Plan Review Details - Permit 07070214
Plan Review Stops For Permit 07070214
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-09-13 Cont ID  
Sent By shill Date 2007-09-13 Time 17:36 Rev Time 0.00
Received By shill Date 2007-09-13 Time 17:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-08-31 Cont ID  
Sent By shill Date 2007-08-31 Time 14:56 Rev Time 0.00
Received By shill Date 2007-08-31 Time 14:56 Sent To  
Notes
2007-08-31 14:57:36****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
  
 COMMENTS FROM PREVIOUS LIST:
  
 1.ADDRESSED.
  
 2.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2), FBC
 R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE C
 HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC
 R301.2.1.4.
  
 PROVIDE DIMENSIONS ON THE FLOOR PLAN, DISTANCE FROM
 CORNER TO EDGE OF WINDOW, FOR OPENINGS NEAR THE CORNER.
 NUMBER THE OPENINGS TO CORRELATE WITH THE INSTALLATION
 SCHEDULE.THE OPENING 48X49, IF IN ZONE 5, HAS A
 DESIGN PRESSURE REQUIREMENT OF -57.11.
  
 3.SEE SHEET14A; A FACTOR OF .5 REQURED FOR ANCHOR
 SPACING WITH EDGE DISTANCE OF 2".
  
 2ND REVIEW; THIS WAS ADDRESSED BY CHANGING THE EDGE
 DISTANCE TO 3".THIS REQUIRES A FACTOR OF .86.
  
 3RD REVIEW; IT APPEARS THAT YOU ARE READING THE
 COMMENTS FROM REVIEW #1.PLEASE SEE ABOVE AND REVIEW
 #2.
  
 NEW COMMENT:
  
 4.)SHUTTER CONNECTION MOUNTING TYPE SHOULD BE A
 THROUGH L, NOT TAPCON.PLEASE REVISE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-20 Cont ID  
Sent By shill Date 2007-08-20 Time 16:54 Rev Time 0.00
Received By shill Date 2007-08-20 Time 16:54 Sent To  
Notes
2007-08-20 16:59:29****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
  
 COMMENTS FROM PREVIOUS LIST:
  
 1.ADDRESSED.
  
 2.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2), FBC
 R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE C
 HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC
 R301.2.1.4.
  
 PROVIDE DIMENSIONS ON THE FLOOR PLAN, DISTANCE FROM
 CORNER TO EDGE OF WINDOW, FOR OPENINGS NEAR THE CORNER.
 NUMBER THE OPENINGS TO CORRELATE WITH THE INSTALLATION
 SCHEDULE.THE OPENING 48X49, IF IN ZONE 5, HAS A
 DESIGN PRESSURE REQUIREMENT OF -57.11.
  
 3.SEE SHEET14A; A FACTOR OF .5 REQURED FOR ANCHOR
 SPACING WITH EDGE DISTANCE OF 2".
  
 2ND REVIEW; THIS WAS ADDRESSED BY CHANGING THE EDGE
 DISTANCE TO 3".THIS REQUIRES A FACTOR OF .86.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-01 Cont ID  
Sent By shill Date 2007-08-01 Time 15:57 Rev Time 0.00
Received By shill Date 2007-08-01 Time 15:57 Sent To  
Notes
2007-08-01 16:00:36****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 1.TWO COMPLETE COLLATED SETS OF PERMIT DOCUMENTS
 REQUIRED.ONLY ONE INSTALLATION SCHEDULE WAS
 SUBMITTED.ALSO IT STATES BUILDING HEIGHT AS >15'; DO
 YOU MEAN < (LESS THAN) 15'?
  
 2.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2), FBC
 R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE C
 HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC
 R301.2.1.4.
  
 3.SEE SHEET14A; A FACTOR OF .5 REQURED FOR ANCHOR
 SPACING WITH EDGE DISTANCE OF 2".
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-07 Cont ID  
Sent By adarroug Date 2007-09-07 Time 16:52 Rev Time 0.00
Received By adarroug Date 2007-09-07 Time 16:52 Sent To B
Notes
2007-09-07 16:52:34TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-29 Cont ID  
Sent By adarroug Date 2007-08-29 Time 08:54 Rev Time 0.00
Received By adarroug Date 2007-08-29 Time 08:54 Sent To B
Notes
2007-08-29 08:54:32TO "SHILL' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-10 Cont ID  
Sent By dpalmer Date 2007-08-10 Time 09:25 Rev Time 0.00
Received By dpalmer Date 2007-08-10 Time 09:25 Sent To B
Notes
2007-08-10 09:29:41TO SH'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-01 Cont ID  
Sent By shill Date 2007-08-01 Time 16:00 Rev Time 0.00
Received By shill Date 2007-07-10 Time 13:12 Sent To  
Notes
2007-07-10 13:13:04TO "MISC" BOX#1