Plan Review Details - Permit 07070039
Plan Review Stops For Permit 07070039
Review Stop E ELECTRICAL
Rev No 1 Status N Date 2007-07-06 Cont ID  
Sent By btrobaug Date 2007-07-06 Time 12:25 Rev Time 0.00
Received By btrobaug Date 2007-07-06 Time 12:22 Sent To I
Notes
2007-07-06 12:25:21 
 PROVISO
  
 THERE IS NEW ELECTRICAL EQUIPMENT INDICATED ON THE
 PLAN. AN ELECTRICAL CONTRACTOR MUST OBTAIN A PERMIT FOR
 THIS WORK.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status P Date 2007-07-16 Cont ID  
Sent By btrobaug Date 2007-07-06 Time 12:26 Rev Time 0.00
Received By btrobaug Date 2007-07-05 Time 15:15 Sent To PC
Notes
2007-07-05 15:16:21TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-07-06 Cont ID  
Sent By tgordon Date 2007-07-06 Time 08:58 Rev Time 0.30
Received By tgordon Date 2007-07-06 Time 08:58 Sent To E
Notes
2007-07-06 09:02:49*** PROVISO ***
 1) 2004 FBC/M 606.2.2 COMMON SUPPLY, RETURN AIR AND
 SUPPLY AIR SYSTEMS.
 WHERE MULTIPLE AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY
 OR RETURN AIR DUCTS OR PLENUMS WITH A COMBINED DESIGN
 CAPACITY GREATER THAN 2,000 CFM (0.9 M 3 /S), THE
 RETURN AIR AND SUPPLY AIR SYSTEM SHALL BE PROVIDED WITH
 SMOKE DETECTORS IN ACCORDANCE WITH SECTION 606.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.