Plan Review Details - Permit 07070146
Plan Review Stops For Permit 07070146
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-09 Cont ID  
Sent By rmcdouga Date 2007-08-09 Time 08:02 Rev Time 0.00
Received By rmcdouga Date 2007-08-08 Time 19:04 Sent To E
Notes
2007-08-09 08:02:022004 FBC
  
 1) THE ONLY ITEM LISTED IN THE DESCRIPTION OF WORK ON
 THE PERMIT APPLICATION THAT REQUIRES A PERMIT IS THE
 INTERIOR PARTITIONS.
  
 2) OWNER BUILDERS ARE NOT ALLOWED TO ACT AS CONTRACTORS
 FOR GROUP R2 MULTIFAMILY RESIDENTIAL BUILDINGS. YOU
 WILL BE REQUIRED TO HIRE A LICENSED GENERAL CONTRACTOR
 TO CONSTRUCT THE INTERIOR PARTITIONS.
  
 3) PLANS ARE REQUIRED TO BE DRAFTSMAN QUALITY DRAWN TO
 A MINIMUM OF 1/8 INCH SCALE. NO HANDWRITTEN NOTES IN
 PENCIL ARE ALLOWED ON THE PLANS. THE PLANS ARE REQUIRED
 TO BE CLEAR AND SUITABLE TO COPY FOR RECORD KEEPING
 PURPOSES.SEE FBC*106.1.3 CITY AMENDMENTS TO THE 2004
 FBC.
  
 4) FBC 717.5 DOES NOT ALLOW COMBUSTIBLES IN CONCEALED
 SPACES IN TYPE I OR II CONSTRUCTION. FBC 603.1 ALLOWS
 FIRE-RETARDANT-TREATED WOOD IN NONBEARING PARTITIONS
 WHERE FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
 THEREFORE, THE 2X4 PT BASEPLATE IS REQUIRED TO BE
 FIRE-RETARDANT-TREATED WOOD.
  
 5) PROVIDE A WALL SECTION OF THE INTERIOR PARTITION.
 SPECIFY STUD SPACING, ANCHOR TYPE AND SPACING THAT WILL
 BE USED TO ATTACH TOP AND BOTTOM OF WALLS TO EXISTING
 STRUCTURE, ETC. SEE FBC106.1.2.
  
 6) ADDITIONAL PERMITS FOR ELECTRICAL MAY BE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-08-10 Cont ID  
Sent By btrobaug Date 2007-08-10 Time 07:55 Rev Time 0.00
Received By btrobaug Date 2007-08-10 Time 07:05 Sent To I
Notes
2007-08-10 07:54:58 
 PLEASE REPLY, IN WRITING OR ON THE PLAN, TO THE
 FOLLOWING ARTICLES FROM THE 2005 NEC, WHICH MAY
 APPLY.INDICATE SPACING TO THE RECEPTACLES FROM THE
 OUTER EDGE OF THE PROPOSED WALL.
  
 210.52(A) GENERAL PROVISIONS IN EVERY KITCHEN, FAMILY
 ROOM, DINING ROOM, LIVING ROOM, PARLOR, LIBRARY, DEN,
 SUNROOM, BEDROOM, RECREATION ROOM, OR SIMILAR ROOM OR
 AREA OF DWELLING UNITS, RECEPTACLE OUTLETS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE GENERAL PROVISIONS
 SPECIFIED IN 210.52(A)(1) THROUGH (A)(3).
 (1) SPACING RECEPTACLES SHALL BE INSTALLED SO THAT NO
 POINT MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY
 WALL SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE
 OUTLET.
  
 DINING ROOMS MUST ALSO COMPLY WITH 210.52(B), SMALL
 APPLIANCE RECEPTACLE REQUIREMENT.
  
 ALSO NOTE SECTION,. R313.1.1, FBC. ALTERATIONS,
 REPAIRS AND ADDITIONS.
 WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE
 ALARMS SHALL BE INTERCONNECTED AND HARD WIRED. ALSO SEE
 EXCEPTION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-09 Cont ID  
Sent By rmcdouga Date 2007-08-09 Time 10:52 Rev Time 0.00
Received By rmcdouga Date 2007-07-09 Time 11:04 Sent To  
Notes
2007-07-09 11:04:15TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status N Date 2007-07-10 Cont ID  
Sent By choops Date 2007-07-10 Time 14:50 Rev Time 0.00
Received By choops Date 2007-07-10 Time 14:50 Sent To B
Notes
***NONE***