Plan Review Details - Permit 07070030
Plan Review Stops For Permit 07070030
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-08-09 Cont ID  
Sent By btrobaug Date 2007-08-09 Time 16:09 Rev Time 0.00
Received By btrobaug Date 2007-08-09 Time 16:08 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-05 Cont ID  
Sent By btrobaug Date 2007-07-05 Time 13:31 Rev Time 0.00
Received By btrobaug Date 2007-07-05 Time 13:28 Sent To FIRE
Notes
2007-07-05 13:31:24 
  
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1}SUBMIT A FLOOR PLAN AND INDICATING THE LOCATION OF
 ALL EQUIPMENT AND DEVICES BEING INSTALLED UNDER THE
 SCOPE OF THIS APPLICATION.106.1.1 FBC.
  
 2} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS,
 CONDUIT AND CONDUCTOR SIZE AND TYPE, AND THE LOCATION
 FOR EQUIPMENT BEING WIRED UNDER THIS PERMIT .
  
 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.3.4.3.FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-09-21 Cont ID  
Sent By mwennerg Date 2007-09-21 Time 14:01 Rev Time 0.00
Received By mwennerg Date 2007-09-21 Time 14:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-08-09 Cont ID  
Sent By mwennerg Date 2007-08-09 Time 15:23 Rev Time 0.00
Received By mwennerg Date 2007-08-09 Time 15:23 Sent To E
Notes
2007-08-09 15:28:18***DENIED***
  
 PLEASE NOTE THAT NOT ALL COMMENTS FROM FIRST FIRE
 REVIEW HAVE BEEN ADDRESSED.
  
 1) OK
  
 2) WORK TO COMPLY WITH NFPA 101, SEC. 7.2.1.6.2. FOR
 ACCESS CONTROLLED EGRESS DOORS.
  
 3) WORK THAT IMPACTS LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 4) OK
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-06 Cont ID  
Sent By mwennerg Date 2007-07-06 Time 15:30 Rev Time 0.00
Received By mwennerg Date 2007-07-06 Time 15:30 Sent To  
Notes
2007-07-06 15:38:45***DENIED***
  
 PLEASE NOTE THAT ADDITIONAL INFORMATION IS NEEDED FOR
 REVIEW
  
 1) PLEASE PROVIDE A FLOOR PLAN ILLUSTRATING SPECIFIC
 EQUIPMENT AND LAYOUT OF DEVICES.
  
 2) WORK TO COMPLY WITH NFPA 101, SEC. 7.2.1.6.2 FOR
 ACCESS CONTROLLED EGRESS DOORS.
  
 3) WORK THAT IMPACTS LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 4) PLEASE SPECIFY HOW EQUIPMENT WILL IMPACT EXISTING
 FIRE ALARM SYSTEM.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-30 Cont ID  
Sent By adarroug Date 2007-08-30 Time 16:24 Rev Time 0.00
Received By adarroug Date 2007-08-30 Time 16:24 Sent To FIRE
Notes
2007-08-30 16:24:32TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-23 Cont ID  
Sent By adarroug Date 2007-07-23 Time 16:52 Rev Time 0.00
Received By adarroug Date 2007-07-23 Time 16:52 Sent To FIRE
Notes
2007-07-23 16:52:44TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-06 Cont ID  
Sent By mwennerg Date 2007-07-06 Time 15:40 Rev Time 0.00
Received By mwennerg Date 2007-07-03 Time 15:06 Sent To  
Notes
2007-07-03 15:07:02TO "E" BOX