2007-07-23 15:24:22 | DENIED |
| REFERENCE: |
| ** FBC-2004 PLUMBING. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. THE SUBMITTED ISOMETRIC DOES NOT REFLECT THE MASTER |
| PERMIT #07030410 FLOOR PLAN BATHROOM LAYOUTS. THERE ARE |
| NO SHOWERS BEING INDICATED ON THE MASTER PERMIT |
| #07030410 ONLY TUBS. PLEASE RESUBMIT WITH THE FOLLOWING |
| INFORMATION A} A FLOOR PLAN WITH THE EXISTING LAYOUT. |
| B} A REVISED FLOOR PLAN THAT CLEARLY REFLECTS THE |
| SUBMITTED BATHROOM ISOMETRIC WITH A WATER/CLOSET, |
| LAVATORY AND SHOWER. |
| |
| 2. CLARIFY WHAT THE THREE INCH (3") STACK IS FOR ON |
| THE RESUBMITTAL. |
| |
| 3. TRAPS ARE REQUIRED FOR THE SHOWER AND LAVATORY PER |
| FBC-2004 PLUMBING, SECTION 1002.1. PLEASE CLEARLY |
| INDICATE THEM ON THE RESUBMITTAL. |
| |
| 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.3: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| ********IMPORTANT INFORMATION******** |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS WHICH HAVE CHANGED AND |
| PROVIDE ONE COPY OF OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| |
| END OF COMMENTS: |
| |