Plan Review Stops For Permit 07070235 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-11-29 |
|
|
Cont ID |
|
Sent By |
amorse |
Date |
2007-11-29 |
Time |
16:51 |
Rev Time |
0.00 |
Received By |
amorse |
Date |
2007-11-29 |
Time |
16:51 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2007-10-13 |
|
|
Cont ID |
|
Sent By |
amorse |
Date |
2007-10-13 |
Time |
07:44 |
Rev Time |
0.00 |
Received By |
amorse |
Date |
2007-10-13 |
Time |
07:44 |
Sent To |
PC |
|
Notes |
2007-10-13 07:46:16 | | | | | DENIED | | | | THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM 1ST | | REVIEW: | | | | 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING | | MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF | | ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND | | STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE | | DRAWINGS | | | | NOTE: FEES ARE DUE IN THE AMOUNT OF $ 158.88FOR | | INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS | | REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW | | | | 6)A TITLE BLOCK WITH THE INFORMATION SPECIFIED PER | | 61G1-16.004 FAC SHALL BE PRESENT ON DRAWINGS ISSUED BY | | THE RESPONSIBLE ARCHITECT AND MUST, | | AT A MINIMUM CONTAIN | | 1) FIRM NAME,ADDRESS, AND TELEPHONE # | | 2) FIRM LICENSE # | | 3) NAME OF PROJECT | | 4) DATE PREPARED | | 5) A SPACE FOR SIGNATURE & DATED SEAL | | 6) A SPACE FOR PRINTED NAME OF PERSON | | SEALING THE DOCUMENT | | | | 7)A CERTIFICATE OF AUTHORIZATION SHALL BE REQUIRED | | FOR A CORPORATION, LIMITED LIABILITY COMPANY, OR | | PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES TO THE | | PUBLIC JOINTLY OR SEPARATELY. | | PER 481.219(2) F.S. | | | | *******THE TITLE BLOCK REQUIRES THE PRINTED NAME OF THE | | PERSON SEALING THE PLANS (RODNEY N GREEN) NOT REGINALD | | HARRIS AS INDICATED, ALSO RNGA ARCHITECTURE INC. IS A | | BUSINESS AND AS SUCH THE LICENCE # OF THE ARCHITECT | | BUSINESS SHALL BE PRESENT ON THE TITLE BLOCK. PLEASE | | NOTE THAT THSEE ARE THE REQUIREMENTS OF 61G1-16.004 OF | | THE FLORIDA ADMINISTRATIVE CODE AND SHALL BE ON ALL | | DRAWINGS SUBMITTED BY THIS FIRM****** | | | | 21)A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT IS REQUIRED PRIOR TO | | A PERMIT BEING ISSUED | | | | NEW COMMENT | | | | 1)PLEASE CORRECT THE SITE DRAWING TO REFLECT THE | | SETBACKS AS STATED ON THE LEGAL SURVEY | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2007-07-28 |
Time |
|
Rev Time |
0.00 |
Received By |
amorse |
Date |
2007-07-28 |
Time |
07:44 |
Sent To |
PC |
|
Notes |
2007-07-28 14:34:13 | | | | | DENIED | | | | 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL | | COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 | | AMENDMENTS PER 106.1.1 FBC* | | | | 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING | | MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF | | ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND | | STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE | | DRAWINGS | | | | 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS | | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS | | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST | | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC | | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES | | PER 108.3 FBC* | | | | 4)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON | | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER | | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE | | ADDED TO THE PERMIT APPLICATION FEES | | | | NOTE: FEES ARE DUE IN THE AMOUNT OF $ 158.88FOR | | INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS | | REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW | | | | 5)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE | | PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR | | SETBACKS | | | | 6)A TITLE BLOCK WITH THE INFORMATION SPECIFIED PER | | 61G1-16.004 FAC SHALL BE PRESENT ON DRAWINGS ISSUED BY | | THE RESPONSIBLE ARCHITECT AND MUST, | | AT A MINIMUM CONTAIN | | 1) FIRM NAME,ADDRESS, AND TELEPHONE # | | 2) FIRM LICENSE # | | 3) NAME OF PROJECT | | 4) DATE PREPARED | | 5) A SPACE FOR SIGNATURE & DATED SEAL | | 6) A SPACE FOR PRINTED NAME OF PERSON | | SEALING THE DOCUMENT | | | | 7)A CERTIFICATE OF AUTHORIZATION SHALL BE REQUIRED | | FOR A CORPORATION, LIMITED LIABILITY COMPANY, OR | | PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES TO THE | | PUBLIC JOINTLY OR SEPARATELY. | | PER 481.219(2) F.S. | | | | 8)IN AREAS OF QUESTIONABLE SOILS AS SHOWN IN THE | | OFFICIAL ZONING MAP OF THE CITY OF WEST PALM BEACH, 2 | | COPIES OF A SOIL TEST REPORT SHALL BE SUBMITTED PER | | R401.4 FBC RES. | | | | 9)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE | | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND | | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO | | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* | | (SEE ROOF TILES) | | | | 10)GENERAL CONTRACTOR CANNOT INSTALL CONCRETE TILE | | ROOFING UNDER THE SCOPE OF HIS LICENSE, REMOVE FROM | | PERMIT APPLICATION AND HAVE ROOFING CONTRACTOR APPLY | | FOR PERMIT | | | | 11)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS | | REQUIRED PER R807.1 FBC RES. | | | | 12)PROVIDE DETAIL (WOOD FRAME, BLOCK) ON PONY WALL AT | | NEW FRONT ENTRY ALCOVE WHERE EXISTING 8'-0" WALL WILL | | BE RAISED TO 12'-0" AND THE ATTACHMENT METHOD | | | | 13)PROVIDE MIN ROOF SHEATHING ATTACHMENT PER | | R803.2.3.1 FBC RES. NOTE THAT ONLY 8D OR BETTER "RING | | SHANK" NAIL MAY BE USED | | | | 14)TRUSS ENGINEERING HAS NO WIND DESIGN DATA ON THE | | SIGNED AND SEALED INDEX SHEET AND THE LAYOUT DRAWING | | HAS THIS INFORMATION BUT IS NOT SIGNED AND SEALED | | | | 15)PHOTO COPIED, STAMPED OR REPRODUCED SIGNATURES ARE | | NOT ACCEPTABLE PER 471.025 F.S. TRUSS INDEX SHEET MUST | | HAVE TRUE SIGNATURE | | | | 16)TRUSS DESIGN LOADS AND DESIGN LOADS ON THE | | DRAWINGS DO NOT MATCH (SEE DL AND LL FOR TOP CORD) MAY | | BE DUE TO CHANGE FROM SHINGLE ROOFING TO CONCRETE TILE | | | | 17)PROVIDE COMPLETE ANCHOR/TIE DOWN SCHEDULE THAT | | INCLUDES THE STATEWIDE PRODUCT APPROVAL # OR THE | | SIMPSON TIE INDEX SHEET WITH THE CHOSEN ANCHORS MARKED | | (THIS WOULD BE PREFERABLE TO PRODUCT APPROVALS FOR ALL | | STRAPS & TIES THAT WILL BE USED) | | | | 18)PER 106.1.3 FBC* THE BUILDING OFFICIAL MAY | | ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR | | PLANS AND SPECIFICATIONS "NO WHITE OUT, PENCIL OR INK" | | ON DRAWINGS | | | | 19)PROVIDE CORRECT MIAMI-DADE NOA FOR THE SERIES | | FD-750 FRENCH DOORS THAT THE FLORIDA STATEWIDE PRODUCT | | APPROVAL USES FOR VALIDATION (07-0103.02) PRODUCT | | APPROVALS WERE SUBMITTED FOR SERIES FD-101 FRENCH DOORS | | ALSO ARE BOTH BEING USED IF SO SPECIFY WHERE EACH ARE | | USED ON THE DRAWING | | | | 20)PROVIDE A PRODUCT APPROVAL FOR THE FRONT ENTRY | | PANEL DOORS | | | | 21)A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT IS REQUIRED PRIOR TO | | A PERMIT BEING ISSUED | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2007-11-08 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-11-08 |
Time |
07:37 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-11-08 |
Time |
06:49 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-09-24 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-09-24 |
Time |
13:35 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-09-24 |
Time |
12:15 |
Sent To |
M |
|
Notes |
2007-09-24 13:35:30 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING | | CODE, 2005 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC | | AS | | AMENDED, CHAPTER 1, AND FOUND NONCOMPLIANT WITH THE | | FOLLOWING: | | | | THESE COMMENTS ARE FROM THE PREVIOUS REVIEW7/17/07. | | | | 4} THERE ARE TWO PANELS SHOWN ON THE RISER DIAGRAM, | | ONLY ONE SHOWN IN THE GARAGE, PLEASE LOCATE ALL | | EQUIPMENT ON THE PLAN. *THE METER AND DISCONNECT ARE | | NOT SHOWN ON THIS RESUBMITTAL EITHER. 106.1.1 FBC. | | | | 8} THE DINING ROOM RECEPTACLES MUST COMPLY WITH | | 210.52(B)(1), NOTE FOR PANEL SCHEDULE.* THEE PANEL | | SCHEDULE HAS A 15 AMP BREAKER, MUST BE A 20 AMP CIRCUIT | | TO COMPLY. | | | | 9} THE AIR HANDLER LOCATED IN THE CLOSET IS IN | | VIOLATION OF 240.24(D) FOR OVERCURRENT PROTECTION. ALSO | | THERE IS A 120 VOLT RECEPTACLE SHOWN AS A DISCONNECT. * | | NOW THE ?CLOSET? IS RENAMED ?STORAGE?, SEE 422.17 TO | | DETERMINE IF THIS UNIT NEEDS TO BE WALLED OFF FROM | | ITEMS INTENDED TO BE STORED IN THIS ROOM. | | | | THESE ARE NEW COMMENTS FOR THIS REVIEW GENERATED BY THE | | PANEL SCHEDULE BEING ADDED TO THE PLAN. | | | | 1} SEE COMMENT #8 ABOVE. | | | | 2} THERE IS ONLY ONE SMALL APPLIANCE CIRCUIT IN THE | | PANEL SCHEDULE, PER 210.11(C)(1), A MINIMUM OF TWO ARE | | REQUIRED. | | | | 3} BATHROOM CIRCUITS ARE REQUIRED TO BE 20 AMP PER | | 210.11(C)(3) ONLY THE MASTER BATH IS LISTED IN THE | | SCHEDULE, AND IT HAS A 15 AMP BREAKER. | | | | 4} THE NOTE FOR PANEL ?A? ON THE RISER DIAGRAM READS | | ?MAIN METER?, CLARIFY IF THIS IS A METER MAIN | | COMBINATION PIECE OF SERVICE EQUIPMENT. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2007-07-17 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-07-17 |
Time |
14:05 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-07-17 |
Time |
12:22 |
Sent To |
M |
|
Notes |
2007-07-17 13:53:59 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL | | INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG | | WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA | | ADMINISTRATIVE CODE. | | | | 2} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL | | SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO | | BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5 | | NEC 2005. SEE 220.80 2005 NEC. SEE SMALL APPLIANCE AN | | AHU. | | | | 3} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE | | EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS | | PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT | | TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS | | CHANGE. | | | | 4} THERE ARE TWO PANELS SHOWN ON THE RISER DIAGRAM, | | ONLY ONE SHOWN IN THE GARAGE, PLEASE LOCATE ALL | | EQUIPMENT ON THE PLAN. | | | | 5} PROVIDE PANEL SCHEDULES PER 408.4, NEC,CIRCUIT | | DIRECTORY OR CIRCUIT IDENTIFICATION | | EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY | | IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC | | PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE | | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE | | DISTINGUISHED FROM ALL OTHERS. | | | | 6} THE KITCHEN PENINSULAR RECEPTACLE SPACING MUST | | COMPLY WITH 210.52(C)(3). | | | | 7} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1), | | SEE PROPOSED FAMILY ROOM. | | | | 8} THE DINING ROOM RECEPTACLES MUST COMPLY WITH | | 210.52(B)(1), NOTE FOR PANEL SCHEDULE. | | | | 9} THE AIR HANDLER LOCATED IN THE CLOSET IS IN | | VIOLATION OF 240.24(D) FOR OVERCURRENT PROTECTION. ALSO | | THERE IS A 120 VOLT RECEPTACLE SHOWN AS A DISCONNECT. | | | | NOTE: IF METAL STUDS ARE USED THEY MUST COMPLY WITH | | 2704.1, 2004 FBC: METAL FRAMING MEMBERS SHALL BE BONDED | | TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT | | THAT MAY ENERGIZE THE FRAMING. PLEASE SEE ARTICLE.AND | | NOTE ON PLAN. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-11-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-02 |
Time |
11:50 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-02 |
Time |
11:50 |
Sent To |
Z |
|
Notes |
2007-11-02 11:50:58 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-09-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-09-17 |
Time |
16:33 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-09-17 |
Time |
16:33 |
Sent To |
Z |
|
Notes |
2007-09-17 16:33:47 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-09-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-07-28 |
Time |
16:33 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-07-11 |
Time |
11:31 |
Sent To |
|
|
Notes |
2007-07-11 11:32:01 | TO "Z" BOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2007-11-08 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-11-08 |
Time |
12:00 |
Rev Time |
0.25 |
Received By |
tgordon |
Date |
2007-11-08 |
Time |
12:00 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2007-09-24 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-09-24 |
Time |
15:28 |
Rev Time |
0.45 |
Received By |
tgordon |
Date |
2007-09-24 |
Time |
15:28 |
Sent To |
P |
|
Notes |
2007-09-24 15:37:52 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) AS NOTED IN LAST REVIEW 7-17-07 #1. BUILDING PLANS | | TITLE BLOCK NEEDS TO ALSO SHOW THE PRINTED NAME OF THE | | PERSON WHO SEALED THEM (RODNEY N. GREEN), SEE FAC | | 61G1-16.004. | | | | 2) AS NOTED IN LAST REVIEW 7-17-07 #1. BUILDING PLANS | | TITLE BLOCK NEEDS TO ALSO SHOW RNGA ARCHITECTURE INC. | | FIRM LICENSE NUMBER (AA26000717), SEE FAC 61G1-16.004. | | | | 3) AS NOTED IN LAST REVIEW 7-17-07 #4. THE MECHANICAL | | PLANS NEED TO SHOW THE AN EXHAUST FAN IN THE MASTER | | BATHROOM SHOWER AND TUB AREA, SEE FBC/R R303.3. | | | | 5) AS NOTED IN LAST REVIEW 7-17-07 #7. THE MECHANICAL | | PLANS NEED THE PRINTED NAME OF THE PERSON RESPONSIBLE | | FOR THE DESIGN ON THEM ALSO, SEE W.P.B. AMEND. | | 106.1.3. | | | | 6) SEE YELLOW HIGH LIGHTS ON MECHANICAL PLANS SHOWING | | MISSING DUCT WORK (FLEX), PLEASE CORRECT. | | | | 7)SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING | | FOUR TIMES THE FEE. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2007-07-17 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-07-17 |
Time |
16:14 |
Rev Time |
0.45 |
Received By |
tgordon |
Date |
2007-07-17 |
Time |
16:14 |
Sent To |
P |
|
Notes |
2007-07-17 16:49:48 | *** DENIED *** | | 1) SEE BUILDING PLANS, INFORMATION MISSING IN TITLE | | BLOCK (FIRM LIC. NO., FIRM PHONE NO., PERSON SEALED | | PLANS PRINTED NAME) FOR ARCHITECT SEE FAC 61G1-16.004 | | TITLE BLOCK. | | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR | | INTERIOR DESIGN DRAWINGS AND SPECIFICATION | | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A | | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | (2) FIRM LICENSE NUMBER. | | (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS" | | SEE CITY WPB AMEND. 106.1.1). | | (4) DATE PREPARED. | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | THE DOCUMENT. | | | | 2) ENERGY CALCULATIONS LINE 15 IS TAKING CREDIT FOR | | CEILING FANS. CEILING FANS ARE NOT IN THE TWO EXISTING | | BEDROOMS, FAMILY ROOM, OR THE LIVING ROOM. PER 2004 FBC | | 13-607.2.A.3.1 CEILING FAN CREDIT MAY BE TAKEN IF ONE | | OR MORE CEILING FANS ARE INSTALLED IN EACH OF THE | | BEDROOMS AND A MINIMUM OF ONE CEILING FAN IS INSTALLED | | IN ALL PRIMARY LIVING AREAS (LIVING ROOMS, FAMILY | | ROOMS, OR GREAT ROOMS). PLEASE CORRECT. | | | | 3) THE BATHROOM BETWEEN THE TWO EXISTING BEDROOMS WILL | | NEED AN EXHAUST FAN, SEE 2004 FBC/R R303.3. | | | | 4) THE MASTER BATHROOM SHOWER AREA WILL NEED AN EXHAUST | | FAN, SEE 2004 FBC/R R303.3. | | | | 5) SHOW CLOTHES DRYER VENT AND ALL BATHROOM EXHAUST | | FANS ON MECHANICAL PLANS. | | | | 6) BUILDING AND ELECTRICAL PLANS SHOW THE AIR HANDLER | | IN A CLOSET BUT THE MECHANICAL PLANS SHOW THE AIR | | HANDLER IN THE GARAGE, THE TWO MUST COINCIDE PLEASE | | CORRECT. | | | | 7) ALL INFORMATION, DRAWINGS (MECHANICAL PLANS), | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | PRINTED NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER | | FBC 104.2.1 . | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2007-11-19 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-11-19 |
Time |
14:10 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-11-19 |
Time |
14:10 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2007-10-12 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-10-12 |
Time |
09:01 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-10-12 |
Time |
08:41 |
Sent To |
B |
|
Notes |
2007-10-12 09:03:46 | DENIED; | | SEE MECHANICAL PLAN REVIEW NOTES 1 AND 2. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2007-07-26 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2007-07-26 |
Time |
08:46 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2007-07-26 |
Time |
08:35 |
Sent To |
|
|
Notes |
2007-07-26 08:54:46 | DENIED; | | 1. SEE ELECTRICAL PLAN REVIEW NOTE # 1. | | 2. DEMO PAGE ADD NOTE NO DEAD ENDS PERMITED IN THE | | DRAINAGE SYSTEM, INSPECTION REQUIRED. | | 3. RISER DIAGRAM; MASTER BATHROOM, REQUIRED VENT SHOULD | | BE AT LAVATORY. (SEE ONE SET OF PLANS MARKED IN RED) | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2007-11-07 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-11-07 |
Time |
15:24 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-11-07 |
Time |
15:23 |
Sent To |
E |
|
Notes |
2007-11-07 15:28:29 | ***APPROVED - RESUB #2*** | | | | | | SENT TO "E" - BT |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2007-09-19 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-09-19 |
Time |
13:50 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-09-19 |
Time |
13:50 |
Sent To |
E |
|
Notes |
2007-09-19 13:52:55 | ***FAILED - RESUB #1*** | | | | REPEAT COMMENTS: | | | | 1)SOME DIMENSIONS DO NOT MATCH BETWEEN SITE PLAN AND | | SURVEY.PLEASE CLARIFY. | | | | 2)PLEASE SHOW ANY PROPOSED OR RELOCATED A/C | | EQUIPMENT WITH SETBACK DIMENSIONS TO THE PROPERTY | | LINES. | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | TECHNICIAN | | (561)805-6720 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2007-07-12 |
|
|
Cont ID |
|
Sent By |
choops |
Date |
2007-07-12 |
Time |
11:16 |
Rev Time |
0.00 |
Received By |
choops |
Date |
2007-07-12 |
Time |
11:16 |
Sent To |
E |
|
Notes |
2007-07-12 11:22:53 | ***FAILED*** | | | | | | 1)PLEASE PROVIDE AND UPDATED SURVEY (WITHIN THE LAST | | YEAR) THAT ACCURATELY REFLECTS THE SITE AS IT IS.SOME | | DIMENSIONS DON'T CORRESPONDE FROM SURVEY PROVIDED TO | | SITE PLAN. | | | | 2)INDICATE A/C EQUIPMENT ON SURVEYS WITH SETBACK | | DIMENSIONS TO THE PROPERTY LINES. | | | | 3)PROVIDE OVERHANG DIMENSIONS IN SECTION DETAILS | | FROM THE WALL TO THE OUTERMOST POINT OF THE ROOF. | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING | | TECHNICIAN | | (561)805-6720 |
|
|