Plan Review Details - Permit 07061034
Plan Review Stops For Permit 07061034
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-01-29 Cont ID  
Sent By shill Date 2008-01-29 Time 14:30 Rev Time 0.00
Received By shill Date 2008-01-29 Time 14:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-08-09 Cont ID  
Sent By shill Date 2007-08-09 Time 11:36 Rev Time 0.00
Received By shill Date 2007-08-09 Time 11:36 Sent To  
Notes
2007-08-09 11:36:57****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PROVIDE ANCHORING INFORMATION TO COMPLY WITH
 FBC1609.1.3, FBC R301; STRUCTURAL MEMBERS AND SYSTEMS,
 AND COMPONENTS AND CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED OVERTURNING,
 UPLIFT AND SLIDING AND TO PROVIDE CONTINUOUS LOAD PATHS
 FOR THESE FORCES TO THE FOUNDATION.WHERE A PORTION OF
 THE RESISTANCE TO THESE FORCES IS PROVIDED BY DEAD
 LOAD, THE MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE USED.
  
 2.)DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.
  
 3.)PROVIDE A DETAIL FOR THE SLAB INCLUDING ALL
 DIMENSIONS AND STRUCTURAL INFORMATION.USE OF A PREFAB
 SLAB REQUIRES CALCULATIONS PREPARED BY AN ENGINEER.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-02-20 Cont ID  
Sent By btrobaug Date 2008-02-20 Time 14:17 Rev Time 0.00
Received By btrobaug Date 2008-02-20 Time 13:29 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-01-28 Cont ID  
Sent By btrobaug Date 2008-01-28 Time 11:11 Rev Time 0.00
Received By btrobaug Date 2008-01-28 Time 10:27 Sent To M
Notes
2008-01-28 11:11:27 
  
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
 THIS COMMENT WAS NOT ADDRESSED FROM THE PREVIOUS
 REVIEW
  
 4} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR INDICATING RECOMMENDED SETBACKS FROM
 STRUCTURES.
  
 NEW COMMENT
  
 INDICATE THE SETBACK FROM THE RESIDENCE TO THE PROPOSED
 GENERATOR, ON THE SITE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-16 Cont ID  
Sent By btrobaug Date 2007-07-16 Time 13:53 Rev Time 0.00
Received By btrobaug Date 2007-07-16 Time 12:53 Sent To G
Notes
2007-07-16 13:53:04 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE
 PLAN/DRAWINGS, SHALL PRINT AND SIGN THEIR NAME ON THE
 SHEETS THEY DRAW. PLEASE DO THIS PRIOR TO
 RESUBMITTING.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 DO THIS ON A SITE PLAN, NOT ON THE SURVEY, 106.1.3FBC.
  
 3} PER 702.5 CAPACITY AND RATING. AN OPTIONAL STANDBY
 SYSTEM SHALL HAVE ADEQUATE CAPACITY AND RATING FOR THE
 SUPPLY OF ALL EQUIPMENT INTENDED TO BE OPERATED AT ONE
 TIME. THE LOAD CALCULATION EXCEEDS THE GENERATOR
 OUTPUT.
  
 4} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR
 INDICATING RECOMMENDED SETBACKS FROM STRUCTURES.
  
 5} INDICATE WHICH TRANSFER SWITCH IS BEING USED. NOTE:
 GIVEN THE LOCATION IN THE SERVICE, THIS SWITCH MUST
 HAVE AN AIC RATING PER 110.9 AND 10.
  
 6} THE SPECIFICATIONS GIVEN FOR THE TRANSFER SWITCH
 INDICATES"UL RECOGNIZED DEVICE". PLEASE PROVIDE THE
 LISTING NUMBER OR HAVE THE MANUFACTURER VERIFY IN
 WRITING THE SWITCH HAS A UL 1008 LISTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2008-03-06 Cont ID  
Sent By mperson Date 2008-03-06 Time 08:17 Rev Time 0.00
Received By mperson Date 2008-03-06 Time 08:17 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2008-02-20 Cont ID  
Sent By mperson Date 2008-02-20 Time 15:24 Rev Time 0.00
Received By mperson Date 2008-02-20 Time 15:24 Sent To M
Notes
2008-02-20 15:36:21PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED 3RD TIME:
  
 NOTE: THE ORIGINAL GAS PERMIT APPLICATION FROM "A MAN
 SERVICE" PERMT #07061036 WAS NOT IN THE RESIDENTIAL
 GENERATOR PERMT #07061034 RESUBMITTAL, HOWEVER THERE
 WAS A GAS PERMIT APPLICATION SUBMITTED FROM "PALM BEACH
 GENERATOR" WITH NO PERMIT NUMBER ATTACHED. IF IT IS THE
 INTENT TO CHANGE CONTRACTORS OR VOID OUT THE ORIGINAL
 GAS PERMIT PLEASE CALL ADRIANNA MCKENZIE, OCCUPATIONAL
 LICENSE/PERMIT SUPERVISOR @ (561) 805-6681 TO ASSIST IN
 THIS PROCESS.
  
 ***NOTE: PERMITS CAN NOT BE ISSUED UNTIL THE ABOVE
 PROBLEM WITH THE GAS PERMIT IS RESOLVED.****
  
 PREVIOUS PLAN REVIEW COMMENTS OF THE GAS PLANS
 SUBMITTED BY PALM BEACH GENERATOR THAT STILL NEED TO BE
 ADDRESSED:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION *401.1 SCOPE.
 **NOT ALL CUT SECTIONS OF PIPE ARE INDICATING
 CORRESPONDING LENGTHS. PLEASE REFERENCE THE RED CIRCLED
 CUT SECTIONS THAT ARE HIGH LIGHTED YELLOW.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.***UNDERGROUND
 GALVANIZED PIPING IS STILL BEING INDICATED TO THE
 PROPOSED GENERATOR. GALVANIZED PIPING UNDERGROUND IN
 NOT APPROVED. PER FBC FUEL GAS SECTION *404.8
 PROTECTION AGAINST CORROSION.
  
 3. ***OK** COMMENT ADDRESSED.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 **PLEASE REFERENCE COMMENT #1 AND COMPLY.
  
 5. **OK** COMMENT ADDRESSED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-01-29 Cont ID  
Sent By mperson Date 2008-01-29 Time 10:19 Rev Time 0.00
Received By mperson Date 2008-01-29 Time 10:19 Sent To B
Notes
2008-01-29 11:01:53PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED 2ND TIME:
  
 NOTE: THE ORIGINAL GAS PERMIT APPLICATION FROM "A MAN
 SERVICE" PERMT #07061036 WAS NOT IN THE RESIDENTIAL
 GENERATOR PERMT #07061034 RESUBMITTAL, HOWEVER THERE
 WAS A GAS PERMIT APPLICATION SUBMITTED FROM "PALM BEACH
 GENERATOR" WITH NO PERMIT NUMBER ATTACHED. IF IT IS THE
 INTENT TO CHANGE CONTRACTORS OR VOID OUT THE ORIGINAL
 GAS PERMIT PLEASE CALL ADRIANNA MCKENZIE, OCCUPATIONAL
 LICENSE/PERMIT SUPERVISOR @ (561) 805-6681 TO ASSIST IN
 THIS PROCESS.
  
 THE FOLLOWING IS A PLAN REVIEW OF THE GAS PLANS
 SUBMITTED BY PALM BEACH GENERATOR:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION *401.1 SCOPE.
 **NOT ALL CUT SECTIONS OF PIPE ARE INDICATING
 CORRESPONDING LENGTHS. PLEASE REFERENCE THE RED CIRCLED
 CUT SECTIONS THAT ARE HIGH LIGHTED YELLOW. THE EXISTING
 GAS IS NOT BEING INDICATED, PLEASE SEE PERMIT
 INFORMATION INDICATING EXISTING GAS TO A TANKLESS WATER
 HEATER.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.**GALVANIZED
 PIPING UNDERGROUND IN NOT APPROVED. PER FBC FUEL GAS
 SECTION *404.8 PROTECTION AGAINST CORROSION.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 **THIS INCLUDES THE GAS TO THE EXISING TANKLESS WATER
 HEATER.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 **THIS INCLUDES GAS TO THE EXISTING GAS TANLESS WATER
 HEATER.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 **NOTE: IF GAS SYSTEM DELIVERY PRESSURE NEEDS TO BE
 INCREASED TO 2 PSI WITH THE ADDITION OF THE EXISTING
 TANKLESS WATER HEATER PLEASE SUBMIT TWO COPIES OF THE
 MP REGULATORS INDICATING THE MAKE, MODEL NUMBER, BTU
 LOAD CAPACITY, AND A LISTING FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-07-18 Cont ID  
Sent By mperson Date 2007-07-18 Time 14:23 Rev Time 0.33
Received By mperson Date 2007-07-18 Time 14:23 Sent To B
Notes
2007-07-18 14:33:31DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THIS INCLUDES THE EXISTING GAS SYSTEM.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: THIS INCLUDES THE EXISTING GAS SYSTEM.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THIS INCLUDES THE EXISTING GAS SYSTEM.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 10. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING (GAS ISOMETRIC) SHALL CLEARLY PRINT AND
 SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL- [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-02-29 Cont ID  
Sent By adarroug Date 2008-02-29 Time 10:45 Rev Time 0.00
Received By adarroug Date 2008-02-29 Time 10:45 Sent To G
Notes
2008-02-29 10:46:12TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-02-12 Cont ID  
Sent By adarroug Date 2008-02-12 Time 16:58 Rev Time 0.00
Received By adarroug Date 2008-02-12 Time 16:58 Sent To E
Notes
2008-02-12 16:59:24TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-17 Cont ID  
Sent By shill Date 2008-01-17 Time 15:53 Rev Time 0.00
Received By shill Date 2008-01-17 Time 15:53 Sent To Z
Notes
2008-01-17 15:53:15TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-08-09 Time   Rev Time 0.00
Received By adarroug Date 2007-07-02 Time 16:11 Sent To  
Notes
2007-07-02 16:11:54TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-02-22 Cont ID  
Sent By tgordon Date 2008-02-22 Time 09:34 Rev Time 0.25
Received By tgordon Date 2008-02-22 Time 09:34 Sent To  
Notes
2008-02-22 09:36:34*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT
 PERMANENTLY INSTALLED EQUIPMENT POWERED BY INTERNAL
 COMBUSTION ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA
 37.NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES: 4.1.4ENGINES
 (GENERATORS) LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT
 FROM OPENINGS IN WALLS & AT LEAST 5 FT FROM STRUCTURES
 HAVING COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT
 REQUIRED WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF
 ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS,
 AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1
 EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES
 OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION
 INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS
 LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE
 TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF
 STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL
 EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK,
 GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED
 CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E.
 FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES
 AROUND EQUIPMENT FOR SERVICING,AND PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-01-28 Cont ID  
Sent By tgordon Date 2008-01-28 Time 11:37 Rev Time 0.20
Received By tgordon Date 2008-01-28 Time 11:37 Sent To G
Notes
2008-01-28 11:39:37PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-07-05 Cont ID  
Sent By tgordon Date 2007-07-05 Time 11:47 Rev Time 0.20
Received By tgordon Date 2007-07-05 Time 11:47 Sent To E
Notes
2007-07-05 11:48:59*** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 3 Status P Date 2008-05-29 Cont ID  
Sent By choops Date 2008-05-29 Time 11:13 Rev Time 0.00
Received By choops Date 2008-05-29 Time 11:13 Sent To PC
Notes
2008-05-29 11:14:18***APPROVED - REVISION - CHANGING GENERATOR LOCATION
 (SIDE SETBACK)***

Review Stop Z ZONING
Rev No 2 Status P Date 2008-01-24 Cont ID  
Sent By choops Date 2008-01-24 Time 09:04 Rev Time 0.00
Received By choops Date 2008-01-24 Time 09:04 Sent To E
Notes
2008-01-24 09:05:21***APPROVED - RESUB #1***
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-07-05 Cont ID  
Sent By choops Date 2007-07-05 Time 08:23 Rev Time 0.00
Received By choops Date 2007-07-05 Time 08:23 Sent To E
Notes
2007-07-05 08:35:55***FAILED***
  
  
 1)PLEASE PROVIDE SETBACK DIMENSIONS FROM THE
 PROPERTY LINES TO THE EDGE OF THE GENERATOR.
  
 NOTE:MUST BE A MINIMUM OF 21' FROM THE GENERATOR TO
 THE FRONT PROPERTY LINE (OLIVE AVE.)MECHANICAL
 EQUIPMENT MAY ENCROACH 4' INTO A REQUIRED SETBACK.THE
 OLIVE AVE SIDE IS CONSIDERED THE FRONT OF THE LOT...IT
 IS THE SHORTEST WIDTH WITH STREET FRONTAGE, THEREFORE
 HAS A REQUIRED SETBACK OF 25' TO THE PRINCIPAL
 BUILDING.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720