Plan Review Details - Permit 07070220
Plan Review Stops For Permit 07070220
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-11-28 Cont ID  
Sent By jwitmer Date 2007-11-28 Time 09:36 Rev Time 2.22
Received By jwitmer Date 2007-11-28 Time 09:36 Sent To PC
Notes
2007-11-28 09:56:42 
 FOUNDATION PERMIT
 PERMIT# 07070220
 ADDRESS: 500 BANYAN BLVD
 CONT: CATALFUMO
 TELL # (561) 307-4746
  
 STRUCTURAL REVISION# 1 FOR FOUNDATION PERMIT: BUILDING
 PROVISOS:
  
 1) SAME REQUEST AS ZONING, PLEASE PROVIDE THE LOCATION
 OF THE PROPERTY LINE FOR THE SOUTH END OF THE BUILDING.
 THE ISSUED SET OF FOUNDATION PLANS (A0.0) CLEARLY
 INDICATES THE NORTH END OF THE BUILDING HAS 8'-2" TO
 THE PROPERTTY LINE BUT THE SOUTH PORTION OF THE
 BUILDING IS NOT INDICATED ON THE PLAN.
  
 2)PLEASE HAVE THE SOILS ENGINEER CONFIRM THAT THESE
 CHANGES IN THE FOUNDATION WILL NOT CREATE A
 DIFFERENTIAL IN THE SETTLEMENT OF THE BUILDING CREATING
 CRACKS IN THE BUILDING.
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT THE
 NECESSARY INVESTIGATION BE MADE. SUCH INVESTIGATION
 SHALL COMPLY WITH THE PROVISIONS OF SECTIONS 1802.4
 THROUGH 1802.6 .
  
 3) 105.13. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT OR ENLARGE A
 BUILDING HAS BEEN FILED, & PENDING ISSURANCE OF SUCH
 PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR THE FOUNDATION
 ONLY, UPON WRITTEN REQUEST OF THE OWNER AND CONTRACTOR.
 THE HOLDER OF SUCH A SPECIAL PERMIT IS PROCEEDING AT
 HIS OR HER OWN RISK AND WITHOUT ASSURANCE THAT A PERMIT
 FOR THE REMAINDER OF THE WORK WILL BE GRANTED AND THAT
 CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO MEET THE
 PROVISIONS OF THE TECHNICAL CODE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-09-28 Cont ID  
Sent By jwitmer Date 2007-09-28 Time 08:52 Rev Time 0.55
Received By jwitmer Date 2007-09-28 Time 08:52 Sent To PC
Notes
2007-09-28 08:54:01VIBROFLOTATION SHOP DRAWINGS AND SUBMITTALS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-09-12 Cont ID  
Sent By jwitmer Date 2007-09-12 Time 09:42 Rev Time 1.55
Received By jwitmer Date 2007-09-12 Time 09:42 Sent To B
Notes
2007-09-12 09:57:31 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 07070220
 ADDRESS: 500 BANYAN BLVD
 CONT: CATALFUMO
 TELL # (561) 307-4746
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET OFPLANS.106.1.1
 ADMINISTRATIVE CODE/ 06.
  
 1) BUILDING PROVISO: 105.13. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT OR ENLARGE A
 BUILDING HAS BEEN FILED, & PENDING ISSURANCE OF SUCH
 PERMIT, THE
 BUILDING OFFICIAL MAY, AT HIS/ HER DISCRETION, ISSUE A
 SPECIAL PERMIT FOR THE FOUNDATION ONLY, UPON WRITTEN
 REQUEST OF THE OWNER AND CONTRACTOR. THE
 HOLDER OF SUCH A SPECIAL PERMIT IS PROCEEDING AT HIS OR
 HER OWN RISK AND WITHOUT ASSURANCE THAT A PERMIT FOR
 THE
 REMAINDER OF THE WORK WILL BE GRANTED AND THAT
 CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO MEET THE
 PROVISIONS
 OF THE TECHNICAL CODE.
  
 2 ) BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERFORMED IN A MANNER SO AS NOT
 TO ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF DUST, NOISE, WATER
 OR DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORIC SURFACE WATER DRAINAGE FLOWS
 SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE SPECIAL DRAINAGE
 DESIGN COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE
 THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCEL SHALL AS A PERMIT CONDITION, PROVIDE
 A
 PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATION FROM A LICENSED ENGINEER
 SHALL BE SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 3) BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED FROM THE
 CONSTRUCTION SITE OR SECURED IN SUCH A MANNER AS TO
 MINIMIZE THE DANGER OF SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS CAUSING DAMAGE TO PERSONS OR
 PROPERTY FROM HIGH WINDS. ANY PERSONS WHO FAILS TO
 COMPLY TO REMOVE OR SECURE THE CONSTRUCTION MATERIALS
 EQUIPMENT AND DEBRIS WITHIN 24 HRS AFTER A HURRICANE
 WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00. IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE SUBJECT
 TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-23 Cont ID  
Sent By jwitmer Date 2007-08-23 Time 15:03 Rev Time 2.22
Received By jwitmer Date 2007-08-23 Time 15:03 Sent To PC
Notes
2007-08-23 15:04:43BUILDING PLAN REVIEW
 PERMIT: 07070220
 ADD: 500 BANYAN BLVD
 CONT: CATALFUMO
 TEL: (561)307-4746
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) SEMI- COMPLIED, THIS COMMENT DEALS WITH THE SPECIAL
 INSPECTOR AGREEMENT PAGE 5 IS TO BE SIGNED BY THE
 CONTRACTOR AND DESIGNER OF RECORD. BOTH OF THESE
 SIGNATURES ARE MISSING AND NOTARY SEAL. 109.3.6
 THRESHOLD BUILDINGS / CITY PROCEDURES.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-31 Cont ID  
Sent By jwitmer Date 2007-07-31 Time 11:33 Rev Time 4.44
Received By jwitmer Date 2007-07-31 Time 11:33 Sent To  
Notes
2007-07-31 14:11:39BUILDING PLAN REVIEW
 PERMIT: 07070220
 ADD: 500 BANYAN BLVD
 CONT: CATALFUMO
 TEL: (561)307-4746
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) )OF THE UTILTY SIGN OFF WE ARE MISSING THE WATER
 DEPARTMENT OR UTILITIES ENGINEERING DEPARTMENT. SHEET
 C-9 DOES INDICATE A 14' ALLEYWAY BETWEEN LOT1 AND LOT
 10, A COPY OF THE UNITY OF TITLE IS IN HAND. PLEASE
 UPDATE SHOWING THE ABANDOMENT OF THE ALLEYWAY AND THEN
 THE SIGN OFF FROM ENGINEERING AND UTILITIES. SHEET
 S1-1.0INDICATES THERE WILL BE AN FPL DUCTBANK BENEATH
 THE BUILDING EAST TO WEST PLEASE PROVIDE THE RECORDED
 UTILITY EASEMENT FOR THIS AREA AS WELL AS FOR THE FPL
 VAULT.
  
 3) SHEETLS0.0PLEASE CORRECT THE ADDRESS TO 500
 BANYAN.
  
 4) NOTE CORRECT FOR BUILDING PLAN LS0.0 FPL VAULT 3HR
 WALL PLANS INDICATE 90 MINUTE DOORS PLEASE SEE TABLE
 715.3 3HR WALLS/ 3 HR OPENING PROTECTIVES.
  
 5)S1-1.0 INDICATES THE USE OF 16" AUGER PILE WHERE AS
 THE SOILS REPORTS DO NOT REFLECT USING SUCH A SYSTEM.
 PLEASE PROVIDE THE GEOENGINEERS CALCULATIONS FOR DEPTH
 OF PILE.
  
 6) SOILS REPORTS SUBMITTED ARE COPIES NOT ORIGINAL
 SIGNED AND SEALED DOCUMENTS. NOTE THIS WILL BE A
 THRESHOLD BUILDING REQUIRING THREE DOCUMENTS TO BE
 SUBMITTED.
  
 7) WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY S. 553.79(5) FLORIDA STATUTES
 TO THE MINIMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561) 805-6711 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 8) S2-4.0 VS DUCT BANK WHICH SYSTEM WILL BE INSTALLED
 FIRST,DUCT BANK, VIBROFLOTATION OR THE FOUNDATION SEE
 DETAIL# 8.IF THE DUCT BANK IS PLACED AFTER THE FOOTERS
 THE SOILS NATURAL REPOSE WILLUNDERMINE THE
 FOUNDATION.
  
 9)105.13. SPECIAL FOUNDATION PERMIT.WHEN APPLICATION
 FOR A PERMIT TO ERECT OR ENLARGE A BUILDING HAS BEEN
 FILED, & PENDING ISSURANCE OF SUCH PERMIT, THE BUILDING
 OFFICIAL MAY, AT HIS/ HER DISCRETION, ISSUE A SPECIAL
 PERMIT FOR THE FOUNDATION ONLY, UPON WRITTEN REQUEST OF
 THE OWNER AND CONTRACTOR. THE HOLDER OF SUCH A SPECIAL
 PERMIT IS PROCEEDING AT HIS OR HER OWN RISK AND WITHOUT
 ASSURANCE THAT A PERMIT FOR THE
 REMAINDER OF THE WORK WILL BE GRANTED AND THAT
 CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO MEET THE
 PROVISIONS OF THE TECHNICAL CODE.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-09-10 Cont ID  
Sent By dpalmer Date 2007-09-10 Time 12:44 Rev Time 0.00
Received By dpalmer Date 2007-09-10 Time 12:44 Sent To B
Notes
2007-09-10 12:47:51*** REDLINED***
  
 ** PERMIT APPLICATION WAS NOT RESUBMITTED WITH PLANS.
 SPOKE TO FRANK FROM CATALFUMO, WILL BRING IN NEW
 APPLICATION.
  
  
 1) ELECTRICAL SHEET SUBMITTED FOR UNDERGROUND GROUNDING
 ELECTRODE SYSTEM ONLY.
  
 2) REDLINED ADDRESS ON ELECTRICAL SHEETS TITLE BLOCKS
 AS SHEETS DO NOT CONTAIN ADDRESS AS REQUIRED.
  
 3) CIVIL AND S-SHEETS ARE FOR FPL DUCT BANK AND THEIR
 REQUIREMENTS WHICH ARE NOT BASED ON ANY NEC
 REQUIREMENTS. (NOT REVIEW FOR MIN CODE).
  
 4) THE UNDERGROUND CONDUITS FOR BUILDING'S ELECTRICAL
 SERVICE AND OTHER ELECTRICAL EQUIPMENT WHICH IS PART OF
 THE MAIN STRUCURE IS NOT PART OF THESE PLANS OR
 PERMIT.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-23 Cont ID  
Sent By dpalmer Date 2007-08-23 Time 14:59 Rev Time 0.00
Received By dpalmer Date 2007-08-23 Time 14:48 Sent To  
Notes
2007-08-23 14:59:51*** DENIED ***
  
  
 1) NOTE:PLEASE PROVIDE MINIMUM GROUNDING ELECTRODE
 SYSTEM DETAIL FOR ELECTRICAL SERVICE OF STRUCTURE AS
 REQUIRED PER 250.50 OF THE 2005 NEC/NFPA-70.
 ** PLEASE SEE STRUCTURAL STEEL BONDING AS REQUIRED PER
 SECTION NOTED ABOVE.
  
 2) NOTE: PLEASE PROVIDE DETAIL FOR ANY AND ALL
 UNDERGROUND CONDUITS BEING INSTALLED FOR DUCT BANKS TO
 AND FROM FPL VAULT BEING INSTALLED.
 PLEASE INDICATE THE SIZE OF THE CONDUITS, THE NUMBER OF
 THE CONDUITS AND A PRELIMINARY CONDUCTOR
 SCHEDULE/REFERENCE TO THE SIZE OF THE SERVICE BEING
 INSTALLED.
 THERE IS A UNDERGROUND CONDUIT DUCT BANK SHOWN ON THE
 *S* SHEET(S) WHICH DOES NOT INDICATE IF THIS IS FPL,
 ETC.
 FBC 106.1.2
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-11-20 Cont ID  
Sent By adarroug Date 2007-11-20 Time 16:47 Rev Time 0.00
Received By adarroug Date 2007-11-20 Time 16:47 Sent To Z
Notes
2007-11-20 16:47:19TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-09-19 Cont ID  
Sent By adarroug Date 2007-09-19 Time 15:37 Rev Time 0.00
Received By adarroug Date 2007-09-19 Time 15:37 Sent To B
Notes
2007-09-19 15:38:08TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-10 Cont ID  
Sent By adarroug Date 2007-09-10 Time 11:10 Rev Time 0.00
Received By adarroug Date 2007-09-10 Time 11:10 Sent To  
Notes
2007-09-10 11:10:22TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-22 Cont ID  
Sent By adarroug Date 2007-08-22 Time 16:08 Rev Time 0.00
Received By adarroug Date 2007-08-22 Time 16:08 Sent To B
Notes
2007-08-22 16:09:14TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-28 Cont ID  
Sent By adarroug Date 2007-07-28 Time 12:32 Rev Time 0.00
Received By adarroug Date 2007-07-28 Time 12:32 Sent To B
Notes
2007-07-28 12:33:12TO "JWITMER" DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-31 Cont ID  
Sent By jwitmer Date 2007-07-31 Time 14:28 Rev Time 0.00
Received By jwitmer Date 2007-07-13 Time 09:31 Sent To  
Notes
2007-07-13 09:32:21TO "Z" BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2007-11-21 Cont ID  
Sent By mflis Date 2007-11-21 Time 08:57 Rev Time 0.00
Received By mflis Date 2007-11-21 Time 08:57 Sent To B
Notes
2007-11-21 09:00:42ZONING REVIEW: PASSED WITH PROVISO
  
 1) N0 ARCHITECTURAL SITE PLAN INCLUDED; ALL FUTURE
 SUBMITTALS SHALL INCLUDE SITE PLAN OR SURVEY, AND SHALL
 INDICATE LOCATION OF BUILDING IN REGARDS TO THE
 PROPERTY LINES.
  
 2) REVISIONS DO NOT INDICATE ANY MOVEMENT/RELOCATION OF
 BUILDING IN RELATIONSHIP TO PROPERTY LINES; PLEASE
 CONFIRM THAT THIS IS CORRECT.
  
 3) EASEMENTS SHALL BE REQUIRED FOR ANY FOOTERS/CAPS
 LOCATED WITHIN ALLEY AND ALONG CLEMATIS STREET, BELOW
 GRADE.
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status P Date 2007-07-13 Cont ID  
Sent By mflis Date 2007-07-13 Time 14:29 Rev Time 0.00
Received By mflis Date 2007-07-13 Time 14:29 Sent To  
Notes
2007-07-13 14:31:55ZONING REVIEW: PASSED
  
 * REVIEW FOR FOUNDATION ONLY
  
 * SURVEY SHALL BE CORRECTED TO REFLECT ACTUAL PROPERTY
 LIMITS, INCLUDING ABANDONED ALLEY
  
 ROUTED TO C.HOOPS
  
 MATT FLIS - 822-1445