2007-07-11 09:47:20 | 1. ENTIRE BUILDING IS TO BE COMPLETELY FIRE SPRINKLER |
| PROTECTED. THIS PROTECTION SHALL INCLUDE ALL |
| MECHANICAL, ELECTRICAL, PLUMBING, ELEVATOR AND JANITOR |
| EQUIPMENT ROOMS. |
| |
| 2. NO ARCHITECTURAL FEATURES OF THE BUILDING SHALL NOT |
| INTERFERE WITH THE OPERATION OF ANY FIRE SPRINKLER |
| HEADS. |
| |
| 3. EACH FIRE DEPARTMENT CONNECTION DISPLAYED SHALL BE |
| EQUIPPED WITH KNOX-BOX LOCKING CAPS. |
| |
| 4. ON SEVERAL SHEETS, KEY NOTE # 6 "FS WATER CURTAIN 6" |
| ON CENTER" ARE DISPLAYED. IT APPEARS IN SOME AREAS THAT |
| THIS WATER CURTAIN IS PROTECTING DOOR OPENINGS. |
| TYPICALLY WATER CURTAINS ARE USED TO PROTECT WINDOW |
| WALLS BUT NOT OPERABLE DOORS. PLEASE PROVIDE RATIONALE |
| FOR THIS DESIGN AT DOOR OPENINGS AND BE AVAILABLE TO |
| DEMONSTRATE CODE ALLOWANCES FOR THIS ACTIVITY. |
| |
| 5. ALL CONTROL VALVES AND TAMPER SWITCHES SHALL BE |
| PROVIDED WITH APPROPRIATE SIGNAGE. |
| |
| 6. NO FIRE SPRINKLER PROTECTION DISPLAYED IN DIMMER |
| CLOSET DISPLAYED ON PAGE FP1-1.1. |
| |
| 7. PUMP ROOM DOORS SHALL NOT INTERFERE WITH CONNECTION |
| TO THE FDC SHOWN ON PAGE FP1-1.1. |
| |
| 8. THE ENTIRE FIRE SPRINKLER SYSTEM AND FIRE PUMP |
| ASSEMBLY SHALL BE INSTALLED TO CODE AND IN AN APPROVED |
| WORKMANLIKE MANNER. |
| |
| 9. THE FIRE SPRINKLER HEAD IN MECHANICAL ROOM AND |
| JANITOR CLOSET NEAR STAIR # 12 DISPLAYED ON PAGE |
| FP1-1.2 DOES NOT APPEAR TO BE CONNECTED TO ANY FIRE |
| SPRINKLER PIPING. |
| |
| 10. TWO SMALL AREAS EQUIPPED WITH DOORS ARE ABSENT OF |
| FIRE SPRINKLER HEADS (BOTTOM CENTER) ON PAGE FP1-3.1. |
| |
| 11. PLEASE CONTACT THIS OFFICE TO DISCUSS STANDPIPE |
| SYSTEM LOCATED BEHIND DOOR ON PAGE FP1-3.2. |
| |
| 12. FIRE SPRINKLER PROTECTION SHALL BE PROVIDED |
| UNDERNEATH AIR CONDITIONING DUCTS OVER FOUR FEET WIDE. |
| |
| 13. AREAS PLANNED FOR STORAGE LOCATED UNDERNEATH ANY |
| STAIRS SHALL BE PROVIDED WITH FIRE SPRINKLER |
| PROTECTION. |
| |
| 14. ALL FIRE SPRINKLER BULK MAINS AND BRANCH LINES |
| SHALL BE PROPERLY SUPPORTED WITH THE APPROPRIATE |
| DEVICES. |
| |
| |
| MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION |
| 804-4709 PHONE |
| 804-4774 FAX |