Plan Review Stops For Permit 07060950 |
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2007-11-19 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-11-19 |
Time |
12:50 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-11-19 |
Time |
12:48 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2007-11-05 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-11-05 |
Time |
12:26 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-11-05 |
Time |
12:19 |
Sent To |
FIRE |
|
Notes |
2007-11-05 12:26:10 | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 | | FS, RESPECTIVELY.THE CONTRACTOR OF RECORD MAY BE THE | | DESIGN PROFESSIONAL IF EXEMPTIONS UNDER CHAPTER | | 471.003, FLORIDA STATUTES, IF EXEMPTIONS APPLY. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2007-07-11 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2007-07-11 |
Time |
13:41 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2007-07-11 |
Time |
13:33 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2007-11-19 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-11-19 |
Time |
13:28 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-11-19 |
Time |
13:05 |
Sent To |
|
|
Notes |
2007-11-19 13:15:51 | *****APPROVED***** | | | | ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | BEEN ADDRESSED.THE PLAN SHEET STAMPED, INITIALED, AND | | DATED;READY FOR PERMIT ISSUANCE. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2007-11-05 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-11-05 |
Time |
14:50 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-11-05 |
Time |
14:37 |
Sent To |
|
|
Notes |
2007-11-05 14:50:30 | *****UNSAT***** | | | | *NEW COMMENT | | | | THE PROJECT SITE ADDRESS IN THE TITLE BLOCK OF THE NEW | | SUBMITTED PLAN SHEETS (501 SO. FLAGLER) NEEDS TO | | REFLECT THE ADDRESS ON THE PERMIT APPLICATION OR | | RECORDED IN THE PERMITTING SYSTEM OF 505 SO. FLAGLER. | | | | *ALL OTHER COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW | | HAVE BEEN ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2007-09-14 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-09-14 |
Time |
10:08 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-09-13 |
Time |
18:10 |
Sent To |
|
|
Notes |
2007-09-14 10:07:09 | *****DENIED***** | | | | PLEASE BE ADVISED THAT WEST PALM BEACH FIRE PREVENTION | | BUREAU HAS SPOKEN TO ATF IN REGARDS TO THIS MATTER AND | | WILL BE PERFORMING A SITE INSPECTION THE WEEK OF | | SEPTEMBER 17 - 24 (AS PER FIRE MARSHAL MIKE CARSILLO | | 561-804-4709) | | | | *THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | REVIEW STILL NEED TO BE ADDRESSED: | | | | 1.DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO | | BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS | | CONTROL SYSTEM PROVIDED THAT THE CRITERIA OF NFPA 101, | | 2003 EDITION, 7.2.1.6.2 ARE MET.PLEASE EXPLAIN (AS | | PER THE PLAN NOTES): STRIKES THAT ARE NOT FREE EGRESS | | DOORS MUST REMAIN IN THE LOCK DOWN MODE. | | | | 2.THE NUMBER OF DOOR HARDWARE APPLIANCES ACTUALLY | | SEEN ON THE PLAN DOES NOT CORRELATE WITH WHAT IS | | DESCRIBED ON THE APPLICATION. | | | | 3.IS THIS FLOOR AND (OR) TENANT SPACE A CHANGEFROM | | THAT OF A BUSINESS OCCUPANCY TO THAT OF A NEW DETENTION | | AND CORECTIONAL OCCUPANCY? | | | | *NEW COMMENT: | | | | A.ILLUSTRATE EXIT ACCESS AND EXIT DOOR LOCATION BY | | WAY OF EXIT SIGN(S). | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS | | ADDRESSED | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2007-07-23 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-07-23 |
Time |
16:30 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-07-23 |
Time |
15:06 |
Sent To |
|
|
Notes |
2007-07-23 16:29:50 | *****DENIED***** | | | | | | 1.DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO | | BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS | | CONTROL SYSTEM PROVIDED THAT THE CRITERIA OF NFPA 101, | | 2003 EDITION, 7.2.1.6.2 ARE MET.PLEASE EXPLAIN (AS | | PER THE PLAN NOTES): STRIKES THAT ARE NOT FREE EGRESS | | DOORS MUST REMAIN IN THE LOCK DOWN MODE. | | | | 2.THE NUMBER OF DOOR HARDWARE APPLIANCES ACTUALLY | | SEEN ON THE PLAN DOES NOT CORRELATE WITH WHAT IS | | DESCRIBED ON THE APPLICATION. | | | | 3.IS THIS FLOOR AND (OR) TENANT SPACE A CHANGEFROM | | THAT OF A BUSINESS OCCUPANCY TO THAT OF A NEW DETENTION | | AND CORECTIONAL OCCUPANCY? | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-11-14 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-14 |
Time |
12:19 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-14 |
Time |
12:19 |
Sent To |
E |
|
Notes |
2007-11-14 12:20:38 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-11-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-11-02 |
Time |
10:53 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-11-02 |
Time |
10:53 |
Sent To |
E |
|
Notes |
2007-11-02 10:54:11 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2007-08-30 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-08-30 |
Time |
15:59 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-08-30 |
Time |
15:59 |
Sent To |
FIRE |
|
Notes |
2007-08-30 16:00:14 | TO "F" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2007-07-23 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-07-23 |
Time |
15:06 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-06-29 |
Time |
09:18 |
Sent To |
|
|
Notes |
2007-06-29 09:18:58 | TO "E" BOX |
|
|