Plan Review Details - Permit 07070140
Plan Review Stops For Permit 07070140
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-04-03 Cont ID  
Sent By rmcdouga Date 2008-04-03 Time 07:33 Rev Time 0.00
Received By rmcdouga Date 2008-04-03 Time 07:06 Sent To  
Notes
2008-04-03 07:33:31FRONT DOOR WAS REVISED TO A THERMA-TRU FIBERGLASS
 DOOR. PRODUCT APPROVALS WERE SUBMITTED ALONG WITH
 REVISION FEE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-10-18 Cont ID  
Sent By rmcdouga Date 2007-10-18 Time 08:05 Rev Time 0.00
Received By rmcdouga Date 2007-10-18 Time 06:44 Sent To  
Notes
2007-10-18 08:05:36BUILDING PROVISO
  
 1) THE ROOFER IS TO SUBMIT RAS 117 CALCULATIONS FOR THE
 GAF RUBEROID MODIFIED BITUMEN ROOF SYSTEM NOA NO.
 03-0501.02, WHEN APPLYING FOR ROOF PERMIT.
  
 2)A SEPARATE PERMIT WITH SITE SPECIFIC ENGINEERING
 FOR THE CUSTOM CYPRESS FRONT DOOR WILL BE APPLIED FOR
 AT A LATER DATE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-24 Cont ID  
Sent By tgordon Date 2007-10-17 Time 16:16 Rev Time 0.00
Received By rmcdouga Date 2007-09-24 Time 07:08 Sent To  
Notes
2007-09-24 13:18:092004 FBC W/2007 SUPPLEMENT
 LEVEL 2 ALTERATION
 2 STORY ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) ON SHEET S3 THE PLANS SPECIFY ISONYNENE (ICYNENE)
 INSULATION, WHICH IS A BRAND NAME FOR SPRAY APPLIED
 FOAM INSULATION. THE SPECIFICATIONS AND ICC ES REPORT
 THAT WAS SUBMITTED IS FOR SEALECTION 500, WHICH
 REQUIRES AN IGNITION BARRIER WHEN INSTALLED IN ATTICS.
 PLEASE SPECIFY ON THE PLANS WHICH METHOD OF IGNITION
 BARRIER WILL BE INSTALLED (SEE 4.3.1 AND 4.3.2 FROM ES
 REPORT ESR-1172). PLEASE REVISE SHEET S3 TO SPECIFY
 SPRAY FOAM INSULATION. SEE FBC R 314.5.3.
  
 4) THE ARCHITECT'S RESPONSE TO ITEM #8 OF FIRST REVIEW
 STATES THAT THE EXISTING WINDOWS AND DOORS WILL NOT BE
 REMOVED AND REUSED ON THIS PROJECT. HOWEVER, SHEETS D1,
 D2 AND A1 OF THE PLANS STILL SPECIFY REUSING EXISTING
 WINDOWS IN THE NEW ADDITION. PLEASE CORRECT.
  
 5) THE FINISH GRADE ON THE PROPOSED EAST ELEVATION ON
 SHEET A.3 IS MISSING THE NEGATIVE SIGN. PLEASE CORRECT.
  
  
 6) SPECIFY THE CEILING CLADDING MATERIAL FOR THE
 COVERED PORCH ON THE PLANS. SEE ITEM # 24 ON FIRST
 REVIEW.
  
 7) THE ROOFER WILL SUBMIT RAS 117 CALCULATIONS FOR THE
 GAF ROOFING MATERIAL UNDER SEPARATE PERMIT PER RESPONSE
 TO ITEM # 33 OF FIRST REVIEW.
  
 8)A SEPARATE PERMIT WITH SITE SPECIFIC ENGINEERING
 FOR THE CUSTOM CYPRESS FRONT DOOR WILL BE APPLIED FOR
 AT A LATER DATE, PER RESPONSE TO ITEM # 35 OF FIRST
 REVIEW.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-24 Cont ID  
Sent By jleech Date 2007-07-17 Time 09:19 Rev Time 0.00
Received By rmcdouga Date 2007-07-24 Time 07:53 Sent To  
Notes
2007-07-24 10:46:11DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS.
 EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM)
 SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE
 RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL
 NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM
 AN ADJACENT PROJECTION OR WALL. SPECIFY THE DISTANCE TO
 THE CARRAIGE HOUSE AND STRUCTURES ON THE ADJACENT LOTS
 WHERE THE DISTANCE TO THE PROPERTY LINE IS LESS THAN 6
 FEET.
  
 4) SUBMIT ENERGY CALCULATIONS FOR THE REMODELED
 CARRIAGE HOUSEAS REQUIRED BY FBC CHAPTER 13.
  
 5) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE ICYNENE INSULATION.
  
 6) SHOW COMPLIANCE WITH FBC R320 PROTECTION AGAINST
 TERMITES. SPECIFY WHAT METHOD OF TERMITE PROTECTION
 WILL BE USED.
  
 7)SHOW COMPLIANCE WITH R320.7 PROTECTION AGAINST DECAY
 AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 8)IN ORDER FOR THE EXTERIOR DOORS OR WINDOWS TO BE
 REUSED THEY ARE REQUIRED TO HAVE A PRODUCT APPROVAL OR
 HAVE SITE SPECIFIC ENGINEERING. INDICATE WHICH PRODUCT
 APPROVALS ARE FOR THESE ITEMS OR SUBMIT SIGNED AND
 SEALED ENGINEERING FOR THEM. IMPACT PROTECTION IS ALSO
 REQUIRED FOR THESE PRODUCTS.
  
 9) SPECIFY THE WINDOW TYPES ON THE PLANS(IE. SINGLE
 HUNG, CASEMENT, ETC.).
  
 10) SPECIFY THE DOOR TYPE OF THE SIDE SWING DOOR AT THE
 GARAGE ON THE FIRST FLOOR PLAN ON CH.2. SUBMIT PRODUCT
 APPROVALS FOR THIS DOOR. THE DOOR IS NOT SHOWN ON THE
 PROPOSED EAST ELEVATION ONCH.4.
  
 11) SHOW COMPLIANCE WITH R322.1.1 FOR BATHROOM DOOR
 WITH A 29" CLEAR OPENING.
  
 12) ON SHEET S.1 THE NOTES REFERENCE ASCE 7-98. PLEASE
 UPDATE THIS TO REFERENCE ASCE 7-02 PER CHAPTER 43 OF
 THE 2004 FBC RESIDENTIAL.
  
 13) ALSO ON SHEET S.1, PLEASE UPDATE ASCE 530-99 TO
 ASCE 530-05. SEE FBC R CHAPTER 43.
  
 14) ON SHEET S.1 THE NOTES SPECIFY REQUIRED SOIL
 BEARING PRESSURE AS 3000 PSF. THE NOTE ON S.2 SPECIFIES
 THE REQUIRED SOIL BEARING PRESSURE AS 2500 PSF. PLEASE
 CORRECT. NOTE: THE SOIL ENGINEER'S REPORT IS FOR A SOIL
 BEARING CAPACITY OF 2500 PSF.
  
 15) PROVIDE DETAILS FOR THE INTERIOR STAIRS. SHOW
 COMPLIANCE WITH FBC R311.5. SPECIFY RISER AND TREAD
 DIMENSIONS, HANDRAILS, GUARDS, ETC.
  
 16) SPECIFY THE SLOPE OF THE PORCH ROOF.
  
 17) SPECIFY THE EMBED DEPTH OF THE #5 REBAR THAT IS
 DOWELED AND EPOXIEDINTO THE EXISTING SLAB. SEE
 FOUNDATION PLAN ON S.2.
  
 18) SPECIFY THE HEIGHT OF THE PORCH ABOVE FINISH
 GRADE.
  
 19) PROVIDE A DETAIL FOR THE FIRST FLOOR JOISTS ATTACH
 TO THE EXISTING FOUNDATION WALL. SEE THE FOUNDATION
 PLAN ON S.2 WHERE THE B CONNECTORS ARE SPECIFIED.
  
 20) DETAIL 2 ON S.2 SPECIFIES THE FOOTING DEPTH AS 1'-
 2" AND THE FOOTING SCHEDULE SPECIFIES THE DEPTH AS 18"
 OR 1'- 6". PLEASE CORRECT.
  
 21) PROVIDE BASE AND CAP CONNECTION DETAILS FOR THE 6 X
 6 WOOD POSTS AT THE PORCH.
  
 22) PROVIDE DETAILS FOR THE WOOD BEAM AT THE PORCH.
 SPECIFY THE CONNECTION OF THE WOOD BEAM TO THE WOOD
 FRAME WALLS.
  
 23) SPECIFY THE CONNECTION OF THE PORCH RAFTERS TO THE
 WALLS OF THE STRUCTURE.
  
 24) SPECIFY THE CEILING MATERIAL THAT WILL BE USED ON
 THE UNDERSIDE OF THE PORCH RAFTERS.
  
 25) SPECIFY THE OVERHANG AT THE PORCH ROOF.
  
 26) PLEASE INDICATE WHERE THE STEEL BEAM DETAILS 6, 7
 AND 8 ON S.3 WILL BE USED.
  
 27) THE EXISTING EAST ELEVATION ON A.3 DOES NOT SHOW
 THE TWO LAUNDRY ROOM WINDOWS.
  
 28) ON THE PROPOSED EAST ELEVATION ON SHEET A.3 PLEASE
 CLARIFY IF THE 19'- 2" IS THE CEILING (BOTTOM OF THE
 TRUSSES) OR THE ROOF (TOP OF TRUSSES). SEE THE LOCATION
 OF THE OVER FLOW SCUPPER.
  
 29) PROVIDE A DETAIL SPECIFING HOW THE PARAPET WALLS
 ARE CONNECTED TO THE ROOF TRUSSES AND THE WALLS BELOW.
 SPECIFY CONNECTORS, SPACING, ETC.
  
 30) SPECIFY WHERE THE 18" DEEP FLOOR TRUSSES IN DETAIL
 4 ON S.3 ARE USED.
  
 31) ON DETAIL 2 OF THE 2ND FLOOR FRAMING PLAN ON S.3
 THE FLOOR TRUSSES ARE SPECIFIED AS ROOF TRUSSES. PLEASE
 CORRECT.
  
 32)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 33) SUBMIT RAS 117 CALCULATIONS FOR ENHANCED FASTENING
 OF THE GAF ROOFING MATERIAL AS ALLOWED BY LIMITATION
 NUMBER 7 ON PAGE 32 OF THE NOA. THE DESIGN PRESSURE FOR
 THE SPECIFIED SYSTEM AND FASTENING OPTION IS - 45 PSF.
 THE COMPONENT AND CLADDING TABLE IN THE 2004 FBC
 SPECIFIES UPLIFTS OF -59.2 PSF IN ROOF ZONE 2 AND -89
 PSF IN ZONE 3.
  
 34) SUBMIT PRODUCT APPROVALS FOR THE DOUBLE OUTSWING
 FRENCH DOORS WITH SIDELITES.
  
 35) SUBMIT PRODUCT APPROVALS FOR THE NEW CYPRESS ENTRY
 DOOR.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-03-28 Cont ID  
Sent By btrobaug Date 2008-03-27 Time 14:40 Rev Time 0.00
Received By btrobaug Date 2008-03-27 Time 14:08 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-10-05 Cont ID  
Sent By btrobaug Date 2007-10-05 Time 08:54 Rev Time 0.00
Received By btrobaug Date 2007-10-05 Time 07:54 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-08-28 Cont ID  
Sent By btrobaug Date 2007-08-28 Time 08:47 Rev Time 0.00
Received By btrobaug Date 2007-08-28 Time 07:59 Sent To M
Notes
2007-08-28 08:47:03 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 THIS COMMENT FROM THE PREVIOUS REVIEW.
  
 #3} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND
 106.3.5.4(8) FBC. ALL PANELS. THIS COMMENT IS NOW IN
 REFERENCE TO PANEL "C".
  
 NEW COMMENT THAT IS NOW BROUGHT BY INCREASING THE
 SERVICE TO 400 AMPS.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66, 1/0 CU MINIMUM.
  
 2} THE MAIN HOUSE GROUND IS SHOWN AT THE INTERIOR PANEL
 "H", INSTEAD AT THE DISCONNECT OUTSIDE. THE GEC IS
 REQUIRED TO BE AT THE DISCONNECT OF A SEPARATE
 STRUCTURE, NOT ON THE LOAD SIDE. SEE 250.30(A).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-12 Cont ID  
Sent By btrobaug Date 2007-07-12 Time 07:27 Rev Time 0.00
Received By btrobaug Date 2007-07-12 Time 06:36 Sent To M
Notes
2007-07-12 07:27:06 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} THE ARCHITECTS SEAL IS INDISCERNIBLE. SEE
 61G1-16.001FAC.
  
 2} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL
 SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO
 BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5
 NEC 2005.
  
 3} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND
 106.3.5.4(8) FBC. ALL PANELS.
  
 4} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. LOCATE ON
 THE PLAN.
  
 5} LOCATE RECEPTACLES AS REQUIRED PER 210.52(D) IN THE
 2ND FLOOR BATHROOMS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-07-06 Cont ID  
Sent By swurafti Date 2007-07-06 Time 11:08 Rev Time 0.00
Received By swurafti Date 2007-07-06 Time 11:08 Sent To  
Notes
2007-08-20 09:41:59ADD $10 HISTORIC FEE PER F MITTNER 1ST RESUB 8-20-07
2007-07-06 11:09:15HISTORIC APPROVED BY JPAPA

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-09-16 Cont ID  
Sent By adarroug Date 2008-09-16 Time 12:39 Rev Time 0.00
Received By adarroug Date 2008-09-16 Time 12:38 Sent To M
Notes
2008-09-16 12:39:24TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-09-03 Cont ID  
Sent By adarroug Date 2008-09-03 Time 16:00 Rev Time 0.00
Received By adarroug Date 2008-09-03 Time 16:00 Sent To M
Notes
2008-09-03 16:01:23TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-03-27 Cont ID  
Sent By adarroug Date 2008-03-27 Time 09:15 Rev Time 0.00
Received By adarroug Date 2008-03-27 Time 09:15 Sent To B
Notes
2008-03-27 09:16:00TO "RMCDOUGAL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-03 Cont ID  
Sent By adarroug Date 2007-10-03 Time 17:09 Rev Time 0.00
Received By adarroug Date 2007-10-03 Time 17:09 Sent To E
Notes
2007-10-03 17:10:06TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-22 Cont ID  
Sent By adarroug Date 2007-08-22 Time 10:05 Rev Time 0.00
Received By adarroug Date 2007-08-22 Time 10:05 Sent To Z
Notes
2007-08-22 10:05:37TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-24 Cont ID  
Sent By rmcdouga Date 2007-07-24 Time 11:03 Rev Time 0.00
Received By rmcdouga Date 2007-07-09 Time 10:40 Sent To  
Notes
2007-07-09 10:40:17TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-09-17 Cont ID  
Sent By tgordon Date 2008-09-17 Time 14:06 Rev Time 0.30
Received By tgordon Date 2008-09-17 Time 14:06 Sent To  
Notes
2008-09-17 14:07:16REVISION TO MECH. PLAN M.1.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-09-05 Cont ID  
Sent By tgordon Date 2008-09-05 Time 08:20 Rev Time 0.30
Received By tgordon Date 2008-09-05 Time 08:19 Sent To  
Notes
2008-09-05 08:39:59PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLAN M.1
 *** DENIED ***
  
 1) THE MECHANICAL PLAN NEEDS TO BE SIGNED AND SEALED BY
 THE ARCHITECT (STEPHEN M. ROY) PER FAC 61G1-16.003.
  
 2) THE A/C EQUIPMENT MODEL NUMBERS ON THE PLAN ARE
 INCORRECT, SEE ATTACHED ARI LISTING. PLEASE CORRECT
 MODEL NUMBERS ON PLAN.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-10-17 Cont ID  
Sent By tgordon Date 2007-10-16 Time 15:06 Rev Time 0.30
Received By tgordon Date 2007-10-16 Time 15:06 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-08-29 Cont ID  
Sent By tgordon Date 2007-08-29 Time 13:04 Rev Time 0.30
Received By tgordon Date 2007-08-29 Time 13:04 Sent To P
Notes
2007-08-29 13:16:05PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR A 13.40 SEER A/C
 SYSTEM, AND THE MECHANICAL PLANS ARE CALLING FOR A
 13.00 SEER. THE TWO MUST COINCIDE PLEASE CORRECT.
  
 2) COULD NOT FIND THE A/C SYSTEM MODEL #25HBR330 LISTED
 ON THE MECHANICAL PLANS IN THE ARI DIRECTORY OR ON THE
 CARRIER WEB SITE. PLEASE SUBMIT THE ARI REFERENCE
 NUMBER, ORMANUFACTURER'S SPECIFICATION'S SHOWING THE
 SEER OF THE SYSTEM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-13 Cont ID  
Sent By tgordon Date 2007-07-13 Time 13:31 Rev Time 0.30
Received By tgordon Date 2007-07-13 Time 13:31 Sent To P
Notes
2007-07-13 13:42:47*** DENIED ***
 1) SEE ELECTRICAL REVIEW #1 REGARDING RAISED SEAL,
 PLEASE CORRECT.
  
 2) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.2.2.
  
 3) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-607.1.ABC.1.
  
 4) MAIN SUPPLY AIR DUCT (FLEX) FROM AHU TO THE MIXING
 BOX NEEDS TO BE SIZED.
  
 5) NEED TO SHOW CLOTHES DRYER VENT ON MECHANICAL PLANS,
 SEE 2004 FBC/R M1501.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-10-17 Cont ID  
Sent By jleech Date 2007-10-17 Time 07:59 Rev Time 0.00
Received By jleech Date 2007-10-17 Time 07:59 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-09-15 Cont ID  
Sent By jleech Date 2007-09-15 Time 12:21 Rev Time 0.00
Received By jleech Date 2007-09-15 Time 12:19 Sent To B
Notes
2007-09-15 12:26:42DENIED;
 PAGE A.3 EAST ELEVATION SHOWS ONLY 1 SCUPPER 2 SCUPPERS
 SHOWN ON PAGE A.0. EMERGENCY OVERFLOW ON PAGE A.0 IS
 LISTEDAT 4 X 12" ON PAGE A.3 EAST ELEVATION IS LISTED
 AS 6 X 10. PLEASE CORRECT.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-17 Cont ID  
Sent By jleech Date 2007-07-17 Time 09:21 Rev Time 0.00
Received By jleech Date 2007-07-17 Time 09:21 Sent To B
Notes
2007-07-17 09:29:57DELETE;
 1. SEE ELECTRICAL NOTE # 1.
 2. RISER DIAGRAMS DO NOT MATCH FLOOR PLAN.
 A) W/M ON 2ND FLOOR R/D 1ST FL FLAT
 B) 4 BATHROOMS SHOWN ON 2ND FL R/D
 CANNOT REVIEW AS DRAWN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
2007-07-17 08:40:58 
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2007-08-22 Cont ID  
Sent By choops Date 2007-08-22 Time 17:17 Rev Time 0.00
Received By choops Date 2007-08-22 Time 17:17 Sent To E
Notes
2007-08-22 17:18:02SENT TO BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-10 Cont ID  
Sent By choops Date 2007-07-10 Time 08:18 Rev Time 0.00
Received By choops Date 2007-07-10 Time 08:18 Sent To E
Notes
2007-07-10 08:20:12***FAILED***
  
  
 1)SHOW DISTANCE FROM PROPOSED ADDITION TO THE
 EXISTING CARRIAGE HOUSE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720