Plan Review Details - Permit 07070046
Plan Review Stops For Permit 07070046
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-12-21 Cont ID  
Sent By btrobaug Date 2007-12-18 Time 09:12 Rev Time 0.00
Received By shill Date 2007-12-13 Time 09:35 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-11-06 Cont ID  
Sent By shill Date 2007-11-06 Time 13:42 Rev Time 0.00
Received By shill Date 2007-11-06 Time 13:42 Sent To  
Notes
2007-11-06 13:44:23****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.BUSINESS OCCUPANCY IS DECLARED.THE CITY AND
 COUNTY RECORDS SHOW THAT STORES ARE IN THIS LOCATION.
 IS THIS A CHANGE OF OCCUPANCY?
  
 2.SEE FIRST LIST REGARDING A LIFE SAFETY PLAN.
 PLEASE PROVIDE ONE AT THIS TIME TO SHOW HOW EGRESS IS
 AFFECTED.SHOW ALL EXIT LIGHTS, OCCUPANT LOAD, EXITS.
 YOU ARE AFFECTING EGRESS BY THIS RENOVATION, AND MUST
 SHOW COMPLIANCE AT THIS TIME (NOT IN THE FUTURE AS
 STATED ON THE PLAN).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-10-17 Cont ID  
Sent By shill Date 2007-10-17 Time 16:20 Rev Time 0.00
Received By shill Date 2007-10-17 Time 16:20 Sent To  
Notes
2007-10-17 16:22:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)"LEVEL 1 MAINTENANCE REPAIR" WAS DECLARED,
 APPARENTLY IN RESPONSE TO THE REQUIREMENT TO DECLARE
 LEVEL OF ALTERATION.PLEASE SEE CHAPTER 3, EXISTING
 BUILDING CODE, AND DECLARE LEVEL OF ALTERATION.YOU
 ARE CREATING NEW OPENINGS.THIS IS NOT A LEVEL 1
 ALTERATION, OR MAINTENANCE (NOT A CATEGORY), OR A
 REPAIR.PLEASE REVISE PLAN.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-24 Cont ID  
Sent By shill Date 2007-09-24 Time 15:01 Rev Time 0.00
Received By shill Date 2007-09-24 Time 15:01 Sent To  
Notes
2007-09-24 15:06:05****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 4.)DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.
  
 A NOTE WAS ADDED TO THE PLAN STATING THAT THE STRUCTURE
 IS DESIGNED TO FBC2001.HOW IS THIS POSSIBLE WHEN THE
 BUILDING WAS CONSTRUCTED IN 1957?THIS COMMENT IS
 APPLICABLE TO THE CURRENT SCOPE OF WORK.GOVERNING
 CODE FOR THIS PROJECT BASED ON APPLICATION DATE IS
 FBC2004.
  
 NEW COMMENT:
  
 DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.
  
 A SET HAS BEEN RETAINED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-05 Cont ID  
Sent By shill Date 2007-09-05 Time 11:42 Rev Time 0.00
Received By shill Date 2007-09-05 Time 11:42 Sent To Z
Notes
2007-09-05 11:47:19****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 4.)DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.
  
 5.)SHOW HOW EGRESS IS AFFECTED BY THE ELIMINATION OF
 THE DOOR.
  
 NEW COMMENT:
  
 6.)SHOW DOOR WIDTHS.
  
 7.)PLANS SHOW INTERIOR PARTITIONS.EGRESS
 REQUIREMENTS CANNOT BE DETERMINED BASED ON THE
 INFORMATION PROVIDED.PROVIDE A COMPLETE FLOOR PLAN,
 LIFE SAFETY PLAN.
  
 8.)SEE ATTACHED FS553.80(2)(B).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By shill Date 2007-07-26 Time 17:53 Rev Time 0.00
Received By shill Date 2007-07-26 Time 17:53 Sent To  
Notes
2007-07-26 18:07:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER),
 FBC*106.3.3.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 IN ADDITION TO THE NOA SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 3.)INCLUDE A CODE SUMMARY; BUILDING TYPE FBC6,
 BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION,
 OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY.
  
 4.)DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.
  
 5.)SHOW HOW EGRESS IS AFFECTED BY THE ELIMINATION OF
 THE DOOR.
  
 6.)IMPACT PROTECTION IS REQUIRED, FBC1609.1.4.
  
 7.)USE OF REMOVABLE SHUTTERS ON COMMERCIAL PROPERTIES
 REQUIRES APPROVAL FROM THE BUILDING OFFICIAL.IF YOU
 ARE PROPOSING TO USE REMOVABLE SHUTTERS, SUBMIT A
 HURRICANE INSTALLATION PLAN, SEE ATTACHED POLICY, ITEM
 13.PROVIDE PRODUCT APPROVALS AND COMPLETE AN
 INSTALLATION SCHEDULE.
  
 8.)THE DOORS PROPOSED ARE NOT FOR USE WHERE WATER
 INFILTRATION RESISTANCE IS REQUIRED.SHOW (ON THE
 PLAN) WHY WATER INFILTRATION RESISTANCE IS NOT
 REQUIRED.SEE FBC1714.5.2.1, EXCEPTIONS.
  
 9.)PROVIDE PRODUCT APPROVALS FOR THE STOREFRONT.
  
 10.)DETAIL A USES THE WORD "HUBGYGYVBGY".WHAT IS
 THIS?THE PURPOSE OF PLANS IS TO SHOW CODE COMPLIANCE
 OR FOR CONSTRUCTION.THE PURPOSE OF THIS NOTE IS NOT
 CLEAR.
  
 11.)THE PLAN SHOWS A 2X4 ALUMINUM TUBE, A GLASS
 PANEL.WINDOWS ARE TO BE TESTED IN ACCORDANCE WITH
 FBC1714.5.PLEASE MAKE SCOPE OF WORK AND
 SPECIFICATIONS CLEAR ON THE PLAN.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-12-18 Cont ID  
Sent By shill Date 2007-12-21 Time 13:50 Rev Time 0.00
Received By btrobaug Date 2007-12-14 Time 12:17 Sent To B
Notes
2007-12-14 12:20:31 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED.INVOLVING EXIT LIGHTS. 105.1 FBC
 AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-11-29 Cont ID  
Sent By adarroug Date 2007-11-29 Time 15:55 Rev Time 0.00
Received By adarroug Date 2007-11-29 Time 15:55 Sent To Z
Notes
2007-11-29 15:55:59TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-10-31 Cont ID  
Sent By adarroug Date 2007-10-31 Time 15:18 Rev Time 0.00
Received By adarroug Date 2007-10-31 Time 15:18 Sent To Z
Notes
2007-10-31 15:19:20TO "Z" BOX/RESUB--NEW SHEETS FOR "Z"

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-10-05 Cont ID  
Sent By adarroug Date 2007-10-05 Time 14:43 Rev Time 0.00
Received By adarroug Date 2007-10-05 Time 14:43 Sent To Z
Notes
2007-10-05 14:43:41TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-05 Cont ID  
Sent By adarroug Date 2007-10-05 Time 14:41 Rev Time 0.00
Received By adarroug Date 2007-10-05 Time 14:41 Sent To Z
Notes
2007-10-05 14:41:55TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-09-13 Cont ID  
Sent By adarroug Date 2007-09-13 Time 14:12 Rev Time 0.00
Received By adarroug Date 2007-09-13 Time 14:12 Sent To B
Notes
2007-09-13 14:12:29TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-31 Cont ID  
Sent By adarroug Date 2007-08-31 Time 09:55 Rev Time 0.00
Received By adarroug Date 2007-08-31 Time 09:55 Sent To B
Notes
2007-08-31 09:55:25TO "SHILL' DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-31 Cont ID  
Sent By adarroug Date 2007-07-26 Time 09:52 Rev Time 0.00
Received By adarroug Date 2007-07-05 Time 09:49 Sent To  
Notes
2007-07-05 09:52:09TO "MISC" BOX#1

Review Stop Z ZONING
Rev No 5 Status P Date 2007-12-03 Cont ID  
Sent By choops Date 2007-12-03 Time 11:03 Rev Time 0.00
Received By choops Date 2007-12-03 Time 11:03 Sent To B
Notes
2007-12-03 11:01:37***APPROVED - RESUB #5***
  
 RESTAMPED PLANS
  
 SENT TO "B" - SH

Review Stop Z ZONING
Rev No 4 Status P Date 2007-11-06 Cont ID  
Sent By choops Date 2007-11-06 Time 11:00 Rev Time 0.00
Received By choops Date 2007-11-06 Time 11:00 Sent To B
Notes
2007-11-06 11:01:23***APPROVED - RESUB #4***
  
 RESTAMPED PLANS
  
 SENT TO "B" - SH

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-11 Cont ID  
Sent By choops Date 2007-10-11 Time 11:08 Rev Time 0.00
Received By choops Date 2007-10-11 Time 11:08 Sent To B
Notes
2007-10-11 11:08:56***APPROVED - RESUB #2***
  
 SENT TO "B" - SH

Review Stop Z ZONING
Rev No 2 Status F Date 2007-09-20 Cont ID  
Sent By choops Date 2007-09-20 Time 08:11 Rev Time 0.00
Received By choops Date 2007-09-20 Time 08:11 Sent To B
Notes
2007-09-20 08:13:37***FAILED - RESUB #2***
  
  
 REPEAT COMMENTS:
  
 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY.
  
 2)PURSUANT TO SECTION 94-219(D)(9)(A) OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS:ALL PROPERTIES
 SHALL BE BROUGHT INTO COMPLIANCE WITH THE LANDSCAPE
 REGULATIONS IN ARTICLE XIV, CONCURRENTLY WITH EXTERIOR
 BUILDING IMPROVEMENTS EXCEEDING $10,000.00. PLEASE
 PROVIDE A LANDSCAPE PLAN INDICATING SUCH.
  
 3)PLANS SHALL SHOW COMPLIANCE WITH SECTION 94-221,
 SPECIFICALLY WITH REGARD TO THE FIRST FLOOR GLAZING
 REQUIREMENTS, THE WINDOWS 2" DEPTH SETBACK, AND THE
 WINDOW OPENINGS 2' SETBACK FROM THE CORNERS OF THE
 BUILDING.PLANS MUST INDICATE THESE
 DIMENSIONS/REQUIREMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720
  

Review Stop Z ZONING
Rev No 1 Status F Date 2007-09-12 Cont ID  
Sent By choops Date 2007-09-12 Time 08:55 Rev Time 0.00
Received By choops Date 2007-09-12 Time 08:55 Sent To  
Notes
2007-09-12 09:09:37***FAILED***
  
  
 1)TWO (2) SETS OF ALL REVISED PLANS SHALL BE
 SUBMITTED.
  
 2)ELEVATIONS SHALL BE LABELED INDICATING WHICH
 STREET FRONTAGE IT FACES.
  
 3)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY.
  
 4)PURSUANT TO SECTION 94-219(D)(9)(A) OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS:ALL PROPERTIES
 SHALL BE BROUGHT INTO COMPLIANCE WITH THE LANDSCAPE
 REGULATIONS IN ARTICLE XIV, CONCURRENTLY WITH EXTERIOR
 BUILDING IMPROVEMENTS EXCEEDING $10,000.00. PLEASE
 PROVIDE A LANDSCAPE PLAN INDICATING SUCH.
  
 5)PLANS SHALL SHOW COMPLIANCE WITH SECTION 94-221,
 SPECIFICALLY WITH REGARD TO THE FIRST FLOOR GLAZING
 REQUIREMENTS, THE WINDOWS 2" DEPTH SETBACK, AND THE
 WINDOW OPENINGS 2' SETBACK FROM THE CORNERS OF THE
 BUILDING.
  
 6)PLANS A-1 SHOW A "FUTURE CEILING HEIGHT" OF 9' ,
 THE CEILING WILL NOT BE PERMITTED TO A LOWER LEVEL THAN
 WHAT IS EXISTING AS IT IS NONCONFORMING WITH RESPECT TO
 SECTION 94-221(A)(3):STORIES AT THE SIDEWALK LEVEL
 SHALL BE NO LESS THAN 12 FEET IN HEIGHT FROM FINISHED
 FLOOR TO FINISHED CEILING AND SHALL NOT EXCEED 16 FEET
 IN HEIGHT FROM FINISHED FLOOR TO FINISHED FLOOR.
 MEZZANINES THAT EXCEED THE PERMISSIBLE PERCENTAGE OF
 FLOOR AREA FOR A MEZZANINE AS DEFINED IN THE CITY'S
 BUILDING CODE SHALL BE COUNTED AS A STORY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720