Plan Review Details - Permit 07060854
Plan Review Stops For Permit 07060854
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-09-12 Cont ID  
Sent By mcarsill Date 2007-09-12 Time 09:16 Rev Time 0.00
Received By mcarsill Date 2007-09-12 Time 09:13 Sent To  
Notes
2007-09-12 09:16:131. ENTIRE INSTALLATION WHEN COMPLETE IS SUBJECT TO
 FIELD VERIFICATION AND APPROVAL BY THIS OFFICE.
  
 MIKE CARSILLO, BATTALION CHIEF
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-11 Cont ID  
Sent By mcarsill Date 2007-07-11 Time 09:47 Rev Time 0.00
Received By mcarsill Date 2007-07-11 Time 09:10 Sent To  
Notes
2007-07-11 09:47:201. ENTIRE BUILDING IS TO BE COMPLETELY FIRE SPRINKLER
 PROTECTED. THIS PROTECTION SHALL INCLUDE ALL
 MECHANICAL, ELECTRICAL, PLUMBING, ELEVATOR AND JANITOR
 EQUIPMENT ROOMS.
  
 2. NO ARCHITECTURAL FEATURES OF THE BUILDING SHALL NOT
 INTERFERE WITH THE OPERATION OF ANY FIRE SPRINKLER
 HEADS.
  
 3. EACH FIRE DEPARTMENT CONNECTION DISPLAYED SHALL BE
 EQUIPPED WITH KNOX-BOX LOCKING CAPS.
  
 4. ON SEVERAL SHEETS, KEY NOTE # 6 "FS WATER CURTAIN 6"
 ON CENTER" ARE DISPLAYED. IT APPEARS IN SOME AREAS THAT
 THIS WATER CURTAIN IS PROTECTING DOOR OPENINGS.
 TYPICALLY WATER CURTAINS ARE USED TO PROTECT WINDOW
 WALLS BUT NOT OPERABLE DOORS. PLEASE PROVIDE RATIONALE
 FOR THIS DESIGN AT DOOR OPENINGS AND BE AVAILABLE TO
 DEMONSTRATE CODE ALLOWANCES FOR THIS ACTIVITY.
  
 5. ALL CONTROL VALVES AND TAMPER SWITCHES SHALL BE
 PROVIDED WITH APPROPRIATE SIGNAGE.
  
 6. NO FIRE SPRINKLER PROTECTION DISPLAYED IN DIMMER
 CLOSET DISPLAYED ON PAGE FP1-1.1.
  
 7. PUMP ROOM DOORS SHALL NOT INTERFERE WITH CONNECTION
 TO THE FDC SHOWN ON PAGE FP1-1.1.
  
 8. THE ENTIRE FIRE SPRINKLER SYSTEM AND FIRE PUMP
 ASSEMBLY SHALL BE INSTALLED TO CODE AND IN AN APPROVED
 WORKMANLIKE MANNER.
  
 9. THE FIRE SPRINKLER HEAD IN MECHANICAL ROOM AND
 JANITOR CLOSET NEAR STAIR # 12 DISPLAYED ON PAGE
 FP1-1.2 DOES NOT APPEAR TO BE CONNECTED TO ANY FIRE
 SPRINKLER PIPING.
  
 10. TWO SMALL AREAS EQUIPPED WITH DOORS ARE ABSENT OF
 FIRE SPRINKLER HEADS (BOTTOM CENTER) ON PAGE FP1-3.1.
  
 11. PLEASE CONTACT THIS OFFICE TO DISCUSS STANDPIPE
 SYSTEM LOCATED BEHIND DOOR ON PAGE FP1-3.2.
  
 12. FIRE SPRINKLER PROTECTION SHALL BE PROVIDED
 UNDERNEATH AIR CONDITIONING DUCTS OVER FOUR FEET WIDE.
  
 13. AREAS PLANNED FOR STORAGE LOCATED UNDERNEATH ANY
 STAIRS SHALL BE PROVIDED WITH FIRE SPRINKLER
 PROTECTION.
  
 14. ALL FIRE SPRINKLER BULK MAINS AND BRANCH LINES
 SHALL BE PROPERLY SUPPORTED WITH THE APPROPRIATE
 DEVICES.
  
  
 MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-09-11 Cont ID  
Sent By adarroug Date 2007-09-11 Time 11:19 Rev Time 0.00
Received By adarroug Date 2007-09-11 Time 11:19 Sent To FIRE
Notes
2007-09-11 11:19:39TO "MWILLIAMS" DESK/FOR MIKE CARSILLO TO DO REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-11 Cont ID  
Sent By mawillia Date 2007-07-11 Time 09:52 Rev Time 0.00
Received By mawillia Date 2007-06-27 Time 11:20 Sent To  
Notes
2007-06-27 11:20:51TO "F" BOX