse Date 2007-10-13 Time 07:44 Rev Time 0.00
Received By amorse Date 2007-10-13 Time 07:44 Sent To PC
Notes
2007-10-13 07:46:16 
  
 DENIED
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM 1ST
 REVIEW:
  
 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $ 158.88FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 6)A TITLE BLOCK WITH THE INFORMATION SPECIFIED PER
 61G1-16.004 FAC SHALL BE PRESENT ON DRAWINGS ISSUED BY
 THE RESPONSIBLE ARCHITECT AND MUST,
 AT A MINIMUM CONTAIN
 1) FIRM NAME,ADDRESS, AND TELEPHONE #
 2) FIRM LICENSE #
 3) NAME OF PROJECT
 4) DATE PREPARED
 5) A SPACE FOR SIGNATURE & DATED SEAL
 6) A SPACE FOR PRINTED NAME OF PERSON
 SEALING THE DOCUMENT
  
 7)A CERTIFICATE OF AUTHORIZATION SHALL BE REQUIRED
 FOR A CORPORATION, LIMITED LIABILITY COMPANY, OR
 PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES TO THE
 PUBLIC JOINTLY OR SEPARATELY.
 PER 481.219(2) F.S.
  
 *******THE TITLE BLOCK REQUIRES THE PRINTED NAME OF THE
 PERSON SEALING THE PLANS (RODNEY N GREEN) NOT REGINALD
 HARRIS AS INDICATED, ALSO RNGA ARCHITECTURE INC. IS A
 BUSINESS AND AS SUCH THE LICENCE # OF THE ARCHITECT
 BUSINESS SHALL BE PRESENT ON THE TITLE BLOCK. PLEASE
 NOTE THAT THSEE ARE THE REQUIREMENTS OF 61G1-16.004 OF
 THE FLORIDA ADMINISTRATIVE CODE AND SHALL BE ON ALL
 DRAWINGS SUBMITTED BY THIS FIRM******
  
 21)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 NEW COMMENT
  
 1)PLEASE CORRECT THE SITE DRAWING TO REFLECT THE
 SETBACKS AS STATED ON THE LEGAL SURVEY
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2007-07-28 Time   Rev Time 0.00
Received By amorse Date 2007-07-28 Time 07:44 Sent To PC
Notes
2007-07-28 14:34:13 
  
 DENIED
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 4)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $ 158.88FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 5)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE
 PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR
 SETBACKS
  
 6)A TITLE BLOCK WITH THE INFORMATION SPECIFIED PER
 61G1-16.004 FAC SHALL BE PRESENT ON DRAWINGS ISSUED BY
 THE RESPONSIBLE ARCHITECT AND MUST,
 AT A MINIMUM CONTAIN
 1) FIRM NAME,ADDRESS, AND TELEPHONE #
 2) FIRM LICENSE #
 3) NAME OF PROJECT
 4) DATE PREPARED
 5) A SPACE FOR SIGNATURE & DATED SEAL
 6) A SPACE FOR PRINTED NAME OF PERSON
 SEALING THE DOCUMENT
  
 7)A CERTIFICATE OF AUTHORIZATION SHALL BE REQUIRED
 FOR A CORPORATION, LIMITED LIABILITY COMPANY, OR
 PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES TO THE
 PUBLIC JOINTLY OR SEPARATELY.
 PER 481.219(2) F.S.
  
 8)IN AREAS OF QUESTIONABLE SOILS AS SHOWN IN THE
 OFFICIAL ZONING MAP OF THE CITY OF WEST PALM BEACH, 2
 COPIES OF A SOIL TEST REPORT SHALL BE SUBMITTED PER
 R401.4 FBC RES.
  
 9)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
 (SEE ROOF TILES)
  
 10)GENERAL CONTRACTOR CANNOT INSTALL CONCRETE TILE
 ROOFING UNDER THE SCOPE OF HIS LICENSE, REMOVE FROM
 PERMIT APPLICATION AND HAVE ROOFING CONTRACTOR APPLY
 FOR PERMIT
  
 11)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS
 REQUIRED PER R807.1 FBC RES.
  
 12)PROVIDE DETAIL (WOOD FRAME, BLOCK) ON PONY WALL AT
 NEW FRONT ENTRY ALCOVE WHERE EXISTING 8'-0" WALL WILL
 BE RAISED TO 12'-0" AND THE ATTACHMENT METHOD
  
 13)PROVIDE MIN ROOF SHEATHING ATTACHMENT PER
 R803.2.3.1 FBC RES. NOTE THAT ONLY 8D OR BETTER "RING
 SHANK" NAIL MAY BE USED
  
 14)TRUSS ENGINEERING HAS NO WIND DESIGN DATA ON THE
 SIGNED AND SEALED INDEX SHEET AND THE LAYOUT DRAWING
 HAS THIS INFORMATION BUT IS NOT SIGNED AND SEALED
  
 15)PHOTO COPIED, STAMPED OR REPRODUCED SIGNATURES ARE
 NOT ACCEPTABLE PER 471.025 F.S. TRUSS INDEX SHEET MUST
 HAVE TRUE SIGNATURE
  
 16)TRUSS DESIGN LOADS AND DESIGN LOADS ON THE
 DRAWINGS DO NOT MATCH (SEE DL AND LL FOR TOP CORD) MAY
 BE DUE TO CHANGE FROM SHINGLE ROOFING TO CONCRETE TILE
  
 17)PROVIDE COMPLETE ANCHOR/TIE DOWN SCHEDULE THAT
 INCLUDES THE STATEWIDE PRODUCT APPROVAL # OR THE
 SIMPSON TIE INDEX SHEET WITH THE CHOSEN ANCHORS MARKED
 (THIS WOULD BE PREFERABLE TO PRODUCT APPROVALS FOR ALL
 STRAPS & TIES THAT WILL BE USED)
  
 18)PER 106.1.3 FBC* THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR
 PLANS AND SPECIFICATIONS "NO WHITE OUT, PENCIL OR INK"
 ON DRAWINGS
  
 19)PROVIDE CORRECT MIAMI-DADE NOA FOR THE SERIES
 FD-750 FRENCH DOORS THAT THE FLORIDA STATEWIDE PRODUCT
 APPROVAL USES FOR VALIDATION (07-0103.02) PRODUCT
 APPROVALS WERE SUBMITTED FOR SERIES FD-101 FRENCH DOORS
 ALSO ARE BOTH BEING USED IF SO SPECIFY WHERE EACH ARE
 USED ON THE DRAWING
  
 20)PROVIDE A PRODUCT APPROVAL FOR THE FRONT ENTRY
 PANEL DOORS
  
 21)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-11-08 Cont ID  
Sent By btrobaug Date 2007-11-08 Time 07:37 Rev Time 0.00
Received By btrobaug Date 2007-11-08 Time 06:49 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-09-24 Cont ID  
Sent By btrobaug Date 2007-09-24 Time 13:35 Rev Time 0.00
Received By btrobaug Date 2007-09-24 Time 12:15 Sent To M
Notes
2007-09-24 13:35:30 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING
 CODE, 2005 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC
 AS
 AMENDED, CHAPTER 1, AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 THESE COMMENTS ARE FROM THE PREVIOUS REVIEW7/17/07.
  
 4} THERE ARE TWO PANELS SHOWN ON THE RISER DIAGRAM,
 ONLY ONE SHOWN IN THE GARAGE, PLEASE LOCATE ALL
 EQUIPMENT ON THE PLAN. *THE METER AND DISCONNECT ARE
 NOT SHOWN ON THIS RESUBMITTAL EITHER. 106.1.1 FBC.
  
 8} THE DINING ROOM RECEPTACLES MUST COMPLY WITH
 210.52(B)(1), NOTE FOR PANEL SCHEDULE.* THEE PANEL
 SCHEDULE HAS A 15 AMP BREAKER, MUST BE A 20 AMP CIRCUIT
 TO COMPLY.
  
 9} THE AIR HANDLER LOCATED IN THE CLOSET IS IN
 VIOLATION OF 240.24(D) FOR OVERCURRENT PROTECTION. ALSO
 THERE IS A 120 VOLT RECEPTACLE SHOWN AS A DISCONNECT. *
 NOW THE ?CLOSET? IS RENAMED ?STORAGE?, SEE 422.17 TO
 DETERMINE IF THIS UNIT NEEDS TO BE WALLED OFF FROM
 ITEMS INTENDED TO BE STORED IN THIS ROOM.
  
 THESE ARE NEW COMMENTS FOR THIS REVIEW GENERATED BY THE
 PANEL SCHEDULE BEING ADDED TO THE PLAN.
  
 1} SEE COMMENT #8 ABOVE.
  
 2} THERE IS ONLY ONE SMALL APPLIANCE CIRCUIT IN THE
 PANEL SCHEDULE, PER 210.11(C)(1), A MINIMUM OF TWO ARE
 REQUIRED.
  
 3} BATHROOM CIRCUITS ARE REQUIRED TO BE 20 AMP PER
 210.11(C)(3) ONLY THE MASTER BATH IS LISTED IN THE
 SCHEDULE, AND IT HAS A 15 AMP BREAKER.
  
 4} THE NOTE FOR PANEL ?A? ON THE RISER DIAGRAM READS
 ?MAIN METER?, CLARIFY IF THIS IS A METER MAIN
 COMBINATION PIECE OF SERVICE EQUIPMENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-17 Cont ID  
Sent By btrobaug Date 2007-07-17 Time 14:05 Rev Time 0.00
Received By btrobaug Date 2007-07-17 Time 12:22 Sent To M
Notes
2007-07-17 13:53:59 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG
 WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 2} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL
 SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO
 BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5
 NEC 2005. SEE 220.80 2005 NEC. SEE SMALL APPLIANCE AN
 AHU.
  
 3} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE.
  
 4} THERE ARE TWO PANELS SHOWN ON THE RISER DIAGRAM,
 ONLY ONE SHOWN IN THE GARAGE, PLEASE LOCATE ALL
 EQUIPMENT ON THE PLAN.
  
 5} PROVIDE PANEL SCHEDULES PER 408.4, NEC,CIRCUIT
 DIRECTORY OR CIRCUIT IDENTIFICATION
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS.
  
 6} THE KITCHEN PENINSULAR RECEPTACLE SPACING MUST
 COMPLY WITH 210.52(C)(3).
  
 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1),
 SEE PROPOSED FAMILY ROOM.
  
 8} THE DINING ROOM RECEPTACLES MUST COMPLY WITH
 210.52(B)(1), NOTE FOR PANEL SCHEDULE.
  
 9} THE AIR HANDLER LOCATED IN THE CLOSET IS IN
 VIOLATION OF 240.24(D) FOR OVERCURRENT PROTECTION. ALSO
 THERE IS A 120 VOLT RECEPTACLE SHOWN AS A DISCONNECT.
  
 NOTE: IF METAL STUDS ARE USED THEY MUST COMPLY WITH
 2704.1, 2004 FBC: METAL FRAMING MEMBERS SHALL BE BONDED
 TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT
 THAT MAY ENERGIZE THE FRAMING. PLEASE SEE ARTICLE.AND
 NOTE ON PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-02 Cont ID  
Sent By adarroug Date 2007-11-02 Time 11:50 Rev Time 0.00
Received By adarroug Date 2007-11-02 Time 11:50 Sent To Z
Notes
2007-11-02 11:50:58TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-17 Cont ID  
Sent By adarroug Date 2007-09-17 Time 16:33 Rev Time 0.00
Received By adarroug Date 2007-09-17 Time 16:33 Sent To Z
Notes
2007-09-17 16:33:47TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-09-17 Cont ID  
Sent By adarroug Date 2007-07-28 Time 16:33 Rev Time 0.00
Received By adarroug Date 2007-07-11 Time 11:31 Sent To  
Notes
2007-07-11 11:32:01TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-11-08 Cont ID  
Sent By tgordon Date 2007-11-08 Time 12:00 Rev Time 0.25
Received By tgordon Date 2007-11-08 Time 12:00 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-09-24 Cont ID  
Sent By tgordon Date 2007-09-24 Time 15:28 Rev Time 0.45
Received By tgordon Date 2007-09-24 Time 15:28 Sent To P
Notes
2007-09-24 15:37:52PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 7-17-07 #1. BUILDING PLANS
 TITLE BLOCK NEEDS TO ALSO SHOW THE PRINTED NAME OF THE
 PERSON WHO SEALED THEM (RODNEY N. GREEN), SEE FAC
 61G1-16.004.
  
 2) AS NOTED IN LAST REVIEW 7-17-07 #1. BUILDING PLANS
 TITLE BLOCK NEEDS TO ALSO SHOW RNGA ARCHITECTURE INC.
 FIRM LICENSE NUMBER (AA26000717), SEE FAC 61G1-16.004.
  
 3) AS NOTED IN LAST REVIEW 7-17-07 #4. THE MECHANICAL
 PLANS NEED TO SHOW THE AN EXHAUST FAN IN THE MASTER
 BATHROOM SHOWER AND TUB AREA, SEE FBC/R R303.3.
  
 5) AS NOTED IN LAST REVIEW 7-17-07 #7. THE MECHANICAL
 PLANS NEED THE PRINTED NAME OF THE PERSON RESPONSIBLE
 FOR THE DESIGN ON THEM ALSO, SEE W.P.B. AMEND.
 106.1.3.
  
 6) SEE YELLOW HIGH LIGHTS ON MECHANICAL PLANS SHOWING
 MISSING DUCT WORK (FLEX), PLEASE CORRECT.
  
 7)SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING
 FOUR TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-17 Cont ID  
Sent By tgordon Date 2007-07-17 Time 16:14 Rev Time 0.45
Received By tgordon Date 2007-07-17 Time 16:14 Sent To P
Notes
2007-07-17 16:49:48*** DENIED ***
 1) SEE BUILDING PLANS, INFORMATION MISSING IN TITLE
 BLOCK (FIRM LIC. NO., FIRM PHONE NO., PERSON SEALED
 PLANS PRINTED NAME) FOR ARCHITECT SEE FAC 61G1-16.004
 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS"
 SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 2) ENERGY CALCULATIONS LINE 15 IS TAKING CREDIT FOR
 CEILING FANS. CEILING FANS ARE NOT IN THE TWO EXISTING
 BEDROOMS, FAMILY ROOM, OR THE LIVING ROOM. PER 2004 FBC
 13-607.2.A.3.1 CEILING FAN CREDIT MAY BE TAKEN IF ONE
 OR MORE CEILING FANS ARE INSTALLED IN EACH OF THE
 BEDROOMS AND A MINIMUM OF ONE CEILING FAN IS INSTALLED
 IN ALL PRIMARY LIVING AREAS (LIVING ROOMS, FAMILY
 ROOMS, OR GREAT ROOMS). PLEASE CORRECT.
  
 3) THE BATHROOM BETWEEN THE TWO EXISTING BEDROOMS WILL
 NEED AN EXHAUST FAN, SEE 2004 FBC/R R303.3.
  
 4) THE MASTER BATHROOM SHOWER AREA WILL NEED AN EXHAUST
 FAN, SEE 2004 FBC/R R303.3.
  
 5) SHOW CLOTHES DRYER VENT AND ALL BATHROOM EXHAUST
 FANS ON MECHANICAL PLANS.
  
 6) BUILDING AND ELECTRICAL PLANS SHOW THE AIR HANDLER
 IN A CLOSET BUT THE MECHANICAL PLANS SHOW THE AIR
 HANDLER IN THE GARAGE, THE TWO MUST COINCIDE PLEASE
 CORRECT.
  
 7) ALL INFORMATION, DRAWINGS (MECHANICAL PLANS),
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-11-19 Cont ID  
Sent By jleech Date 2007-11-19 Time 14:10 Rev Time 0.00
Received By jleech Date 2007-11-19 Time 14:10 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-10-12 Cont ID  
Sent By jleech Date 2007-10-12 Time 09:01 Rev Time 0.00
Received By jleech Date 2007-10-12 Time 08:41 Sent To B
Notes
2007-10-12 09:03:46DENIED;
 SEE MECHANICAL PLAN REVIEW NOTES 1 AND 2.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By jleech Date 2007-07-26 Time 08:46 Rev Time 0.00
Received By jleech Date 2007-07-26 Time 08:35 Sent To  
Notes
2007-07-26 08:54:46DENIED;
 1. SEE ELECTRICAL PLAN REVIEW NOTE # 1.
 2. DEMO PAGE ADD NOTE NO DEAD ENDS PERMITED IN THE
 DRAINAGE SYSTEM, INSPECTION REQUIRED.
 3. RISER DIAGRAM; MASTER BATHROOM, REQUIRED VENT SHOULD
 BE AT LAVATORY. (SEE ONE SET OF PLANS MARKED IN RED)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2007-11-07 Cont ID  
Sent By choops Date 2007-11-07 Time 15:24 Rev Time 0.00
Received By choops Date 2007-11-07 Time 15:23 Sent To E
Notes
2007-11-07 15:28:29***APPROVED - RESUB #2***
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 2 Status F Date 2007-09-19 Cont ID  
Sent By choops Date 2007-09-19 Time 13:50 Rev Time 0.00
Received By choops Date 2007-09-19 Time 13:50 Sent To E
Notes
2007-09-19 13:52:55***FAILED - RESUB #1***
  
 REPEAT COMMENTS:
  
 1)SOME DIMENSIONS DO NOT MATCH BETWEEN SITE PLAN AND
 SURVEY.PLEASE CLARIFY.
  
 2)PLEASE SHOW ANY PROPOSED OR RELOCATED A/C
 EQUIPMENT WITH SETBACK DIMENSIONS TO THE PROPERTY
 LINES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720
  

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-12 Cont ID  
Sent By choops Date 2007-07-12 Time 11:16 Rev Time 0.00
Received By choops Date 2007-07-12 Time 11:16 Sent To E
Notes
2007-07-12 11:22:53***FAILED***
  
  
 1)PLEASE PROVIDE AND UPDATED SURVEY (WITHIN THE LAST
 YEAR) THAT ACCURATELY REFLECTS THE SITE AS IT IS.SOME
 DIMENSIONS DON'T CORRESPONDE FROM SURVEY PROVIDED TO
 SITE PLAN.
  
 2)INDICATE A/C EQUIPMENT ON SURVEYS WITH SETBACK
 DIMENSIONS TO THE PROPERTY LINES.
  
 3)PROVIDE OVERHANG DIMENSIONS IN SECTION DETAILS
 FROM THE WALL TO THE OUTERMOST POINT OF THE ROOF.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved