Plan Review Details - Permit 07060950
Plan Review Stops For Permit 07060950
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-11-19 Cont ID  
Sent By btrobaug Date 2007-11-19 Time 12:50 Rev Time 0.00
Received By btrobaug Date 2007-11-19 Time 12:48 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-11-05 Cont ID  
Sent By btrobaug Date 2007-11-05 Time 12:26 Rev Time 0.00
Received By btrobaug Date 2007-11-05 Time 12:19 Sent To FIRE
Notes
2007-11-05 12:26:10 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.THE CONTRACTOR OF RECORD MAY BE THE
 DESIGN PROFESSIONAL IF EXEMPTIONS UNDER CHAPTER
 471.003, FLORIDA STATUTES, IF EXEMPTIONS APPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-07-11 Cont ID  
Sent By btrobaug Date 2007-07-11 Time 13:41 Rev Time 0.00
Received By btrobaug Date 2007-07-11 Time 13:33 Sent To FIRE
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-11-19 Cont ID  
Sent By mawillia Date 2007-11-19 Time 13:28 Rev Time 0.00
Received By mawillia Date 2007-11-19 Time 13:05 Sent To  
Notes
2007-11-19 13:15:51*****APPROVED*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED.THE PLAN SHEET STAMPED, INITIALED, AND
 DATED;READY FOR PERMIT ISSUANCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-11-05 Cont ID  
Sent By mawillia Date 2007-11-05 Time 14:50 Rev Time 0.00
Received By mawillia Date 2007-11-05 Time 14:37 Sent To  
Notes
2007-11-05 14:50:30*****UNSAT*****
  
 *NEW COMMENT
  
 THE PROJECT SITE ADDRESS IN THE TITLE BLOCK OF THE NEW
 SUBMITTED PLAN SHEETS (501 SO. FLAGLER) NEEDS TO
 REFLECT THE ADDRESS ON THE PERMIT APPLICATION OR
 RECORDED IN THE PERMITTING SYSTEM OF 505 SO. FLAGLER.
  
 *ALL OTHER COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW
 HAVE BEEN ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-09-14 Cont ID  
Sent By mawillia Date 2007-09-14 Time 10:08 Rev Time 0.00
Received By mawillia Date 2007-09-13 Time 18:10 Sent To  
Notes
2007-09-14 10:07:09*****DENIED*****
  
 PLEASE BE ADVISED THAT WEST PALM BEACH FIRE PREVENTION
 BUREAU HAS SPOKEN TO ATF IN REGARDS TO THIS MATTER AND
 WILL BE PERFORMING A SITE INSPECTION THE WEEK OF
 SEPTEMBER 17 - 24 (AS PER FIRE MARSHAL MIKE CARSILLO
 561-804-4709)
  
 *THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
 1.DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS
 CONTROL SYSTEM PROVIDED THAT THE CRITERIA OF NFPA 101,
 2003 EDITION, 7.2.1.6.2 ARE MET.PLEASE EXPLAIN (AS
 PER THE PLAN NOTES): STRIKES THAT ARE NOT FREE EGRESS
 DOORS MUST REMAIN IN THE LOCK DOWN MODE.
  
 2.THE NUMBER OF DOOR HARDWARE APPLIANCES ACTUALLY
 SEEN ON THE PLAN DOES NOT CORRELATE WITH WHAT IS
 DESCRIBED ON THE APPLICATION.
  
 3.IS THIS FLOOR AND (OR) TENANT SPACE A CHANGEFROM
 THAT OF A BUSINESS OCCUPANCY TO THAT OF A NEW DETENTION
 AND CORECTIONAL OCCUPANCY?
  
 *NEW COMMENT:
  
 A.ILLUSTRATE EXIT ACCESS AND EXIT DOOR LOCATION BY
 WAY OF EXIT SIGN(S).
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-23 Cont ID  
Sent By mawillia Date 2007-07-23 Time 16:30 Rev Time 0.00
Received By mawillia Date 2007-07-23 Time 15:06 Sent To  
Notes
2007-07-23 16:29:50*****DENIED*****
  
  
 1.DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS
 CONTROL SYSTEM PROVIDED THAT THE CRITERIA OF NFPA 101,
 2003 EDITION, 7.2.1.6.2 ARE MET.PLEASE EXPLAIN (AS
 PER THE PLAN NOTES): STRIKES THAT ARE NOT FREE EGRESS
 DOORS MUST REMAIN IN THE LOCK DOWN MODE.
  
 2.THE NUMBER OF DOOR HARDWARE APPLIANCES ACTUALLY
 SEEN ON THE PLAN DOES NOT CORRELATE WITH WHAT IS
 DESCRIBED ON THE APPLICATION.
  
 3.IS THIS FLOOR AND (OR) TENANT SPACE A CHANGEFROM
 THAT OF A BUSINESS OCCUPANCY TO THAT OF A NEW DETENTION
 AND CORECTIONAL OCCUPANCY?
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-14 Cont ID  
Sent By adarroug Date 2007-11-14 Time 12:19 Rev Time 0.00
Received By adarroug Date 2007-11-14 Time 12:19 Sent To E
Notes
2007-11-14 12:20:38TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-02 Cont ID  
Sent By adarroug Date 2007-11-02 Time 10:53 Rev Time 0.00
Received By adarroug Date 2007-11-02 Time 10:53 Sent To E
Notes
2007-11-02 10:54:11TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-30 Cont ID  
Sent By adarroug Date 2007-08-30 Time 15:59 Rev Time 0.00
Received By adarroug Date 2007-08-30 Time 15:59 Sent To FIRE
Notes
2007-08-30 16:00:14TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-23 Cont ID  
Sent By mawillia Date 2007-07-23 Time 15:06 Rev Time 0.00
Received By mawillia Date 2007-06-29 Time 09:18 Sent To  
Notes
2007-06-29 09:18:58TO "E" BOX