Plan Review Details - Permit 07070098
Plan Review Stops For Permit 07070098
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-09-10 Cont ID  
Sent By shill Date 2007-09-10 Time 18:41 Rev Time 0.00
Received By shill Date 2007-09-10 Time 18:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-08-27 Cont ID  
Sent By shill Date 2007-08-27 Time 13:01 Rev Time  
Received By shill Date 2007-08-27 Time 12:33 Sent To  
Notes
2007-08-27 13:02:36****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.)YOU'VE DESIGNED THIS JOB TO -47.2 PSF.ENGINEER
 HAS SPECIFIED DESIGN PRESSURE OF -51.6.YOU HAVE
 CHANGED THE DESIGN PRESSURE ON THE INSTALLATION
 SCHEDULE BUT DID NOT CHANGE THE ANCHOR SPACING, SEE
 SHEET 7 OF THE PRODUCT APPROVAL.
  
 THE PLANS WERE RETURNED WITH NO CORRECTIONS AND NOTES
 STATING:"CORRECT NEGATIVE PRESSURE IS CIRCLED ON
 TABLE 1" AND "POSITIVE PRESSURES IS 36.5 ANCHOR
 SCHEDULE IS CORRECT."
  
 PLEASE SEE THE PRODUCT APPROVAL, SHEET 7, WHICH I HAVE
 HIGHLIGHTED.TABLE 1 IS A TABLE FOR ALLOWABLE SPANS
 PER DESIGN PRESSURE.YOU HAVE CIRCLED -52, MAX
 ALLOWABLE SPAN OF 11'6.THIS INFORMATION IS CODE
 COMPLIANT FOR THIS JOB AND WAS NOT MENTIONED IN MY
 PREVIOUS REVIEW.
  
 THE ANCHOR SCHEDULE ON SHEET 7 IS FOR NEGATIVE
 PRESSURES.YOU HAVE CIRCLED 47.2, BUT AS THE NEGATIVE
 PRESSURE FOR THIS JOB IS -51.6, YOU SHOULD BE USING THE
 77PSF ROW.IF I UNDERSTAND YOUR RESPONSE CORRECTLY,
 YOU ARE STATING THAT THE ANCHOR SCHEDULE IS FOR
 POSITIVE PRESSURES.THIS IS NOT CORRECT; THIS CHART IS
 TO BE USED FOR NEGATIVE PRESSURES AS THAT IS WORST
 CASE.PLEASE EITHER HAVE THE QUALIFIER CONTACT ME OR
 CONTACT THE ENGINEER FOR CLARIFICATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-21 Cont ID  
Sent By shill Date 2007-08-21 Time 07:16 Rev Time 0.00
Received By shill Date 2007-08-21 Time 07:16 Sent To  
Notes
2007-08-21 07:19:30****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)YOU'VE DESIGNED THIS JOB TO -47.2 PSF.ENGINEER
 HAS SPECIFIED DESIGN PRESSURE OF -51.6.YOU HAVE
 CHANGED THE DESIGN PRESSURE ON THE INSTALLATION
 SCHEDULE BUT DID NOT CHANGE THE ANCHOR SPACING, SEE
 SHEET 7 OF THE PRODUCT APPROVAL.
  
 2.)PLEASE SEE THE NOTE AT THE BOTTOM OF THE
 INSTALLATION SCHEDULE - "ANCHOR TYPE MUST BE SPECIFIC,
 EG. THERE ARE DIFFERENT TYPES OF TAPCONS WITH DIFFERENT
 STRENGTH VALUES."THE INSTALLATION SCHEDULE STATES
 "1/4" TAPCON".THERE ARE TWO DIFFERENT 1/4" TAPCONS ON
 THE ANCHOR SCHEDULE.IN THIS CASE, IT APPEARS THAT YOU
 ARE SPECIFYING ANCHORING FOR THE MORE STRINGENT.IF
 THIS IS NOT THE CASE, SPECIFIC ANCHOR TYPE WILL BE
 REQUIRED ON THE INSTALLATION SCHEDULE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By shill Date 2007-07-26 Time 19:35 Rev Time 0.00
Received By shill Date 2007-07-26 Time 19:35 Sent To  
Notes
2007-07-26 19:36:16****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 _XX_1.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A
 DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ARCHITECT
 OR ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED SEALED ORIGINALS FAC61G15, FAC61G1 16.
  
 ____2.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 ____3.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.
  
 ____4.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____5.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.
  
 ____6.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 3
 ABOVE.
  
 ____8.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2),
 FBC R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE
 C HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC
 R301.2.1.4.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-05 Cont ID  
Sent By adarroug Date 2007-09-05 Time 12:04 Rev Time 0.00
Received By adarroug Date 2007-09-05 Time 12:04 Sent To B
Notes
2007-09-05 12:05:17TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 08:31 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 08:31 Sent To B
Notes
2007-08-27 08:31:45TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-09 Cont ID  
Sent By dpalmer Date 2007-08-09 Time 09:52 Rev Time 0.00
Received By dpalmer Date 2007-08-09 Time 09:52 Sent To B
Notes
2007-08-09 09:53:10TO SH'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-26 Cont ID  
Sent By shill Date 2007-07-26 Time 19:36 Rev Time 0.00
Received By shill Date 2007-07-06 Time 10:59 Sent To  
Notes
2007-07-06 10:59:38TO "MISC" BOX#1