Plan Review Details - Permit 07070033
Plan Review Stops For Permit 07070033
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-05 Cont ID  
Sent By kconrad Date 2007-12-05 Time 18:56 Rev Time 0.00
Received By kconrad Date 2007-12-05 Time 18:13 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-09-06 Cont ID  
Sent By kconrad Date 2007-09-06 Time 17:39 Rev Time 0.00
Received By kconrad Date 2007-09-06 Time 16:31 Sent To I
Notes
2007-09-06 17:48:49ALL PREVIOUS BUILDING PLAN REVIEW COMMENTS HAVE BEEN
 ADDRESSED. HOWEVER, THE PROJECT VALUATION APPEARS LOW
 AND SHOULD BE ADJUSTED TO $150,000.00.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-12 Cont ID  
Sent By kconrad Date 2007-07-12 Time 19:08 Rev Time 0.00
Received By kconrad Date 2007-07-12 Time 17:17 Sent To I
Notes
2007-07-12 19:08:35PROJECT: 1551 NORTH FLAGLER DRIVE
  
 REVIEW: 2004 FLORIDA BUILDING CODE WITH 2006 REVISIONS
  
 STATUS: DENIED
  
 COMMENTS:
  
  
 1) PLEASE REVISE OCCUPANCY TYPE TO REFLECT BUSINESS
 GROUP B AS PER THE FBC, SECTION 304.1. ALSO INDICATE
 OCCUPANCY LOAD.
  
 2) PLEASE REVISE THE INDICATED CONSTRUCTION TYPE. THIS
 BUILDING WAS CONSTRUCTED AS A TYPE 1.
  
 3) PLEASE INDICATE THE MECHANICAL ATTACHMENT OF THE
 RUNNER CHANNEL TO THE EXISTING STRUCTURE. ALSO PROVIDE
 CLARIFICATION OF EXISTING FRAMING MEMBER: WOOD OR STEEL
 JOISTS.
  
 4) SHOW MECHANICAL ATTACHMENT OF THE METAL FRAMING
 DIAGONAL BRACING TO EXISTING STRUCTURE CONNECTION. SEE
 DETAIL 1 ON SHEET A3 OF 8.
  
 5) PROVIDE SPECIFICATIONS FOR CMU WALL INSULATION.
  
 6) PLEASE SHOW FINISHED COUNTERTOP HEIGHTS ON FLOOR
 PLAN, SHEET A1 OF 8.
  
 7) PLEASE PROVIDE FIRE-STOPPING DETAILS IF APPLICABLE.
  
 8) FIRE- BLOCKING SHALL CONFORM TO THE FOLLOWING:
  
 717.1 GENERAL.
 FIREBLOCKING AND DRAFTSTOPPING SHALL BE INSTALLED IN
 COMBUSTIBLE CONCEALED LOCATIONS IN ACCORDANCE WITH THIS
 SECTION. FIREBLOCKING SHALL COMPLY WITH SECTION 717.2.
 DRAFTSTOPPING IN FLOOR/CEILING SPACES AND ATTIC SPACES
 SHALL COMPLY WITH SECTIONS 717.3 AND 717.4,
 RESPECTIVELY. THE PERMITTED USE OF COMBUSTIBLE
 MATERIALS IN CONCEALED SPACES OF NONCOMBUSTIBLE
 BUILDINGS SHALL BE LIMITED TO THE APPLICATIONS
 INDICATED IN SECTION 717.5.
  
 9) COMBUSTIBLES IN CONCEALED SPACES SHALL COMPLY WITH
 THE FOLLOWING:
  
 717.5 COMBUSTIBLES IN CONCEALED SPACES IN TYPE I OR II
 CONSTRUCTION.
 COMBUSTIBLES SHALL NOT BE PERMITTED IN CONCEALED SPACES
 OF BUILDINGS OF TYPE I OR II CONSTRUCTION.
 EXCEPTIONS:
 1. COMBUSTIBLE MATERIALS IN ACCORDANCE WITH SECTION
 603.
 2. COMBUSTIBLE MATERIALS COMPLYING WITH SECTION 602 OF
 THE FLORIDA BUILDING CODE, MECHANICAL.
 3. CLASS A INTERIOR FINISH MATERIALS.
 4. COMBUSTIBLE PIPING WITHIN PARTITIONS OR ENCLOSED
 SHAFTS INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF
 THIS CODE. COMBUSTIBLE PIPING SHALL BE PERMITTED WITHIN
 CONCEALED CEILING SPACES WHERE INSTALLED IN ACCORDANCE
 WITH THE FLORIDA BUILDING CODE, MECHANICAL AND THE
 FLORIDA BUILDING CODE, PLUMBING.
  
 10) FIRE RETARDANT TREATED LUMBER SHALL BE USED AS PER
 THE FOLLOWING SECTION:
  
 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
 1.2. NONBEARING EXTERIOR WALLS WHERE NO FIRE RATING IS
 REQUIRED.
 1.3. ROOF CONSTRUCTION AS PERMITTED IN TABLE 601, NOTE
 C, ITEM 3.
  
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-01-03 Cont ID  
Sent By btrobaug Date 2008-01-03 Time 12:04 Rev Time 0.00
Received By btrobaug Date 2008-01-03 Time 10:05 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-11-19 Cont ID  
Sent By btrobaug Date 2007-11-19 Time 11:37 Rev Time 0.00
Received By btrobaug Date 2007-11-19 Time 11:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-08-28 Cont ID  
Sent By btrobaug Date 2007-08-28 Time 13:45 Rev Time 0.00
Received By btrobaug Date 2007-08-28 Time 13:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-07-11 Cont ID  
Sent By btrobaug Date 2007-07-11 Time 13:12 Rev Time 0.00
Received By btrobaug Date 2007-07-11 Time 13:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-11-20 Cont ID  
Sent By mawillia Date 2007-11-20 Time 15:37 Rev Time 0.00
Received By mawillia Date 2007-11-20 Time 15:17 Sent To  
Notes
2007-11-20 15:36:49*****APPROVED REVISION DATED 11/04/07*****
  
  
 REVIEWED REVISED PLAN SHEETS A1, A2, E1, E2, P1 AND M1;
 SHEETS A2 AND E2 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-08-28 Cont ID  
Sent By mawillia Date 2007-08-28 Time 17:21 Rev Time 0.00
Received By mawillia Date 2007-08-28 Time 16:53 Sent To  
Notes
2007-08-28 17:17:52*****PROVISO*****
  
  
 WITH THE UNDERSTANDING THAT THE CORRECT OCCUPANCY TYPE
 (BUSINESS, NOT ASSEMBLY) BE INDICATED ON THE COVER
 SHEET;PLAN SHEET A3 AND E2 WERE STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-13 Cont ID  
Sent By mwennerg Date 2007-07-13 Time 14:13 Rev Time 0.00
Received By mwennerg Date 2007-07-13 Time 14:13 Sent To  
Notes
2007-07-13 14:26:12***DENIED***
  
 1) PLEASE MAKE CORRECTION TO OCCUPANCY CLASSIFICATION,
 AND INCLUDE OCCUPANT LOAD INFORMATION.
  
 2) DUCT SMOKE DETECTORS WHERE PROVIDED SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS IF APPLICABLE.
  
 3) IN ADDITION TO FIRE SPRINKLER, SEPARATE SHOP
 DRAWINGS AND PERMIT REQUIRED FOR FIRE ALARM REMODEL.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-11-27 Cont ID  
Sent By mperson Date 2007-11-27 Time 15:31 Rev Time 0.00
Received By mperson Date 2007-11-27 Time 15:31 Sent To PC
Notes
2007-11-27 15:36:58GAS REVISION: THE GAS RISER DIAGRAM AND RELOCATED GAS
 DRYERS AND METER HAVE BEEN REVIEWED FOR CODE
 COMPLIANCE. THESE NEW SHEETS ARE IDENTIFIED AS SK-2 AND
 SK-3.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-08-31 Cont ID  
Sent By mperson Date 2007-08-31 Time 15:50 Rev Time 0.00
Received By mperson Date 2007-08-31 Time 15:50 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-07-23 Cont ID  
Sent By jleech Date 2007-07-23 Time 10:43 Rev Time 0.00
Received By jleech Date 2007-07-23 Time 10:28 Sent To  
Notes
2007-07-23 10:43:20DENIED;
 1. GAS RISER DIAGRAM IS NOT SIZED THE SAME AS GAS LOAD
 CALCULATIONS. SIZING ON DIAGRAM IS TOO SMALL SEE SIZING
 TABLE 402.4(2).
 2. SHOW COMPLIANCE FOR COMBUSTION AIR AS
 PER 2001 FBC(M) CHAPTER 7. ( DRYERS)
  
 3. PROVIDE MANUFACTURE CUT SHEETS FOR WATER HEATERS.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-02 Cont ID  
Sent By spalmer Date 2008-01-02 Time 16:14 Rev Time 0.00
Received By spalmer Date 2008-01-02 Time 16:14 Sent To E
Notes
2008-01-02 16:14:16TO BILL TROBAUGHS DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-12-26 Cont ID  
Sent By spalmer Date 2007-12-26 Time 10:13 Rev Time 0.00
Received By spalmer Date 2007-12-26 Time 10:13 Sent To M
Notes
2007-12-26 10:13:25TO TOM GORDON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-07 Cont ID  
Sent By adarroug Date 2007-11-07 Time 15:58 Rev Time 0.00
Received By adarroug Date 2007-11-07 Time 15:58 Sent To  
Notes
2007-11-08 15:57:25TO "BOB"#12
2007-11-07 15:59:08WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-08 Cont ID  
Sent By dpalmer Date 2007-08-08 Time 18:17 Rev Time 0.00
Received By dpalmer Date 2007-08-08 Time 18:17 Sent To  
Notes
2007-08-23 13:29:09TO "BOB"#9
2007-08-08 18:17:48WAITING FOR BOB BOARD.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-07-23 Time   Rev Time 0.00
Received By adarroug Date 2007-07-05 Time 10:57 Sent To  
Notes
2007-07-05 10:58:36WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-12-26 Cont ID  
Sent By tgordon Date 2007-12-26 Time 11:45 Rev Time 0.30
Received By tgordon Date 2007-12-26 Time 11:45 Sent To  
Notes
2007-12-26 11:46:40MECH. REVISION TO PLANS PAGE M1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-11-14 Cont ID  
Sent By tgordon Date 2007-11-14 Time 14:04 Rev Time 0.40
Received By tgordon Date 2007-11-14 Time 14:03 Sent To  
Notes
2007-11-14 14:04:49MECHANICAL REVISION TO PAGE M1.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-08-28 Cont ID  
Sent By tgordon Date 2007-08-24 Time 07:57 Rev Time 1.15
Received By tgordon Date 2007-08-24 Time 07:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-11 Cont ID  
Sent By tgordon Date 2007-07-11 Time 15:51 Rev Time 2.00
Received By tgordon Date 2007-07-11 Time 15:51 Sent To  
Notes
2007-07-11 16:48:43*** DENIED ***
 1) PLEASE PROVIDE COMBUSTION AND MAKE-UP AIR, AND
 CALCULATIONS FOR GAS CLOTHES DRYERS AS THEY ARE IN A
 CONFINED SPACE, SEE 2004 FBC/FG 304.
  
 2) PLEASE RE-CALCULATE OUTSIDE AIR CALCULATIONS. MY
 CALCULATIONS SHOW THAT ZONE 1 REQUIRES 1,000 CFM'S,
 ZONE 2 REQUIRES 531 CFM'S, AND ZONE 3 REQUIRES 750
 CFM'S, SEE 2004 FBC/M TABLE 403.3 'SPECIALTY SHOPS'
 'BEAUTY' .
  
 3) SEE A/C SYSTEMS ON MECHANICAL PLANS ARE NOT LABELED
 CORRECT, CHECK THE WSHP SCHEDULE.
  
 4) SEE RETURN AIR GRILL FROM UNIT 2 IS COMMON DUCTED TO
 UNIT 3 GRILL ALSO AND THIS WOULD REQUIRE SMOKE DETECTOR
 IN THE SUPPLY AND RETURN DUCTS, PER 2004 FBC/M 606.2.2.
 IF THE ERV SUPPLIED OUTSIDE AIR TO UNIT 3 RETURN AIR
 GRILL THEN THE RETURNS WOULD NOT BE A COMMON RETURN AND
 NOT REQUIRE SMOKE DETECTORS IN THE RETURNS, ONLY THE
 SUPPLIES.
  
 5) PLEASE SHOW THE LOCATION OF THE DUCT SMOKE DETECTORS
 ON THE PLANS, ALSO THE ERV. SEE 2004 FBC/M 606.1.
  
 6) PLEASE LIST THE ERV IN THE EQUIPMENT SCHEDULE.
  
 7) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE
 ERV.
  
 8) PLEASE SHOW THE CFM'S FOR THE BATHROOM EXHAUST FANS
 ON THE MECHANICAL PLANS.
  
 9) THE FAN SCHEDULE IS SHOWING EF-2 AT 750 CFM'S, BUT
 IN THE NAILS ROOM IT SHOWS 1200 CFM'S, PLEASE CORRECT.
  
 10) IF EF-2 IS REMOVING 1200 CFM'S AND OUTSIDE AIR INTO
 THE BUILDING IS ONLY 650 CFM'S THE BUILDING WOULD BE IN
 A NEGATIVE PRESSURE, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-12-03 Cont ID  
Sent By jleech Date 2007-12-03 Time 09:49 Rev Time 0.00
Received By jleech Date 2007-12-03 Time 09:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-08-31 Cont ID  
Sent By mperson Date 2007-08-31 Time 15:50 Rev Time 0.00
Received By mperson Date 2007-08-31 Time 15:50 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-07-23 Cont ID  
Sent By jleech Date 2007-07-23 Time 10:05 Rev Time 0.00
Received By jleech Date 2007-07-23 Time 09:10 Sent To  
Notes
2007-07-23 10:27:25DENIED;
 1. SANITARY RISER DIAGRAM;
 A) AUTOMATIC CLOTHES WASHERS ARE NOT PERMITED
 TO DUMP INTO A SANITARY CROSS SEFBC-2004 PLUMBING
 SECTION 706.3.
 B) LABLE ALL FIXTURES.
 C) EXPLAIN SANITARY STUB.
 D) LAUNDRY TUB NOT SHOWN.
 2. WATER RISER; SHOW WATER HAMMER ARRESTORS WHERE
 REQUIRED AND SPEC OUT SIZE AND MANUFATURE. SEE SECTION
 604.9
 3. PLUMBING NOTE # 8 PIPE2 1/2" AND SMALLER MUST PITCH
 1/4" PER FOOT. SEE TABLE 704.1.
 4. BREAK SINK MUST MEET THE REQUIREMENTS OF FBC-2004
 BUILDING CHAPTER 11 ACCESSIBITY CODE SEE SECTIONS;
 11-4.24.2 HEIGHT
 11-4.24.3 KNEE CLEARANCE UNDER SINK ( NO
 DOORS)
 11-4.24.4 DEPTH OF SINK. ( 6 1/2 DEEP MAX.
 11-4.24.5 CLEAR FLOOR SPACE SHOW ON PLANS.
 11-4.24.6 RAP EXPOSED PIPES.
 11-4.24.7 LEVER OPERATED FAUCETS.
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2007-07-24 Cont ID  
Sent By choops Date 2007-07-24 Time 11:22 Rev Time 0.00
Received By choops Date 2007-07-24 Time 11:22 Sent To  
Notes
2007-07-24 11:23:10*VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.